Page 2
SPECIFICATIONS
Gas
Heating
Performance
Model No.
SL297UH040NV36B
SL297UH060NV36B
1
AFUE
97.5%
97.5%
High
Fire
Input - Btuh
40,000
60,000
Output - Btuh
39,000
58,000
Temperature rise range - °F
30-60
50-80/25-55
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5
3.5
Low
Fire
Input - Btuh
26,000
39,000
Output - Btuh
25,000
38,000
Temperature rise range - °F
20 - 50
25 - 55
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
1.5
1.5
High static - in. w.g.
Heating
0.8
0.8
Cooling
1.0
1.0
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
with furnished 90° street elbow
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d.
3/4 slip x 3/4 MPT
3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nominal diameter x width - in.
10 x 9
10 x 9
Motor output - hp
1/2
1/2
Tons of add-on cooling
2 - 3
2 - 3
Air Volume Range - cfm
440-1370
475-1380
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
7.7
7.7
Maximum overcurrent protection
15
15
Shipping Data
lbs. - 1 package
125
130
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Gas
Heating
Performance
Model No.
SL297UH080NV48C
SL297UH080NV60C
1
AFUE
97.5%
97.5%
High
Fire
Input - Btuh
80,000
80,000
Output - Btuh
78,000
78,000
Temperature rise range - °F
45-75
40-70
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5
3.5
Low
Fire
Input - Btuh
52,000
52,000
Output - Btuh
51,000
51,000
Temperature rise range - °F
30 - 60
25 - 55
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
1.5
1.5
High static - in. w.g.
Heating
0.8
0.8
Cooling
1.0
1.0
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
with furnished 90° street elbow
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d.
3/4 slip x 3/4 MPT
3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nominal diameter x width - in.
11 x 11
11 x 11
Motor output - hp
3/4
1
Tons of add-on cooling
2.5 - 4
3 - 5
Air Volume Range - cfm
620-1730
870-2285
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
10.1
12.8
Maximum overcurrent protection
15
15
Shipping Data
lbs. - 1 package
154
156
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.