NOTE: DIAGRAMS AND ILLUSTRATIONS ARE REPRESENTATIVE AND ARE NOT DRAWN TO SCALE.
www.LennoxHearthProducts.com
8
Figure 8-2
fRAMINg dIMENSIONS
Construct framing with 2x4 or larger lumber.
Note: Illustration provided for dimension information only.
Fireplace must be adequately framed and supported.
A = Required frame opening width. (
1/2 of A
= horizontal centerline
of
fireplace
and vent framing opening. See EXTERIOR WALL
OPENING FRAMING section.)
B = Required frame opening depth with 1/2" (13mm) thick wall finish
material. For other wall finish thicknesses, adjust frame opening
depth and nailing flanges accordingly (see UNIT NAILING FLANGES
section).
C = Min. frame opening height (from base of appliance to header).
d = Min. height from appliance base to vertical centerline of
horizontal termination vent pipe (with 6" straight vent section and
90° elbow off appliance vent collar). (Note: The vertical centerline
of the horizontal termination vent pipe is NOT the same as the
vertical centerline of the vent frame opening because of firestop/
spacer offset. See ExtErIor WALL oPENING FrAMING section.
E = Min. height from appliance base front to ceiling.
f = Mounting platform (Note: Mount appliance on a fully supported
platform extending full width and depth of unit.)
B
7
(178)
5-1/8
(130)
12-1/8
(308)
10-1/2
(267)
Note: Illustration provided for dimension information only. Fireplace must be adequately framed and supported.
A = Required frame opening width. (
1/2 of A
= horizontal centerline of fireplace and vent framing opening.)
B = Required frame opening depth with 1/2" (13mm) thick wall finish material. For other wall finish thicknesses,
adjust frame opening depth and nailing flanges accordingly (see “Unit Nailing Flanges” section).
C = Min. frame opening height (from base of appliance to header).
D = Min. height from appliance base to vertical centerline of horizontal termination vent pipe (with 6" straight vent
section and 90° elbow off appliance vent collar). (Note: Vertical centerline of horizontal termination vent pipe
is NOT the same as vertical centerline of vent frame opening. ecause of firestop/spacer offset.
See “Exterior Wall Opening Framing” section.)
E = Min. height from appliance base (front) to ceiling.
F = Mounting platform (Note: Mount appliance on fully supported platform extending full width and depth of unit.)
65
(1651)
E
C
D
inches
(millimeters)
CE
ILI
NG
F
~
A
1/2 of A
framing dimensions
Model
Unit
A
B
C
d
RHAP54N
in.
65-3/4 18-1/2 46-3/4 48-1/4
mm
1670
470
1184
1226
Viewable glass Size
RHAP54N
50" Wide
14-3/4" High
Figure 8-1
fIREPLACE dIMENSIONS
Vent Collar Size
4-1/2" Inner / 7-1/2" Outer
9-7/8
(251)
32-1/2
(823)
64-3/4
(1645.9)
36-3/8
(923.8)
18-1/2
(471.2)
9-3/8
(238.1)
TOP VIEW
FRONT VIEW (with Spacers installed)
RIGHT SIDE VIEW
Inches
(millimeters)
Top/Bottom
Nailing
langes
IMPORTANT!
Before installing fireplace,
nailing flanges MUST be
ad justed according to finish
(cleanface or surround) and
wall finish material thickness.
This is critical to ensure proper
fireplace location, especially
if installing optional Surround
and Bezel. See next page.
Assemble TOP SPACERS
before in stall ing fireplace
(Figure 7-1).
LENNOX HEARTH PRODUCTS • RHAPSODY™ LINEAR DIRECT-VENT GAS FIREPLACES (MODEL RHAP54N) • INSTALLATION INSTRUCTIONS
LOCATION ANd fRAMINg
(CONTINUEd)