background image

Page 14

IV−Charging

System Performance

For maximum performance of this cooling system, the
operating temperatures and pressure should be checked
and subcooling determined at Standard ARI test conditions
of 82

_

 F outdoor temperature / 80

_

 F indoor dry bulb / 67

_

 F

indoor wet bulb. If subcooling measured deviates from
values in table 6, refrigerant charge should be adjusted
accordingly for maximum performance.

TABLE 6

Subcooling Values

Unit Model No.

82

_

F OD / 80

_

F IDDB

/ 67

_

F IDWB

15CHAX−24
15CHAX−30

12

_

15CHAX−36

15

_

15CHAX−42
15CHAX−48
15CHAX−60

10

_

Verify system performance using table 7 as a general guide.
Table 7 should not be used for charging unit. Minor variations
in these pressures may be expected due to differences in
installations. Significant differences could mean that the sys-
tem is not properly charged or that a problem exists with
some component in the system.

Used carefully, this table could serve as a useful service
guide. Data is based on 80

°

F dry bulb / 67

°

F wet bulb return

air. Allow unit operation to stabilize before taking pressure
readings.

Table 7

Normal Operating Pressures

80

°

F db / 67

°

F wb RETURN AIR

Air Temperature Entering Outdoor Coil (

°

F)

UNIT

PRESSURE

65

70

75

80

82

85

90

95

100

105

110

115

15CHAX−24

142

143

144

146

146

147

148

149

150

151

152

153

15CHAX−30

134

136

138

140

141

142

144

146

148

149

151

152

15CHAX−36

Suction

143

144

146

147

148

149

151

152

155

155

157

157

15CHAX−42

Suction

140

140

140

141

141

141

142

142

143

144

145

147

15CHAX−48

140

141

142

144

144

145

146

147

148

149

150

151

15CHAX−60

143

144

145

146

146

147

147

148

149

150

151

152

15CHAX−24

219

242

264

287

296

310

333

355

379

398

430

457

15CHAX−30

232

255

277

300

309

323

345

368

390

408

440

470

15CHAX−36

Liquid

244

268

292

316

326

340

363

369

410

429

461

493

15CHAX−42

Liquid

225

247

269

291

300

314

337

357

383

402

434

457

15CHAX−48

243

264

285

307

315

328

349

370

391

408

440

470

15CHAX−60

257

280

303

326

335

349

372

395

418

436

468

497

V−Maintenance

At the start of each cooling season, this equipment should
be serviced by a qualified technician. Periodic inspection
and maintenance normally consists of changing or cleaning
filters.

Filters

Not supplied. Inspect once a month. Replace disposable or
clean permanent type as necessary. DO NOT replace per-
manent type with disposable.

Motors

Indoor, outdoor fan and vent motors are permanently
lubricated and require no further lubrication. Motors
should be cleaned yearly to prevent the accumulation of
dust and dirt on the windings or motor exterior.

Coil

Dirt and debris should not be allowed to accumulate on the
coil surfaces or other parts in the air conditioning circuit.
Cleaning should be performed as often as necessary. Use a
brush, vacuum cleaner attachment, or other suitable
means. If water is used to clean the coil, be sure the power
to unit is shut off prior to cleaning.

NOTE − Care should be used when cleaning the coil so that
the coil fins are not damaged.

Do not permit the hot condenser air discharge to be ob-
structed by overhanging structures or shrubs.

Содержание Residential Packaged Cooling System 15CHAX

Страница 1: ...ways use service equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life Installation and servi...

Страница 2: ...0 hz 208 230V 1ph 60hz OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Compressor Crankcase Heater 93M04 S S S S S S Compressor Hard Start Kit 10J42 S S S S S p 81J69 S Compressor Time Off Control 47J27 S...

Страница 3: ...r Amps 2 2 2 2 2 2 4 4 4 Indoor Bl M t Rated Load Amps 1 5 1 5 1 5 2 7 2 7 2 7 Blower Motor Locked Rotor Amps 3 3 4 5 5 5 1 Maximum O t Unit only no electric heat 30 30 30 40 50 60 Overcurrent Protect...

Страница 4: ...Page 4 FIGURE 1 15CHAX PARTS ARRANGEMENT FIGURE 2 15CHAX CONTROL BOX DUAL FAN CAPACITOR C12 TRANSFORMER T1 CONTACTOR K1 BLOWER CONTROL A54 SYSTEM OPERATION MONITOR A132...

Страница 5: ...mode See figure 4 Factory settings for the blower speed jumpers are given in the wiring diagram Figure 4 shows the blower control board Use tables 1 2 and 3 to determine the correct air vol ume for op...

Страница 6: ...activated only when W is energized In the backup heat mode the blower continues to operate for 2 minutes after the heating demand is satisfied NOTE Due to the nature of electric heat CFM settings are...

Страница 7: ...0 975 1840 870 1610 760 1380 650 1610 760 1610 760 1610 760 1610 760 1035 490 920 435 805 380 690 325 NORM 1800 850 1600 755 1400 660 1200 565 1400 660 1400 660 1400 660 1400 660 900 425 800 380 700 3...

Страница 8: ...enser fan is not running 4 Return air duct has substantial leakage 5 If low pressure switch is present see Flash Code 1 info Yellow Alert Flash Code 3 Short Cycling Compres sor is running only briefly...

Страница 9: ...the Harmony zone control system Lennox Signatu reStatt or a conventional thermostat Motor rpm is continually adjusted internally to maintain constant static pressure against the blower wheel The cont...

Страница 10: ...ONTROL CONNECTOR J49 BLOWER B3 HARNESS CONNECTORS J49 PIN 1 C1 PIN 2 W W1 PIN 3 C2 PIN 4 Delay PIN 5 Cool PIN 6 Y1 PIN 7 Adjust PIN 8 0ut PIN 9 0 PIN 10 DS PWM PIN 11 Heat PIN 12 R PIN 13 EM W2 PIN 14...

Страница 11: ...rce as shown above 17 Disconnect W2 from ignition control and connect a separate wire between R on transformer and W2 on ignition control 18 Turn on power to unit Blower should operate at HIGH HEATING...

Страница 12: ...the two scrolls fig ure figure 11 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 11 2 As the orbiting motion continues the gas is forced toward the center...

Страница 13: ...limits will automatically close when temperatures return to normal Limit rating will be on front side 2 Heating Element HE1 through HE4 Heating elements are composed of helix wound bare nich rome wire...

Страница 14: ...Suction 140 140 140 141 141 141 142 142 143 144 145 147 15CHAX 48 140 141 142 144 144 145 146 147 148 149 150 151 15CHAX 60 143 144 145 146 146 147 147 148 149 150 151 152 15CHAX 24 219 242 264 287 29...

Страница 15: ...Page 15 VI Wiring Diagram and Sequence of Operation A Unit Diagram...

Страница 16: ...E ELECTRIC HEAT 2ND STAGE 1 1 4 4 3 3 5 5 BLU BLU 1 1 2 2 3 3 4 4 5 5 6 6 208 240 208 240 VOLTAGE VOLTAGE BY OTHERS BY OTHERS BLK BLK YEL YEL RED RED BLU BLU WHT WHT BLK BLK 6 PIN 6 PIN PLUG PLUG Wiri...

Отзывы: