background image

Page 9

B−Blower Compartment

Access panels can easily be removed for service.

1−Blower Wheel

Blower wheel size varies between models. See SPECIFI-
CATIONS.

2−Variable Speed Motor (B3)

15CHAX units use a three-phase, electronically controlled
D.C. brushless motor (controller converts single phase a.c. to
three phase D.C.), with a permanent-magnet-type rotor (fig-
ure 6). Because this motor has a permanent magnet rotor it
does not need brushes like conventional D.C. motors.
Internal components are shown in figure 7. The stator wind-
ings are split into three poles which are electrically connected
to the controller. This arrangement allows motor windings to
turn on and off in sequence by the controller.

A solid-state controller is permanently attached to the
motor. The controller is primarily an A.C. to D.C. convert-
er. Converted D.C. power is used to drive the motor. The
controller contains a microprocessor which monitors
varying conditions inside the motor (such as motor work-
load).

FIGURE 6

BLOWER MOTOR B3

MOTOR

CONTROLLER

SHAFT

J49

J48

BLOWER MOTOR COMPONENTS

FIGURE 7

STATOR

(WINDINGS)

OUTPUT

SHAFT

BEARING

ROTOR

The controller uses sensing devices to sense what position
the rotor is in at any given time. By sensing the position of the
rotor and then switching the motor windings on and off in se-
quence, the rotor shaft turns the blower.

 All blower motors use single phase power. An external
run capacitor is not used. The motor uses permanently
lubricated ball-type bearings.

Internal Operation

Each time the controller switches a stator winding (figure 7) on
and off, it is called a pulse." The length of time each pulse
stays on is called the pulse width." By varying the pulse width ,
the controller varies motor speed (called pulse-width modula-

tion"). This allows for precise control of motor speed and allows
the motor to compensate for varying load conditions as sensed
by the controller. In this case, the controller monitors the static
workload on the motor and varies motor rpm in order to main-
tain constant airflow (cfm).

The motor controller is driven by the blower control
board (figure 4). The board receives its demand (PWM
signal or fixed 24 VAC or VDC signal) from optional controls
such as the Harmony zone control system, Lennox Signatu-
reStat

t

 or a conventional thermostat.

Motor rpm is continually adjusted internally to maintain
constant static pressure against the blower wheel. The control-
ler monitors the static work load on the motor and motor amp-
draw to determine the amount of rpm adjustment. Blower rpm
may be adjusted any amount in order to maintain a constant
cfm as shown in Blower Ratings Tables (1, 2 and 3).  The cfm
remains relatively stable over a broad range of static pressure.
Since the blower constantly adjusts rpm to maintain a specified
cfm, motor rpm is not rated. Hence, the terms cool speed" ,
heat speed "  or speed tap"  if used in this manual, on the unit
wiring diagram and on blower B3, refer to blower cfm regard-
less of motor rpm.

When Harmony is used, speed taps are overridden and a
PWM signal generated by the Harmony controller continuously
varies motor speed based upon zone demands.

Initial Power Up

When line voltage is applied to B3, there will be a large inrush
of power lasting less than 1/4 second. This inrush charges a
bank of DC filter capacitors inside the controller. If the discon-
nect switch is bounced when the disconnect is closed, the dis-
connect contacts may become welded. Try not to bounce the
disconnect switch when applying power to the unit.

Motor Start-Up

When B3 begins start-up, the motor gently vibrates back and
forth for a moment. This is normal. During this time the elec-
tronic controller is determining the exact position of the rotor.
Once the motor begins turning, the controller slowly eases the
motor up to speed (this is called soft-start"). The motor may
take as long as 10-15 seconds to reach full speed. If the motor
does not reach 200rpm within 13 seconds, the motor shuts
down. Then the motor will immediately attempt a restart. The
shutdown feature provides protection in case of a frozen bear-
ing or blocked blower wheel. The motor may attempt to start
eight times. If the motor does not start after the eighth try, the
controller locks out. Reset controller by momentarily turning off
power to unit.

The DC filter capacitors inside the controller are connected
electrically to the speed tap wires. The capacitors take
approximately 5 minutes to discharge when the disconnect
is opened. For this reason it is necessary to wait at least 5
minutes after turning off power to the unit before attempt-
ing to change speed taps.

Содержание Residential Packaged Cooling System 15CHAX

Страница 1: ...ways use service equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life Installation and servi...

Страница 2: ...0 hz 208 230V 1ph 60hz OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Compressor Crankcase Heater 93M04 S S S S S S Compressor Hard Start Kit 10J42 S S S S S p 81J69 S Compressor Time Off Control 47J27 S...

Страница 3: ...r Amps 2 2 2 2 2 2 4 4 4 Indoor Bl M t Rated Load Amps 1 5 1 5 1 5 2 7 2 7 2 7 Blower Motor Locked Rotor Amps 3 3 4 5 5 5 1 Maximum O t Unit only no electric heat 30 30 30 40 50 60 Overcurrent Protect...

Страница 4: ...Page 4 FIGURE 1 15CHAX PARTS ARRANGEMENT FIGURE 2 15CHAX CONTROL BOX DUAL FAN CAPACITOR C12 TRANSFORMER T1 CONTACTOR K1 BLOWER CONTROL A54 SYSTEM OPERATION MONITOR A132...

Страница 5: ...mode See figure 4 Factory settings for the blower speed jumpers are given in the wiring diagram Figure 4 shows the blower control board Use tables 1 2 and 3 to determine the correct air vol ume for op...

Страница 6: ...activated only when W is energized In the backup heat mode the blower continues to operate for 2 minutes after the heating demand is satisfied NOTE Due to the nature of electric heat CFM settings are...

Страница 7: ...0 975 1840 870 1610 760 1380 650 1610 760 1610 760 1610 760 1610 760 1035 490 920 435 805 380 690 325 NORM 1800 850 1600 755 1400 660 1200 565 1400 660 1400 660 1400 660 1400 660 900 425 800 380 700 3...

Страница 8: ...enser fan is not running 4 Return air duct has substantial leakage 5 If low pressure switch is present see Flash Code 1 info Yellow Alert Flash Code 3 Short Cycling Compres sor is running only briefly...

Страница 9: ...the Harmony zone control system Lennox Signatu reStatt or a conventional thermostat Motor rpm is continually adjusted internally to maintain constant static pressure against the blower wheel The cont...

Страница 10: ...ONTROL CONNECTOR J49 BLOWER B3 HARNESS CONNECTORS J49 PIN 1 C1 PIN 2 W W1 PIN 3 C2 PIN 4 Delay PIN 5 Cool PIN 6 Y1 PIN 7 Adjust PIN 8 0ut PIN 9 0 PIN 10 DS PWM PIN 11 Heat PIN 12 R PIN 13 EM W2 PIN 14...

Страница 11: ...rce as shown above 17 Disconnect W2 from ignition control and connect a separate wire between R on transformer and W2 on ignition control 18 Turn on power to unit Blower should operate at HIGH HEATING...

Страница 12: ...the two scrolls fig ure figure 11 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 11 2 As the orbiting motion continues the gas is forced toward the center...

Страница 13: ...limits will automatically close when temperatures return to normal Limit rating will be on front side 2 Heating Element HE1 through HE4 Heating elements are composed of helix wound bare nich rome wire...

Страница 14: ...Suction 140 140 140 141 141 141 142 142 143 144 145 147 15CHAX 48 140 141 142 144 144 145 146 147 148 149 150 151 15CHAX 60 143 144 145 146 146 147 147 148 149 150 151 152 15CHAX 24 219 242 264 287 29...

Страница 15: ...Page 15 VI Wiring Diagram and Sequence of Operation A Unit Diagram...

Страница 16: ...E ELECTRIC HEAT 2ND STAGE 1 1 4 4 3 3 5 5 BLU BLU 1 1 2 2 3 3 4 4 5 5 6 6 208 240 208 240 VOLTAGE VOLTAGE BY OTHERS BY OTHERS BLK BLK YEL YEL RED RED BLU BLU WHT WHT BLK BLK 6 PIN 6 PIN PLUG PLUG Wiri...

Отзывы: