background image

Page 5

I−APPLICATION

15CHAX 2 through 5 ton (7.0 through 17.6kW)  model units
are single phase air conditioning units designed for  outdoor
installation on a slab or roof top.The units are available in two
cabinet sizes. Electric heat can be factory or field installed if
required. Refer to the Engineering Handbook for more spe-
cific application data.

II−UNIT COMPONENTS

15CHAX components are shown in figure 1.  Control box com-
ponents are shown in figure 2.

A−Control Box Components

1−Compressor Contactor K1

K1 is a 24VAC to line voltage s ingle  pole double break contac-
tor, which energizes the compressor in response to thermostat
demand.

2−Control Transformer T1

All 15CHAX series units use line voltage to 24VAC transformer
mounted in the control box. The transformer supplies power to
control circuits in the unit. Transformers use two primary volt-
age taps as shown in figure 3.

FIGURE 3

240 VOLTS

208 VOLTS

PRIMARY

SECONDARY

208 / 240 VOLT TRANSFORMER

24 VOLTS

L1

L2

3−Dual Capacitor C12

The compressor and condenser fan in the 15CHAX series
units use permanent split capacitor motors. The capacitor is lo-
cated in the control box. A dual rated capacitor is used for both
the condenser fan motor and the compressor (see unit wiring
diagram per respective unit). The fan side and the compressor
side of  the capacitor have different MFD ratings. See side of
capacitor for ratings.

4− Blower Control A15

Electric shock hazard. Can cause injury or
death. Before attempting to perform any
service or maintenance, turn the electrical
power to unit OFF at disconnect switch(es).
Unit may have multiple power supplies.

WARNING

!

15CHAX units are equipped with a variable speed motor
that is capable of maintaining a specified CFM throughout
the external static range. A particular CFM can be obtained
by positioning jumpers (

COOL

HEAT

, and 

ADJUST

) on

the blower control board. The HEAT and COOL  jumpers
are labeled A, B, C and D. Each of the numbers corre-
sponds with an air volume (CFM) setting. The 

ADJUST

jumper is labeled Test, −, +, and Norm. The + and − pin set-
tings are used to add or subtract a percentage of the CFM
selected. The Test jumper is used to operate the motor in
the test mode. See figure 4.

Factory settings for the blower speed jumpers are given in
the wiring diagram. Figure 4  shows the blower control
board. Use tables 1, 2 and 3 to determine the correct air vol-
ume for operation in heat and cool mode.

The CFM

 LED located on the blower control board flashes

one time per 100 cfm to indicate selected blower speed.
For example, if the unit is operating at 1000 CFM, 

CFM

 LED

will flash 10 times. If the CFM is 1150, 

CFM

 LED will flash 11

full times plus one fast or half flash.

At times the light may appear to flicker or glow. This takes
place when the control is communicating with the motor be-
tween cycles. This is normal operation.

Read through the jumper settings section before adjusting
the jumper to obtain the appropriate blower speed.

To change jumper positions, gently pull the jumper off the pins
and place it on the desired set of pins. The following section
outlines the different jumper selections available and condi-
tions associated with each one. Refer to figure 4.

After the CFM for each application has been determined,
the jumper settings must be adjusted to reflect those given
in tables 1, 2 and 3. From the tables, determine which row
most closely matches the desired CFM. Once a specific row
has been chosen (+, NORMAL, or −), CFM volumes from
other rows cannot be used. Below are descriptions of the
jumper selections.

The variable speed motor slowly ramps up to and down
from the selected air flow during both cooling and heating
demand. This minimizes noise and eliminates the initial
blast of air when the blower is initially energized.

ADJUST

The 

ADJUST

 pins allow the motor to run at normal speed,

approximately 15 percent higher, or approximately 15 per-
cent lower than normal speed. Tables 1, 2 and 3 give three
rows (+, NORMAL, and −) with their respective CFM vol-
umes. Notice that the normal adjustment setting for cool
speed position D in table 1 is  900 CFM. The + adjustment
setting for that position is 1035 CFM and for the − adjust-
ment setting is 765 CFM. After the adjustment setting has
been determined, choose the remaining speed settings
from those offered in the table in that row.

The TEST pin is available to bypass the blower control and
run the motor at approximately 70 percent to make sure that
the motor is operational. This is used mainly in trouble-
shooting. The G terminal must be energized for the motor to
run.

Содержание Residential Packaged Cooling System 15CHAX

Страница 1: ...ways use service equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life Installation and servi...

Страница 2: ...0 hz 208 230V 1ph 60hz OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Compressor Crankcase Heater 93M04 S S S S S S Compressor Hard Start Kit 10J42 S S S S S p 81J69 S Compressor Time Off Control 47J27 S...

Страница 3: ...r Amps 2 2 2 2 2 2 4 4 4 Indoor Bl M t Rated Load Amps 1 5 1 5 1 5 2 7 2 7 2 7 Blower Motor Locked Rotor Amps 3 3 4 5 5 5 1 Maximum O t Unit only no electric heat 30 30 30 40 50 60 Overcurrent Protect...

Страница 4: ...Page 4 FIGURE 1 15CHAX PARTS ARRANGEMENT FIGURE 2 15CHAX CONTROL BOX DUAL FAN CAPACITOR C12 TRANSFORMER T1 CONTACTOR K1 BLOWER CONTROL A54 SYSTEM OPERATION MONITOR A132...

Страница 5: ...mode See figure 4 Factory settings for the blower speed jumpers are given in the wiring diagram Figure 4 shows the blower control board Use tables 1 2 and 3 to determine the correct air vol ume for op...

Страница 6: ...activated only when W is energized In the backup heat mode the blower continues to operate for 2 minutes after the heating demand is satisfied NOTE Due to the nature of electric heat CFM settings are...

Страница 7: ...0 975 1840 870 1610 760 1380 650 1610 760 1610 760 1610 760 1610 760 1035 490 920 435 805 380 690 325 NORM 1800 850 1600 755 1400 660 1200 565 1400 660 1400 660 1400 660 1400 660 900 425 800 380 700 3...

Страница 8: ...enser fan is not running 4 Return air duct has substantial leakage 5 If low pressure switch is present see Flash Code 1 info Yellow Alert Flash Code 3 Short Cycling Compres sor is running only briefly...

Страница 9: ...the Harmony zone control system Lennox Signatu reStatt or a conventional thermostat Motor rpm is continually adjusted internally to maintain constant static pressure against the blower wheel The cont...

Страница 10: ...ONTROL CONNECTOR J49 BLOWER B3 HARNESS CONNECTORS J49 PIN 1 C1 PIN 2 W W1 PIN 3 C2 PIN 4 Delay PIN 5 Cool PIN 6 Y1 PIN 7 Adjust PIN 8 0ut PIN 9 0 PIN 10 DS PWM PIN 11 Heat PIN 12 R PIN 13 EM W2 PIN 14...

Страница 11: ...rce as shown above 17 Disconnect W2 from ignition control and connect a separate wire between R on transformer and W2 on ignition control 18 Turn on power to unit Blower should operate at HIGH HEATING...

Страница 12: ...the two scrolls fig ure figure 11 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 11 2 As the orbiting motion continues the gas is forced toward the center...

Страница 13: ...limits will automatically close when temperatures return to normal Limit rating will be on front side 2 Heating Element HE1 through HE4 Heating elements are composed of helix wound bare nich rome wire...

Страница 14: ...Suction 140 140 140 141 141 141 142 142 143 144 145 147 15CHAX 48 140 141 142 144 144 145 146 147 148 149 150 151 15CHAX 60 143 144 145 146 146 147 147 148 149 150 151 152 15CHAX 24 219 242 264 287 29...

Страница 15: ...Page 15 VI Wiring Diagram and Sequence of Operation A Unit Diagram...

Страница 16: ...E ELECTRIC HEAT 2ND STAGE 1 1 4 4 3 3 5 5 BLU BLU 1 1 2 2 3 3 4 4 5 5 6 6 208 240 208 240 VOLTAGE VOLTAGE BY OTHERS BY OTHERS BLK BLK YEL YEL RED RED BLU BLU WHT WHT BLK BLK 6 PIN 6 PIN PLUG PLUG Wiri...

Отзывы: