Page 13

1−Condenser Fan

All  15CHAX units use single phase condenser fans. Specifica-
tions for the condenser fans are at the front of this manual. See
figure 12 for fan and motor replacement.

FIGURE

12

hub and shaft
should be flush

fan guard

1 1/2"

2−High Pressure Switch S4

S4 is a N.C. auto−reset high pressure switch located on the
liquid line. The switch shuts off the compressor when liquid
pressure rises above the factory setting. The switch on
15CHAX units is set to open at 590 + 10 psi and close at
418 + 10 psi.

3−Low Pressure Switch (S79)

The low pressure switch is an auto−reset N.C. switch that
opens on pressure drop. The switch is wired in series with
the  high pressure switch S4 and compressor contactor
K1 and is located on the suction line . When suction pres-
sure drops to 10

 

psig

 

(68.95kPa)

 

the switch opens and the

compressor is de−energized. When suction  pressure
rises to 30 psig

 

(206.85 kPa) the pressure switch will

close.

III−Electric Heat
A−Matchups and Ratings

Matchups and ratings are listed with ELECTRICAL  DATA"
See table of contents.

B−Electric Heat Components

See figure 13 for electric heat parts arrangement.

1− Limit Switches 1, 2, 3 and 4

Limit switches 1, 2, 3and 4 are N.C. auto−reset high tempera-
ture limits located on the electric heat vest panel. Each heating
element is wired in series with a high temperature limit. When
the limit opens  the corresponding heating element is de−ener-
gized. All other heating elements remain energized. The limits
will   automatically close when temperatures return to normal.
Limit rating will be on front side.

2−Heating Element HE1 through HE4

Heating elements are composed of helix−wound bare nich-
rome wire exposed directly to the air stream. The elements are
supported by insulators mounted to the wire frame. Each ele-
ment is energized independently by a corresponding relay lo-
cated on the heat vest panel. Once energized, heat transfer is
instantaneous.

FIGURE 13

PHK VESTIBULE PARTS ARRANGEMENT

(PHK−10)

SEQUENCER

RELAY

PRIMARY

LIMITS

TB 2

3−Terminal Strip TB2 PHK−05, −07, −10

For electric heat sections without circuit breakers or fuses, line
voltage connections are made to terminal strip TB2.

4− Sequencer Relays 1 and 2

Relays  1 and 2 are N.O. sequencer  relays with a resistive ele-
ment for a coil and bi−metal disk which actuates the contacts.
The relays are located on the electric heat vest panel and are
energized by a 24V heating demand (W1 and W2) via jack/
plug P2 which is used to connect electric heat to the blower
control circuit. When energized, the internal resistance heats
the bi−metal disk causing the contacts to close. When the relay
is de−energized the disk cools and the contacts open. The re-
lays energize different stages of heat, as well as the blower.
The blower is always first on and last off.

5−Circuit Breaker CB1 and CB2 (option) 

PHK−15, −20,

Line voltage connections are made to circuit breakers CB1 and
CB2 in electric heat sections with circuit breakers. Table 5
shows amp rating for each circuit breaker used. Two−pole cir-
cuit breakers are used.

TABLE 5

Circuit  Breakers

UNIT

CB1 AMPS

CB2 AMPS

PHK15CP

60 AMPS

30 AMPS

PHK20CP

60 AMPS

60 AMPS

Содержание Residential Packaged Cooling System 15CHAX

Страница 1: ...ways use service equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life Installation and servi...

Страница 2: ...0 hz 208 230V 1ph 60hz OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA Compressor Crankcase Heater 93M04 S S S S S S Compressor Hard Start Kit 10J42 S S S S S p 81J69 S Compressor Time Off Control 47J27 S...

Страница 3: ...r Amps 2 2 2 2 2 2 4 4 4 Indoor Bl M t Rated Load Amps 1 5 1 5 1 5 2 7 2 7 2 7 Blower Motor Locked Rotor Amps 3 3 4 5 5 5 1 Maximum O t Unit only no electric heat 30 30 30 40 50 60 Overcurrent Protect...

Страница 4: ...Page 4 FIGURE 1 15CHAX PARTS ARRANGEMENT FIGURE 2 15CHAX CONTROL BOX DUAL FAN CAPACITOR C12 TRANSFORMER T1 CONTACTOR K1 BLOWER CONTROL A54 SYSTEM OPERATION MONITOR A132...

Страница 5: ...mode See figure 4 Factory settings for the blower speed jumpers are given in the wiring diagram Figure 4 shows the blower control board Use tables 1 2 and 3 to determine the correct air vol ume for op...

Страница 6: ...activated only when W is energized In the backup heat mode the blower continues to operate for 2 minutes after the heating demand is satisfied NOTE Due to the nature of electric heat CFM settings are...

Страница 7: ...0 975 1840 870 1610 760 1380 650 1610 760 1610 760 1610 760 1610 760 1035 490 920 435 805 380 690 325 NORM 1800 850 1600 755 1400 660 1200 565 1400 660 1400 660 1400 660 1400 660 900 425 800 380 700 3...

Страница 8: ...enser fan is not running 4 Return air duct has substantial leakage 5 If low pressure switch is present see Flash Code 1 info Yellow Alert Flash Code 3 Short Cycling Compres sor is running only briefly...

Страница 9: ...the Harmony zone control system Lennox Signatu reStatt or a conventional thermostat Motor rpm is continually adjusted internally to maintain constant static pressure against the blower wheel The cont...

Страница 10: ...ONTROL CONNECTOR J49 BLOWER B3 HARNESS CONNECTORS J49 PIN 1 C1 PIN 2 W W1 PIN 3 C2 PIN 4 Delay PIN 5 Cool PIN 6 Y1 PIN 7 Adjust PIN 8 0ut PIN 9 0 PIN 10 DS PWM PIN 11 Heat PIN 12 R PIN 13 EM W2 PIN 14...

Страница 11: ...rce as shown above 17 Disconnect W2 from ignition control and connect a separate wire between R on transformer and W2 on ignition control 18 Turn on power to unit Blower should operate at HIGH HEATING...

Страница 12: ...the two scrolls fig ure figure 11 1 The centrifugal action of the orbiting scroll seals off the flanks of the scrolls figure 11 2 As the orbiting motion continues the gas is forced toward the center...

Страница 13: ...limits will automatically close when temperatures return to normal Limit rating will be on front side 2 Heating Element HE1 through HE4 Heating elements are composed of helix wound bare nich rome wire...

Страница 14: ...Suction 140 140 140 141 141 141 142 142 143 144 145 147 15CHAX 48 140 141 142 144 144 145 146 147 148 149 150 151 15CHAX 60 143 144 145 146 146 147 147 148 149 150 151 152 15CHAX 24 219 242 264 287 29...

Страница 15: ...Page 15 VI Wiring Diagram and Sequence of Operation A Unit Diagram...

Страница 16: ...E ELECTRIC HEAT 2ND STAGE 1 1 4 4 3 3 5 5 BLU BLU 1 1 2 2 3 3 4 4 5 5 6 6 208 240 208 240 VOLTAGE VOLTAGE BY OTHERS BY OTHERS BLK BLK YEL YEL RED RED BLU BLU WHT WHT BLK BLK 6 PIN 6 PIN PLUG PLUG Wiri...

Отзывы: