background image

31

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

LENNOX HEARTH PRODUCTS  •  MERIT PLUS

®

 DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS

Step 10. REMOVING ANd  INSTALLING 

THE GLASS dOOR 

Air Shutter Adjustment Guidelines

Amount of 

Primary Air

Flame 

Color

Air Shutter 

Adjustment

If air shutter is 

closed too far

Flame will 

be orange

Air shutter 

gap should be 

increased

If air shutter is 

open too far

Flame will 

be blue

Air shutter 

gap should be 

decreased

Step 11. BURNER AdJUSTMENTS 

Flame Appearance and Sooting

Proper flame appearance is a flame that is blue 

at the base and becomes yellowish-orange in 

the body of the flame.
When the appliance is first lit, the entire flame 

may be blue and will gradually turn yellowish-

orange during the first 15 minutes of operation. 

If the flame remains blue, or if the flame is 

orange with evidence of sooting (black tip), the 

air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, 

sooting may develop. Sooting is indicated by 

black puffs developing at the tips of very long 

orange flames. Sooting results in black deposits 

forming on the logs, appliance inside surfaces 

and on exterior surfaces adjacent to the vent 

termination. 
Sooting is caused by incomplete combustion 

in the flames and lack of combustion air enter-

ing the air shutter opening. To achieve a warm 

yellowish-orange flame with an orange body 

that does not soot, the shutter opening must be 

adjusted between these two extremes.

Air Shutter Adjustment Guidelines

•  If there is smoke or soot present, first check 

the log set positioning to ensure that the 

flames are not impinging on any of the logs. 

If the log set is properly positioned and a 

sooting condition still exists, then the air 

shutter opening should be increased.

•  The more offsets in the vent system, the larger 

the air shutter opening will need to be.

•  An appliance operated with the air shutter 

opened too far, may have flames that appear 

blue and transparent. These weak, blue and 

transparent flames are termed anemic. 

•  Propane models may exhibit flames which 

candle or appear stringy. If this is present 

and persists, adjust the air shutter to a more 

closed position, then operate the appliance 

for a few more minutes to ensure that the 

flame normalizes and the flames do not 

appear sooty. 

The following chart is provided to aid you in 

achieving the correct air shutter adjustment 

for your installation.

Figure 56

 

Removing the Glass Enclosure Panel 

(see 

Figure 56

Remove the top louver assembly or radiant 

panel. To access the glass door securing latches, 

first open the lower control compartment door 

(

Figure 56

 

) by pushing in simultaneously the 

left and right top corners of the door (the door 

is hinged at the bottom). 

Remove the bottom compartment door by 

sliding the hinge pin, located at the door’s left 

side, to the right until it disengages from the 

left corner post hole. Pull the door diagonally 

to the left, away from the fireplace.

Locate the two (2) latches at the top of the 

control compartment and disengage them from 

the door frame bottom vee-flange, pulling down 

on their handles to open them.

Installing the Glass Enclosure Panel 

(see 

Figure 56

Retrieve the glass door. Visually inspect the 

gasket on the backside of the frame. Gasket 

surface must be clean, free of irregularities 

and seated firmly. 

Position the door in front of the firebox opening 

with the bottom of the door held away from the 

fireplace 

(Figure 56)

. Hook the top flange of the 

door frame over the top of the firebox frame. 

Let the bottom of the door frame swing gently 

in towards the fireplace ensuring that the gasket 

seats evenly as the door frame draws shut. 

Fasten the two latches located underneath the 

firebox floor to the door's vee-flange. Close 

both the latches securely.

Lower Compartment Door and Hinge

Glass Door Frame

Top Flange

Glass

Door

Glass Door Latch

Firebox Floor

Glass Door Frame

Bottom Vee-flange

Only doors certified with the appliance 

shall be used.

Seules des portes certifiées pour cet 

appareil doivent être utilisées.

WARNING: dO NOT abuse glass door by 

striking or slamming shut.

       WARNING 

 

do not attempt to substitute the 

materials used on these doors, 

or replace cracked or broken 

glass. 

• Handle this glass with extreme 

care! Glass is susceptible to 

damage - do not scratch or 

handle roughly while reinstall-

ing the glass door frame.

• The  glass  door  of  this  appli

-

ance must only be replaced 

as a complete unit as provided 

by the manufacturer.  do not 

attempt to replace broken, 

cracked or chipped glass sepa-

rately. 

 

do not attempt to touch the 

front enclosure glass with your 

hands while the fireplace is in 

use.

       WARNING 

do not operate appliance with 

the glass front removed, cracked 

or broken.

       AVERTISSEMENT 

Ne pas utiliser l'appareil si le 

panneau frontal en verre n'est 

pas en place, est craqué ou 

brisé. 

Содержание MPD35CNE

Страница 1: ...fire or explosion may result causing property damage personal injury or death WARNING AVERTISSEMENT AVISO HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLAS...

Страница 2: ...cal Installation Sequence 9 Detailed Installation Steps 9 Step 1 Framing 9 Fireplace and Framing Specifications 10 Step 2 Routing Gas Line 11 Step 3 Preparing Appliance Vent Collar 12 Step 4 Installin...

Страница 3: ...is appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning WARNING Failure to position the parts in accordance with these diagrams or failure to use only par...

Страница 4: ...55 0 052 19L52 MPD40 38 0 102 99K76 0 062 21L01 MPD45 37 0 104 24M10 52 0 0635 37G00 Table 4 Standard size installed at factory Part Cat Number REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSETTS These f...

Страница 5: ...the appliance Cold Climate Insulation For cold climate installations seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room It is especially imp...

Страница 6: ...ents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch H ft H m Flat 6 12 1 0 0 3 6 12 7 12 1 25 0 38 7 12 8 12 1 5 0 46 8 12 9 12 2 0 0 61 9 12 10 12 2 5 0 76 10 12 11 12 3 25 0 99 11 12...

Страница 7: ...er 5 12 7 cm 5 12 7 cm G Clearance to inside corner 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS H Clearancetoeachinsideofcenterlineexten...

Страница 8: ...ve to conform to standard hearth extension installation requirements Shelf Height To provide for the lowest possible shelf surface use the alternate rear vent outlet the venting attached to the top ve...

Страница 9: ...the framing and secure with nailing brackets IMPORTANT Bend up the appropriate header spacing standoffs for the drywall finish material thickness to be used see Figure 11 Bend up the outer pair for 1...

Страница 10: ...lectrical Inlet Knockout requiring a Field Provided Junction Box either side E B D C Front View 3 76 A Header Spacing Top Standoffs Vertical Venting through the Ceiling Frame ceiling opening Use a plu...

Страница 11: ...aming 6 1 2 152 mm Pipe Coupling Recommended NOTE Rear Vent Applications in Corner Installations The horizontal vent length from a to b must not exceed 28 inches 711 mm MPDT33 and MPDR33 Models Dimens...

Страница 12: ...ct Venting System Horizontal or Vertical Withtheappliancesecuredinframing determine ventroutingandidentifytheexteriortermination location The following sections describe vertical roof and horizontal e...

Страница 13: ...4 1 1 0 0 5 0 6 3 8 1 5 2 5 1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1...

Страница 14: ...e radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar refer to Figure 21 Push the vent component againstthecollaruntilitfullyengages...

Страница 15: ...llar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking anyofthepreviouslyconnected...

Страница 16: ...ou are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet Example If 8 feet of H horizontal vent run is needed then 4 feet minimum V vertical vent will be required TABLE A H M...

Страница 17: ...6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This tab...

Страница 18: ...al both the inner and outer pipe elements with the same procedure Sealant and securing screws are not required NOTE An elbow may also be attached to the appliance collar Attach in the same manner as y...

Страница 19: ...4 32 mm as shown in Figure 34 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The vertical distance between the inlet and...

Страница 20: ...owingwallthicknessrange when using SV4 5HT 2 termination kit HORIZONTAL Vent Figures Tables NOTE Secure Vent components rigid vent pipe and terminal are shown in the figures Secure Flex components fle...

Страница 21: ...of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run...

Страница 22: ...al rise except where an elbow is the only vertical component in the system See Figure 36 V Minimum feet feet 5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meter...

Страница 23: ...No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pip...

Страница 24: ...t of 2 conductor wire supplied with the unit NOTE The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed l...

Страница 25: ...eplace The millivolt control valve has a 3 8 10mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is fitted with a 1 2 x 3 8 13 mm x 10 mm NPT fitting Secu...

Страница 26: ...onovertime A Light the appliance refer to the lighting instructionslabelinthecontrolcompartment or in the Care and Operation Instructions manual B Brush all joints and connections with the gas leak te...

Страница 27: ...pli ances to Figure 54 for MPD35 Series appli ancesandtoFigure55forMPD40andMPD45 Series appliances WARNING DO NOT attempt to install the logs until the appliance instal lationhasbeencompleted the gas...

Страница 28: ...firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the hole on its upper end Place the left log and then the smaller...

Страница 29: ...the order shown Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear l...

Страница 30: ...ividual logs as shown below Logs should be placed in the order shown Position the center log on the burner first then place the glowing embers as shown in Figure 52 Place the rear log both the right a...

Страница 31: ...t appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 56 Removing the Glass Enclosure Panel see Figure 56 Remove the to...

Страница 32: ...ireplace rod located in the lower control area Position the air shutter to the factory setting as shown in the table in Figure 60 2 Light appliance follow lighting procedure on lighting label in contr...

Страница 33: ...bustible material may touch top of appliance Combustible materials NOT allowed below this point on face of appliance Header Spacing Top Standoff Top of Appliance Top of Door Frame Hood must be install...

Страница 34: ...er la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la l...

Страница 35: ...6 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate Installation Accessories Liste...

Страница 36: ...T48SS Small Square Termination for flex with 48 1219 mm of compressed flex vent Ref Instr 750204M 94L09 SF HTSS Horizontal Small Square Termination for flex without flex vent Ref Instr 750204M INSTALL...

Страница 37: ...pin located at the door s left side to the right until it disengages from the left corner post hole Pull the control compartment door diagonally to the left away from the fireplace Step 3 Remove the...

Страница 38: ...crews previously removed Step 12 Reinstall the baffle with the two baffle securing screws Step 13 Reassemble the remaining compo nents by reversing the procedures outlined in the Steps 1 5 Step 14 Att...

Отзывы: