LENNOX HEARTH PRODUCTS  •  MERIT PLUS

®

 DIRECT VENT GAS FIREPLACES (MPD33/35/40/45)  •  INSTALLATION INSTRUCTIONS

5 in. (127 mm)

Radius Minimum

Flexible Vent Section

E. Attach Flex Vent to Termination

Secure Flex

 components can be purchased 

separately and attached to bulk lengths of 

Secure Flex

 flexible tubing cut to size at the 

job site. Secure the flexible vent to the 

Secure 

Flex

 terminations in the same manner (see

 

Figure 42

as it was attached to the adaptor.

NOTE:  Secure  Flex  vent  must  be  attached 

to  Secure  Flex  terminations  only.  DO  NOT 

substitute Secure Vent terminations or 

the  Secure  Vent  adaptor  for  Secure  Flex 

components.  The  collars  of  Secure  Flex 

terminations and adaptors have a different 

circumference than what is used with the 

Secure Vent pipe. Additionally, Secure Flex 

components have an extended length center 

tube for use in attaching the flexible vent.

See the appropriate sections and figures 

shown throughout the venting section for 

their installation requirments. 

Figure 43 

VERTICAL OR HORIZONTAL VENTING USING 

SECURE FlEx

®

 KITS ANd COMPONENTS

Secure Flex

®

 venting kits and components may 

be used in any venting application where rigid 

Secure Vent

®

 (SV4.5) direct vent components 

can be used. All restrictions, clearances and 

allowances that pertain to the rigid piping apply 

to the flexible venting. 

Secure Flex

 kits may not 

be modified; also, under no circumstances 

may separate sections of flex pipe be joined 

together

Secure Flex

 kits may be added to 

the end of a vent run made up of rigid 

Secure 

Vent

 (SV4.5) vent sections provided that 

doing so does not violate any of the venting 

length, height, routing, horizontal to vertical 

ratio requirements or clearance considerations 

detailed in this manual.

Secure Flex

 kits come with an included adaptor 

that can be fitted to the appliance collar or the 

inclined channel end of the last 

Secure Vent

 

(SV4.5) vent section in a rigid system in the 

exact same fashion as any other 

Secure Vent 

section. Align the dimpled end of the adaptor 

over the previously installed section or appliance 

collar, adjusting the radial alignment until the 

four locking dimples of the adaptor are aligned 

with the inlets of the four incline channels of the 

last vent section or collar. Push on the adaptor 

until it fully engages, then twist the adaptor 

clockwise running the dimples down and along 

the incline channels until they seat at the end 

of the channels.

Attach the flexible vent to the adaptor as 

follows 

(see Figure 42)

:

A. Install the Inner Flex Pipe
1.

 Install the small gear clamp loosely around 

the inner flexible vent pipe, push it back out 

of the way.

2.

 Apply a bead of 

Mill-Pac Black (700°F) high 

temperature sealant - Catalog No. 10K81)

 to 

the inner adaptor collar, approximately 1/2

 

inch 

from the end.

3.

 Pull and extend the inner flexible vent pipe. 

4.

 Slide the inner flex pipe over the adaptor 

collar. Ensure the flexible vent pipe completely 

engages the adaptor collar to a distance of 1 

3/4

 

inches from the end, and that it is free from 

damage or tears. 

 5

. Slide the gear clamp down and tighten it 

fully to secure the flexible vent to the adaptor 

inner collar approximately 3/4

 

inch from the 

end of the flex.

6

. Install 

three screws 120 degrees apart

 

through the flexible vent pipe and into the 

adaptor collar just below the gear clamp to 

provide additional security to the connection.

B. Install the Outer Flex Pipe
1.

 Install the large gear clamp loosely around 

the outer flexible vent pipe, push it back out 

of the way.

 

2.

 Apply a bead of 

Mill-Pac Black (700°F) high 

temperature sealant - Catalog No. 10K81)

 to 

the outer adaptor collar; to the grooves of the 

collar which extend approximately 1 inch from 

the end and to the flat surface, approximately 

1 3/8

 

inches from the end. 

3.

 Pull and extend the outer flexible vent pipe. 

4.

 Slide the outer flex pipe over the adaptor 

collar. Ensure the flexible vent pipe completely 

engages the adaptor collar to a distance of 

1 3/4

"

 from the end, and that it is free from 

damage or tears. 

5

. Slide the gear clamp down and tighten it 

fully to secure the flexible vent to the adaptor 

outer collar approximately 3/4

 

inch from the 

end of the flex.

6.

 Install 

three screws 120 degrees apart

 

through the flexible vent pipe and into the 

adaptor collar just below the gear clamp to 

provide additional security to the connection.

C. Route Flex Vent 

Ensure that the flex vent is properly routed to 

provide the required clearance. Do Not allow the 

flexible vent to bend in a radius tighter than 5" 

(127 mm). Refer to 

Figure 43. 

Place the internal 

flex vent spacers evenly and avoid kinking the 

inner pipe. Support horizontal sections of flex 

vent with metal straps at 2 ft (0.61 m) intervals. 

d. Install Firestop/Spacers at ceilings and walls

When Secure Flex penetrates a wall or ceiling, 

a firestop/spacer is required: use the SF4.5 VF 

firestop/spacer for ceilings and the SF4.5 HF 

firestop/spacer for walls. 

GEAR

CLAMPS

Adaptor

(SV4.5RF)

Apply  ONLY  MIL-PAC  BLACK  HIGH

TEMPERATURE SEALANT (Catalog No.

10K81) to the outside surface of both

collars of the adaptor (be especially

careful to fill the grooves of the outer

collar to be covered by the flexible

pipe)  and  slide  flexible  pipe  over

inner  and  outer  adaptor  collars.

NOTE:  OUTER PIPE IS PULLED AWAY TO

SHOW THE DETAIL OF THE INNER PIPE

FLEX VENT

1-3/4 in. (44 mm)

Flexible Pipe and

 Adaptor Outer

Collar Overlap

1-3/4 in. (44 mm)

Flexible Pipe and

 Adaptor Inner

Collar Overlap

SECURING SCREW

(3 PLACES EQUALLY SPACED

JUST BELOW GEAR CLAMP)

Attach Adaptor to Appliance

Collar, or Secure Vent Sections

SECURING SCREW

(3 PLACES EQUALLY SPACED

JUST BELOW GEAR CLAMP)

Figure 42

Содержание MPD35CNE

Страница 1: ...fire or explosion may result causing property damage personal injury or death WARNING AVERTISSEMENT AVISO HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLAS...

Страница 2: ...cal Installation Sequence 9 Detailed Installation Steps 9 Step 1 Framing 9 Fireplace and Framing Specifications 10 Step 2 Routing Gas Line 11 Step 3 Preparing Appliance Vent Collar 12 Step 4 Installin...

Страница 3: ...is appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning WARNING Failure to position the parts in accordance with these diagrams or failure to use only par...

Страница 4: ...55 0 052 19L52 MPD40 38 0 102 99K76 0 062 21L01 MPD45 37 0 104 24M10 52 0 0635 37G00 Table 4 Standard size installed at factory Part Cat Number REQUIREMENTS FOR THE COMMONWEALTHOFMASSACHUSETTS These f...

Страница 5: ...the appliance Cold Climate Insulation For cold climate installations seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room It is especially imp...

Страница 6: ...ents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch H ft H m Flat 6 12 1 0 0 3 6 12 7 12 1 25 0 38 7 12 8 12 1 5 0 46 8 12 9 12 2 0 0 61 9 12 10 12 2 5 0 76 10 12 11 12 3 25 0 99 11 12...

Страница 7: ...er 5 12 7 cm 5 12 7 cm G Clearance to inside corner 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS 2 5 08cm minimum SV4 5HT 2 6 15 2cm minimum SV4 5HTSS H Clearancetoeachinsideofcenterlineexten...

Страница 8: ...ve to conform to standard hearth extension installation requirements Shelf Height To provide for the lowest possible shelf surface use the alternate rear vent outlet the venting attached to the top ve...

Страница 9: ...the framing and secure with nailing brackets IMPORTANT Bend up the appropriate header spacing standoffs for the drywall finish material thickness to be used see Figure 11 Bend up the outer pair for 1...

Страница 10: ...lectrical Inlet Knockout requiring a Field Provided Junction Box either side E B D C Front View 3 76 A Header Spacing Top Standoffs Vertical Venting through the Ceiling Frame ceiling opening Use a plu...

Страница 11: ...aming 6 1 2 152 mm Pipe Coupling Recommended NOTE Rear Vent Applications in Corner Installations The horizontal vent length from a to b must not exceed 28 inches 711 mm MPDT33 and MPDR33 Models Dimens...

Страница 12: ...ct Venting System Horizontal or Vertical Withtheappliancesecuredinframing determine ventroutingandidentifytheexteriortermination location The following sections describe vertical roof and horizontal e...

Страница 13: ...4 1 1 0 0 5 0 6 3 8 1 5 2 5 1 0 1 0 5 0 6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1...

Страница 14: ...e radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar refer to Figure 21 Push the vent component againstthecollaruntilitfullyengages...

Страница 15: ...llar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking anyofthepreviouslyconnected...

Страница 16: ...ou are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet Example If 8 feet of H horizontal vent run is needed then 4 feet minimum V vertical vent will be required TABLE A H M...

Страница 17: ...6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max meters meters Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This tab...

Страница 18: ...al both the inner and outer pipe elements with the same procedure Sealant and securing screws are not required NOTE An elbow may also be attached to the appliance collar Attach in the same manner as y...

Страница 19: ...4 32 mm as shown in Figure 34 SVHRK Snorkel Cap The snorkel cap is designed to be fitted into a basement window box The SVHRK cap is for use with flex vent The vertical distance between the inlet and...

Страница 20: ...owingwallthicknessrange when using SV4 5HT 2 termination kit HORIZONTAL Vent Figures Tables NOTE Secure Vent components rigid vent pipe and terminal are shown in the figures Secure Flex components fle...

Страница 21: ...of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H horizontal run...

Страница 22: ...al rise except where an elbow is the only vertical component in the system See Figure 36 V Minimum feet feet 5 1 524 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 meter...

Страница 23: ...No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex pipe over the adaptor collar Ensure the flexible vent pip...

Страница 24: ...t of 2 conductor wire supplied with the unit NOTE The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed l...

Страница 25: ...eplace The millivolt control valve has a 3 8 10mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is fitted with a 1 2 x 3 8 13 mm x 10 mm NPT fitting Secu...

Страница 26: ...onovertime A Light the appliance refer to the lighting instructionslabelinthecontrolcompartment or in the Care and Operation Instructions manual B Brush all joints and connections with the gas leak te...

Страница 27: ...pli ances to Figure 54 for MPD35 Series appli ancesandtoFigure55forMPD40andMPD45 Series appliances WARNING DO NOT attempt to install the logs until the appliance instal lationhasbeencompleted the gas...

Страница 28: ...firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the hole on its upper end Place the left log and then the smaller...

Страница 29: ...the order shown Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear l...

Страница 30: ...ividual logs as shown below Logs should be placed in the order shown Position the center log on the burner first then place the glowing embers as shown in Figure 52 Place the rear log both the right a...

Страница 31: ...t appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation Figure 56 Removing the Glass Enclosure Panel see Figure 56 Remove the to...

Страница 32: ...ireplace rod located in the lower control area Position the air shutter to the factory setting as shown in the table in Figure 60 2 Light appliance follow lighting procedure on lighting label in contr...

Страница 33: ...bustible material may touch top of appliance Combustible materials NOT allowed below this point on face of appliance Header Spacing Top Standoff Top of Appliance Top of Door Frame Hood must be install...

Страница 34: ...er la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la l...

Страница 35: ...6 SV4 5HF 10 Firestop Spacer Hori zontal rigid 3 1 1 spac ing 10 Pack H2247 SV4 5VF 10 Firestop Spacer Verti cal rigid 1 1 1 spac ing 10 Pack 96K92 SV4 5SP Support Plate Installation Accessories Liste...

Страница 36: ...T48SS Small Square Termination for flex with 48 1219 mm of compressed flex vent Ref Instr 750204M 94L09 SF HTSS Horizontal Small Square Termination for flex without flex vent Ref Instr 750204M INSTALL...

Страница 37: ...pin located at the door s left side to the right until it disengages from the left corner post hole Pull the control compartment door diagonally to the left away from the fireplace Step 3 Remove the...

Страница 38: ...crews previously removed Step 12 Reinstall the baffle with the two baffle securing screws Step 13 Reassemble the remaining compo nents by reversing the procedures outlined in the Steps 1 5 Step 14 Att...

Отзывы: