background image

Page 14

505361M 09/07

Step 1. Determine the desired 

D

T

Measure entering air tempera-

ture using dry bulb (

A

) and wet bulb (

B

). 

D

T

 is the intersecting value of

A

 and

 B

 in the table (see triangle).

Step 2. Find temperature drop across coil

Measure the coil’s dry

bulb entering and leaving air temperatures (

A

 and 

C

). Temperature

Drop Formula: (

T

Drop

) = 

A

 minus 

C

.

Step 3. Determine if fan needs adjustment

If the difference be-

tween the measured 

T

Drop

 and the desired 

D

T

 

(T

Drop

D

T) 

is within

+3º, no adjustment is needed. See examples: Assume 

D

T

 = 15 and 

A

temp. = 72º, these 

temperatures would necessitate stated actions:

Cº T

Drop

D

T

=

ºF

ACTION

53º

 19

15

=

4

Increase the airflow

58º

14

15

=

−1

(3º range) no change

62º

10

15

=

−5

Decrease the airflow

Step 4. Adjust the fan speed

See indoor unit instructions to in-

crease/decrease fan speed.

Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and 

D

T are 3º.

Delta−

T

80

24 24 24 23 23 22 22 22 20 19 18 17 16 15

78

23 23 23 22 22 21 21 20 19 18 17 16 15 14

76

22 22 22 21 21 20 19 19 18 17 16 15 14 13

74

21 21 21 20 19 19 18 17 16 16 15 14 13 12

72

20 20 19 18 17 17 16 15 15 14 13 12 11 10

70

19 19 18 18 17 17 16 15 15 14 13 12 11 10

57 58 59 60 61 62 63 64 65 66 67 68 69 70

Temp.
of air
entering
indoor
coil ºF

INDOOR
COIL

DRY

BULB

DRY

BULB

WET

BULB

B

T

Drop

19º

A

Dry−bulb

Wet−bulb ºF

A

72º

B

64º

C

53º

air flow

air flow

All temperatures are
expressed in ºF

Figure 23. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart

Start−Up Procedures

IMPORTANT

If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start−up to
prevent compressor damage as a result of slugging.

1. Rotate fan to check for binding.

2. Inspect all factory− and field−installed wiring for loose

connections.

3. After evacuation is complete, open the liquid line and

vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system.

4. Replace the stem caps and tighten as specified in

Operating Service Valves

 on page 2.

5. Check voltage supply at the disconnect switch. The

voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted with the power company and the
voltage condition has been corrected.

6. Set the thermostat for a cooling demand. Turn on

power to the indoor indoor unit and close the outdoor
unit disconnect switch to start the unit.

7. Recheck voltage while the unit is running. Power must

be within range shown on the nameplate.

8. Check system for sufficient refrigerate by using the

procedures listed under 

Testing and Charging

System

.

SETTING UP TO CHECK CHARGE

1. Close manifold gauge set valves. Connect the center

manifold hose to an upright cylinder of HCFC−22.

2. Connect the manifold gauge set to the unit’s service

ports as illustrated in figure 1.

low pressure gauge to 

vapor service port

high pressure gauge to 

liquid service port

COOLING MODE INDOOR AIRFLOW CHECK

Check airflow using the Delta−T (

D

T)

 process as illustrated

in figure 23.

HEATING MODE INDOOR AIRFLOW CHECK

Blower airflow (CFM) may be calculated by energizing
electric heat and measuring:

temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,

voltage supplied to the unit,

amperage being drawn by the heat elements.

Then, apply the measurements taken in following formula
to determine CFM:

CFM =

Amps x Volts x 3.41

1.08 x Temperature rise (F)

The unit is factory charged with the amount of HCFC−22
refrigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with a 15
foot (4.6 m) line set. For varying lengths of line set, refer to
table 6 for refrigerant charge adjustment.

Table 6. Refrigerant Charge per Line Set Lengths

Liquid Line Set

Diameter

Ounces per 5 feet (g per 1.5 m) adjust

from 15 feet (4.6 m) line set*

3/8 in. (9.5 mm)

3 ounce per 5 ft. (85 g per 1.5 m)

NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If
line length is less than 15 ft. (4.6 m), subtract this amount.

The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. 

The method of charging is

determined the 

outdoor ambient temperature

.

Measure the liquid line temperature and the outdoor
ambient temperature as outlined below:

1. Close manifold gauge set valves. Connect the

manifold gauge set to the service valves.

low pressure gauge to 

vapor 

valve service port

high pressure gauge to 

liquid 

valve service port

2. Connect the center manifold hose to an upright

cylinder of HCFC−22.

Содержание Merit 13HPD018

Страница 1: ...61M 09 07 Supersedes 504 943M Table of Contents Shipping and Packing List 1 13HPD Outdoor Unit 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant from Existing System 4 Disconnecting and...

Страница 2: ...rom address shown below or contact your supervisor Lennox Industries Inc P O Box 799900 Dallas TX 75379 9900 General Information These instructions are intended as a general guide and do not supersede...

Страница 3: ...stripping of the various caps used the appropriately sized wrench should be used and fitted snugly over the cap before tightening Operating Angle Type Service Valve To Access Angle Type Service Port...

Страница 4: ...tem clockwise 90 3 Replace the stem cap and tighten as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench...

Страница 5: ...lifting heavy objects See Unit Dimensions on page 2 to determine the correct mounting size slab platform or support Refer to figure 7 for mandatory installation clearance requirements SEE NOTES BELOW...

Страница 6: ...s the refrigerant lines will not create unnecessary vibration and subsequent sounds REFRIGERANT LINE SET Field refrigerant piping consists of liquid and vapor lines from the outdoor unit braze connect...

Страница 7: ...TUDS STRAP SLEEVE WOOD BLOCK STRAP SLEEVE WIRE TIE WIRE TIE WIRE TIE INSIDE WALL Figure 11 Refrigerant Line Set Installing Vertical Runs New Construction Shown NOTE Similar installation practices shou...

Страница 8: ...fixed orifice size for each unit In non standard applications the provided fixed orifice may not be appropriate CTXV SYSTEMS 1 On fully cased coils remove the coil access and plumbing panels 2 Remove...

Страница 9: ...VALVE Figure 16 Typical Service Valve Port Core Removal WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressu...

Страница 10: ...s IMPORTANT Leak detector must be capable of sensing HFC refrigerant 1 Connect an HCFC 22 manifold gauge set high pressure hose to the vapor valve service port NOTE Normally the high pressure hose is...

Страница 11: ...if there is a rapid rise in sure indicates a relatively large leak If this occurs repeat the leak testing procedure NOTE The term absolute pressure means the total actual pressure within a given volu...

Страница 12: ...ground NOTE For proper voltages select thermostat wire gauge per the following table Table 5 Wire Run Lengths Wire run length AWG Insulation type Less than 100 feet 30 m 18 Color coded with a minimum...

Страница 13: ...must be grounded in accordance with national and local codes NOTE For use with copper conductors only Refer to unit rating plate for minimum circuit ampacity and maximum over current protection size...

Страница 14: ...you have consulted with the power company and the voltage condition has been corrected 6 Set the thermostat for a cooling demand Turn on power to the indoor indoor unit and close the outdoor unit disc...

Страница 15: ...the unit during warm weather use one of the following procedures CHARGE USING THE SUBCOOLING METHOD OUTDOOR TEMPERATURE 65 F 18 C When the outdoor ambient temperature is below 65 F 18 C use the subcoo...

Страница 16: ...mperature F C Outdoor Temperature F C Approach Temperature F C Model 018 024 030 036 042 048 060 F C 7 3 9 8 4 4 9 5 13 7 2 7 3 9 9 5 7 3 9 NOTE For best results use the same electronic thermome ter t...

Страница 17: ...es two components a defrost thermostat and a defrost control board DCB DEFROST THERMOSTAT The defrost thermostat as illustrated in figure 27 is located on the liquid line between the CTXV and the dist...

Страница 18: ...gure 29 DS1 and DS2 Diagnostic LEDs The DCB uses two LEDs DS1 and DS2 for diagnostics The LEDs flash a specific sequence according to the condition Table 10 DS1 and DS2 LED Codes Defrost Control Board...

Страница 19: ...occasional sounds that may occur while the unit is cycling in and out of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out...

Страница 20: ...n operation 4 Electronic Air Cleaner Some systems are equipped with an electronic air cleaner designed to remove airborne particles from the air passing through the cleaner If your system is so equipp...

Страница 21: ...er operates only when the thermostat calls for heating or cooling This mode is generally preferred when humidity control is a priority The ON or CONT mode provides continuous indoor blower operation r...

Страница 22: ...r Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or ins...

Отзывы: