background image

Page 20

505361M 09/07

Check the condensate drain line for free and
unobstructed flow; clean, if necessary.

Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.

Check drive belt for wear and proper tension.

If owner reports insufficient cooling, then:

Measure the temperature drop over the coil.

Gauged and check refrigerant charge.

Refer to section on refrigerant charging in this
instruction.

OPTIONAL ACCESSORIES

Refer to the Engineering Handbook for optional
accessories that may apply to this unit. The following may
or may not apply:

Loss of Charge Kit

High Pressure Switch Kit

Mild Weather Kit

Compressor Monitor

Compressor Crankcase Heater

Hail Guards

Mounting Bases

Timed Off Control

Stand−off Kit

Sound Cover

Low Ambient Kit

Monitor Kit

Dave Lennox 

Signature Stat

 Room Thermostat

Homeowner Information

In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.

1.

Air Filter

Ask your Lennox dealer to show you where

your indoor unit’s filter is located. It will be either at the
indoor unit (installed internal or external to the cabinet)
or behind a return air grille in the wall or ceiling. Check
the filter monthly and clean or replace it as needed.

2.

Disposable Filter

Disposable filters should be

replaced with a filter of the same type and size.

NOTE − If you are unsure about the filter required for your
system, call your Lennox dealer for assistance.

IMPORTANT

Turn off electrical power to the unit at the
disconnect switch before performing any
maintenance. The unit may have multiple power
supplies. Unit may delay coming back on from the
time delay in the thermostat or the defrost control.

3.

Reusable Filter

Many indoor units are equipped

with reusable foam filters. Clean foam filters with a

mild soap and water solution; rinse thoroughly; allow
filter to dry completely before returning it to the unit or
grille.

NOTE − The filter and all access panels must be in place
any time the unit is in operation.

4.

Electronic Air Cleaner

Some systems are

equipped with an electronic air cleaner, designed to
remove airborne particles from the air passing through
the cleaner. If your system is so equipped, ask your
dealer for maintenance instructions.

5.

Indoor Unit

The indoor unit’s evaporator coil is

equipped with a drain pan to collect condensate
formed as your system removes humidity from the
inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. (This
would also apply to an auxiliary drain, if installed.)

IMPORTANT

Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts and diminish
performance and longevity of the unit.

6.

Outdoor Unit

Make sure no obstructions restrict

airflow to the outdoor unit. Leaves, trash or shrubs
crowding the unit cause the outdoor unit to work harder
and use more energy. Keep shrubbery trimmed away
from the unit and periodically check for debris which
collects around the unit.

When removing debris from around the unit, be aware
of metal edges on parts and screws. Although special
care has been taken to keep exposed edges to a
minimum, physical contact with metal edges and
corners while applying excessive force or rapid motion
can result in personal injury.

Cleaning of the outdoor unit’s coil should be performed
by a trained service technician. Contact your dealer
and set up a schedule (preferably twice a year, but at
least once a year) to inspect and service your heat
pump system.

HEAT PUMP OPERATION

Your new Lennox heat pump has several characteristics
that you should be aware of:

Heat pumps satisfy heating demand by delivering
large amounts of 

warm

 air into the living space. This

is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably 

hotter

 air to heat the space.

Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45

°

F (7

°

C). An electronic control activates a

defrost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.

Содержание Merit 13HPD018

Страница 1: ...61M 09 07 Supersedes 504 943M Table of Contents Shipping and Packing List 1 13HPD Outdoor Unit 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant from Existing System 4 Disconnecting and...

Страница 2: ...rom address shown below or contact your supervisor Lennox Industries Inc P O Box 799900 Dallas TX 75379 9900 General Information These instructions are intended as a general guide and do not supersede...

Страница 3: ...stripping of the various caps used the appropriately sized wrench should be used and fitted snugly over the cap before tightening Operating Angle Type Service Valve To Access Angle Type Service Port...

Страница 4: ...tem clockwise 90 3 Replace the stem cap and tighten as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench...

Страница 5: ...lifting heavy objects See Unit Dimensions on page 2 to determine the correct mounting size slab platform or support Refer to figure 7 for mandatory installation clearance requirements SEE NOTES BELOW...

Страница 6: ...s the refrigerant lines will not create unnecessary vibration and subsequent sounds REFRIGERANT LINE SET Field refrigerant piping consists of liquid and vapor lines from the outdoor unit braze connect...

Страница 7: ...TUDS STRAP SLEEVE WOOD BLOCK STRAP SLEEVE WIRE TIE WIRE TIE WIRE TIE INSIDE WALL Figure 11 Refrigerant Line Set Installing Vertical Runs New Construction Shown NOTE Similar installation practices shou...

Страница 8: ...fixed orifice size for each unit In non standard applications the provided fixed orifice may not be appropriate CTXV SYSTEMS 1 On fully cased coils remove the coil access and plumbing panels 2 Remove...

Страница 9: ...VALVE Figure 16 Typical Service Valve Port Core Removal WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressu...

Страница 10: ...s IMPORTANT Leak detector must be capable of sensing HFC refrigerant 1 Connect an HCFC 22 manifold gauge set high pressure hose to the vapor valve service port NOTE Normally the high pressure hose is...

Страница 11: ...if there is a rapid rise in sure indicates a relatively large leak If this occurs repeat the leak testing procedure NOTE The term absolute pressure means the total actual pressure within a given volu...

Страница 12: ...ground NOTE For proper voltages select thermostat wire gauge per the following table Table 5 Wire Run Lengths Wire run length AWG Insulation type Less than 100 feet 30 m 18 Color coded with a minimum...

Страница 13: ...must be grounded in accordance with national and local codes NOTE For use with copper conductors only Refer to unit rating plate for minimum circuit ampacity and maximum over current protection size...

Страница 14: ...you have consulted with the power company and the voltage condition has been corrected 6 Set the thermostat for a cooling demand Turn on power to the indoor indoor unit and close the outdoor unit disc...

Страница 15: ...the unit during warm weather use one of the following procedures CHARGE USING THE SUBCOOLING METHOD OUTDOOR TEMPERATURE 65 F 18 C When the outdoor ambient temperature is below 65 F 18 C use the subcoo...

Страница 16: ...mperature F C Outdoor Temperature F C Approach Temperature F C Model 018 024 030 036 042 048 060 F C 7 3 9 8 4 4 9 5 13 7 2 7 3 9 9 5 7 3 9 NOTE For best results use the same electronic thermome ter t...

Страница 17: ...es two components a defrost thermostat and a defrost control board DCB DEFROST THERMOSTAT The defrost thermostat as illustrated in figure 27 is located on the liquid line between the CTXV and the dist...

Страница 18: ...gure 29 DS1 and DS2 Diagnostic LEDs The DCB uses two LEDs DS1 and DS2 for diagnostics The LEDs flash a specific sequence according to the condition Table 10 DS1 and DS2 LED Codes Defrost Control Board...

Страница 19: ...occasional sounds that may occur while the unit is cycling in and out of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out...

Страница 20: ...n operation 4 Electronic Air Cleaner Some systems are equipped with an electronic air cleaner designed to remove airborne particles from the air passing through the cleaner If your system is so equipp...

Страница 21: ...er operates only when the thermostat calls for heating or cooling This mode is generally preferred when humidity control is a priority The ON or CONT mode provides continuous indoor blower operation r...

Страница 22: ...r Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or ins...

Отзывы: