background image

Page 11

13HPD SERIES

5. Close the valve on the HCFC−22 cylinder and the valve

on the high pressure side of the manifold gauge set.

6. Disconnect the HCFC−22 cylinder.

7. Connect a cylinder of dry nitrogen with a pressure

regulating valve to the center port of the manifold
gauge set.

NOTE − 

Amounts of refrigerant will vary with line lengths.

8. Adjust dry nitrogen pressure to 150 psig (1034 kPa).
9. Open the valve on the high side of the manifold gauge

set in order to pressurize the line set and the indoor unit.

10. After a few minutes, open one of the service valve

ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector

11. Check the indoor and outdoor units and line set for

leaks using the leak detector mentioned in paragraph
10.

12. Proceed with evacuation as outlined in the 

Evacuating

the System

.

Evacuating the System

WARNING

Danger of Equipment Damage. Avoid deep
vacuum operation. Do not use compressors to
evacuate a system. Extremely low vacuums can
cause internal arcing and compressor failure.
Damage caused by deep vacuum operation will
void warranty.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
capable of accurately measuring down to 50 microns.

Evacuating the system of non−condensables is critical for
proper operation of the unit. Non−condensables are
defined as any gas that will not condense under
temperatures and pressures present during operation of
an air conditioning system. Non−condensables and water
vapor combine with refrigerant to produce substances that
corrode copper piping and compressor parts.

1. Connect manifold gauge set to the service valve ports

as follows:

low pressure gauge to 

vapor 

line service valve

high pressure gauge to 

liquid 

line service valve

2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to

the center port of the manifold gauge set.

4. Open both manifold valves and start the vacuum

pump.

5. Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23,000 microns (29.01 inches of

mercury).

NOTE − 

During the early stages of evacuation, it is

desirable to close the manifold gauge valve at least once to
determine if there is a rapid rise in sure indicates a
relatively large leak. If this occurs, 

repeat the leak testing

procedure

.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system, above
the absolute zero of pressure. Absolute pressure in a
vacuum is equal to atmospheric pressure minus vacuum
pressure.

6. When the absolute pressure reaches 23,000 microns

(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a dry nitrogen
cylinder with pressure regulator set to 150 psig (1034
kPa) and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and indoor
unit. Close the manifold gauge valves.

7. Shut off the dry nitrogen cylinder and remove the

manifold gauge hose from the cylinder. Open the
manifold gauge valves to release the dry nitrogen from
the line set and indoor unit.

8. Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

9. When the absolute pressure requirement above has

been met, disconnect the manifold hose from the
vacuum pump and connect it to an upright cylinder of
HCFC−22 refrigerant. Open the manifold gauge valve
1 to 2 psig in order to release the vacuum in the line set
and indoor unit.

10. Close manifold gauge valves and shut off the

HCFC−22 cylinder and remove the manifold gauge
set

.

SERVICING UNITS DELIVERED VOID OF CHARGE

If the system is void of refrigerant, clean the system using
the procedure described below.

1. Use nitrogen to pressurize the system and check for

leaks. Repair all leaks.

2. Evacuate the system to remove as much of the

moisture as possible.

3. Use nitrogen to break the vacuum and install a new

filter drier in the system.

4. Evacuate the system again. Then, weigh the

appropriate amount of HCFC−22 refrigerant as listed
on unit nameplate into the system.

5. Monitor the system to determine the amount of

moisture remaining in the oil. It may be necessary to
replace the filter drier several times to achieve the
required dryness level.

 If system dryness is not

verified, the compressor will fail in the future.

Содержание Merit 13HPD018

Страница 1: ...61M 09 07 Supersedes 504 943M Table of Contents Shipping and Packing List 1 13HPD Outdoor Unit 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant from Existing System 4 Disconnecting and...

Страница 2: ...rom address shown below or contact your supervisor Lennox Industries Inc P O Box 799900 Dallas TX 75379 9900 General Information These instructions are intended as a general guide and do not supersede...

Страница 3: ...stripping of the various caps used the appropriately sized wrench should be used and fitted snugly over the cap before tightening Operating Angle Type Service Valve To Access Angle Type Service Port...

Страница 4: ...tem clockwise 90 3 Replace the stem cap and tighten as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench...

Страница 5: ...lifting heavy objects See Unit Dimensions on page 2 to determine the correct mounting size slab platform or support Refer to figure 7 for mandatory installation clearance requirements SEE NOTES BELOW...

Страница 6: ...s the refrigerant lines will not create unnecessary vibration and subsequent sounds REFRIGERANT LINE SET Field refrigerant piping consists of liquid and vapor lines from the outdoor unit braze connect...

Страница 7: ...TUDS STRAP SLEEVE WOOD BLOCK STRAP SLEEVE WIRE TIE WIRE TIE WIRE TIE INSIDE WALL Figure 11 Refrigerant Line Set Installing Vertical Runs New Construction Shown NOTE Similar installation practices shou...

Страница 8: ...fixed orifice size for each unit In non standard applications the provided fixed orifice may not be appropriate CTXV SYSTEMS 1 On fully cased coils remove the coil access and plumbing panels 2 Remove...

Страница 9: ...VALVE Figure 16 Typical Service Valve Port Core Removal WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressu...

Страница 10: ...s IMPORTANT Leak detector must be capable of sensing HFC refrigerant 1 Connect an HCFC 22 manifold gauge set high pressure hose to the vapor valve service port NOTE Normally the high pressure hose is...

Страница 11: ...if there is a rapid rise in sure indicates a relatively large leak If this occurs repeat the leak testing procedure NOTE The term absolute pressure means the total actual pressure within a given volu...

Страница 12: ...ground NOTE For proper voltages select thermostat wire gauge per the following table Table 5 Wire Run Lengths Wire run length AWG Insulation type Less than 100 feet 30 m 18 Color coded with a minimum...

Страница 13: ...must be grounded in accordance with national and local codes NOTE For use with copper conductors only Refer to unit rating plate for minimum circuit ampacity and maximum over current protection size...

Страница 14: ...you have consulted with the power company and the voltage condition has been corrected 6 Set the thermostat for a cooling demand Turn on power to the indoor indoor unit and close the outdoor unit disc...

Страница 15: ...the unit during warm weather use one of the following procedures CHARGE USING THE SUBCOOLING METHOD OUTDOOR TEMPERATURE 65 F 18 C When the outdoor ambient temperature is below 65 F 18 C use the subcoo...

Страница 16: ...mperature F C Outdoor Temperature F C Approach Temperature F C Model 018 024 030 036 042 048 060 F C 7 3 9 8 4 4 9 5 13 7 2 7 3 9 9 5 7 3 9 NOTE For best results use the same electronic thermome ter t...

Страница 17: ...es two components a defrost thermostat and a defrost control board DCB DEFROST THERMOSTAT The defrost thermostat as illustrated in figure 27 is located on the liquid line between the CTXV and the dist...

Страница 18: ...gure 29 DS1 and DS2 Diagnostic LEDs The DCB uses two LEDs DS1 and DS2 for diagnostics The LEDs flash a specific sequence according to the condition Table 10 DS1 and DS2 LED Codes Defrost Control Board...

Страница 19: ...occasional sounds that may occur while the unit is cycling in and out of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out...

Страница 20: ...n operation 4 Electronic Air Cleaner Some systems are equipped with an electronic air cleaner designed to remove airborne particles from the air passing through the cleaner If your system is so equipp...

Страница 21: ...er operates only when the thermostat calls for heating or cooling This mode is generally preferred when humidity control is a priority The ON or CONT mode provides continuous indoor blower operation r...

Страница 22: ...r Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or ins...

Отзывы: