background image

Page 4

505361M 09/07

3. Replace the stem cap and tighten as follows:

With Torque Wrench

: Tighten finger tight and then

tighten per table 1.

Without Torque Wrench

: Finger tighten and use an

appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 2. 

 SERVICE PORT

SERVICE PORT

CORE

TO OUTDOOR

UNIT

STEM CAP

(VALVE STEM SHOWN OPEN)

INSERT HEX WRENCH HERE

SERVICE PORT CAP

TO INDOOR

UNIT

OPEN TO BOTH

INDOOR AND

OUTDOOR UNITS]

Figure 4. 

Angle−Type Service Valve 

(Valve Back−Seated Opened)

NOTE − A label with specific torque requirements may be
affixed to the stem cap. If the label is present, use the
specified torque.

Operating Ball−Type Service Valve

To Access Ball−Type Service Port:

A service port cap protects the service port core from
contamination and serves as the primary leak seal.

1. Remove service port cap with an appropriately sized

wrench.

2. Connect gauge to the service port.

3. When testing is completed, replace service port cap and

tighten as follows:

With Torque Wrench

: Finger tighten and then

tighten per table table 1.

Without Torque Wrench

: Finger tighten and use an

appropriately sized wrench to turn an additional
1/6 turn clockwise as illustrated in figure 2.

To Open and Close Ball−Type Service Valve:

A valve stem cap protects the valve stem from
contamination and assures a leak−free seal.

1. Remove stem cap with a wrench.

2. Use an appropriately sized wrench to open. To open

valve, rotate stem counterclockwise 90°. To close
rotate stem clockwise 90°.

3. Replace the stem cap and tighten as follows:

With Torque Wrench

: Finger tighten and then

tighten per table 1.

Without Torque Wrench

: Finger tighten and use an

appropriately sized wrench to turn an additional
1/12 turn clockwise as illustrated in figure 2.

NOTE − A label with specific torque requirements may be
affixed to the stem cap. If the label is present, use the
specified torque.
NOTE− To prevent stripping of the cap, the wrench should
be appropriately sized and fit snugly over the cap before
tightening the cap.

BALL
(SHOWN
CLOSED)

SERVICE PORT

CORE

TO INDOOR UNIT

TO OUTDOOR UNIT

Use appropriately sized
wrench.

To 

open

 rotate stem

counterclockwise 90°.
To 

close 

rotate stem clockwise

90°.

SERVICE PORT

SERVICE PORT CAP

STEM CAP

VALVE
STEM

Open to line set when valve is closed, to
both line set and unit when valve is open.

Figure 5. Ball−Type Service Valve

Recovering Refrigerant from Existing
HCFC−22 System

Remove existing HCFC−22 refrigerant using one of the
following methods:

METHOD 1:

If the existing outdoor unit is not equipped with shut−off
valves, or if the unit is not operational, then:

1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean

recovery cylinder and a recovery machine. Use the
instructions provided with the recover machine on how
to setup the connections.

3. Remove all HCFC−22 refrigerant from the existing

system. Check gauges after shutdown to confirm that
the entire system is completely void of refrigerant.

4. Disconnect the liquid and vapor lines from the existing

outdoor unit.

5. Remove the existing outdoor unit.

NOTE − Use recovery machine instructions for specific
setup requirements.

Содержание Merit 13HPD018

Страница 1: ...61M 09 07 Supersedes 504 943M Table of Contents Shipping and Packing List 1 13HPD Outdoor Unit 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant from Existing System 4 Disconnecting and...

Страница 2: ...rom address shown below or contact your supervisor Lennox Industries Inc P O Box 799900 Dallas TX 75379 9900 General Information These instructions are intended as a general guide and do not supersede...

Страница 3: ...stripping of the various caps used the appropriately sized wrench should be used and fitted snugly over the cap before tightening Operating Angle Type Service Valve To Access Angle Type Service Port...

Страница 4: ...tem clockwise 90 3 Replace the stem cap and tighten as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench...

Страница 5: ...lifting heavy objects See Unit Dimensions on page 2 to determine the correct mounting size slab platform or support Refer to figure 7 for mandatory installation clearance requirements SEE NOTES BELOW...

Страница 6: ...s the refrigerant lines will not create unnecessary vibration and subsequent sounds REFRIGERANT LINE SET Field refrigerant piping consists of liquid and vapor lines from the outdoor unit braze connect...

Страница 7: ...TUDS STRAP SLEEVE WOOD BLOCK STRAP SLEEVE WIRE TIE WIRE TIE WIRE TIE INSIDE WALL Figure 11 Refrigerant Line Set Installing Vertical Runs New Construction Shown NOTE Similar installation practices shou...

Страница 8: ...fixed orifice size for each unit In non standard applications the provided fixed orifice may not be appropriate CTXV SYSTEMS 1 On fully cased coils remove the coil access and plumbing panels 2 Remove...

Страница 9: ...VALVE Figure 16 Typical Service Valve Port Core Removal WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressu...

Страница 10: ...s IMPORTANT Leak detector must be capable of sensing HFC refrigerant 1 Connect an HCFC 22 manifold gauge set high pressure hose to the vapor valve service port NOTE Normally the high pressure hose is...

Страница 11: ...if there is a rapid rise in sure indicates a relatively large leak If this occurs repeat the leak testing procedure NOTE The term absolute pressure means the total actual pressure within a given volu...

Страница 12: ...ground NOTE For proper voltages select thermostat wire gauge per the following table Table 5 Wire Run Lengths Wire run length AWG Insulation type Less than 100 feet 30 m 18 Color coded with a minimum...

Страница 13: ...must be grounded in accordance with national and local codes NOTE For use with copper conductors only Refer to unit rating plate for minimum circuit ampacity and maximum over current protection size...

Страница 14: ...you have consulted with the power company and the voltage condition has been corrected 6 Set the thermostat for a cooling demand Turn on power to the indoor indoor unit and close the outdoor unit disc...

Страница 15: ...the unit during warm weather use one of the following procedures CHARGE USING THE SUBCOOLING METHOD OUTDOOR TEMPERATURE 65 F 18 C When the outdoor ambient temperature is below 65 F 18 C use the subcoo...

Страница 16: ...mperature F C Outdoor Temperature F C Approach Temperature F C Model 018 024 030 036 042 048 060 F C 7 3 9 8 4 4 9 5 13 7 2 7 3 9 9 5 7 3 9 NOTE For best results use the same electronic thermome ter t...

Страница 17: ...es two components a defrost thermostat and a defrost control board DCB DEFROST THERMOSTAT The defrost thermostat as illustrated in figure 27 is located on the liquid line between the CTXV and the dist...

Страница 18: ...gure 29 DS1 and DS2 Diagnostic LEDs The DCB uses two LEDs DS1 and DS2 for diagnostics The LEDs flash a specific sequence according to the condition Table 10 DS1 and DS2 LED Codes Defrost Control Board...

Страница 19: ...occasional sounds that may occur while the unit is cycling in and out of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out...

Страница 20: ...n operation 4 Electronic Air Cleaner Some systems are equipped with an electronic air cleaner designed to remove airborne particles from the air passing through the cleaner If your system is so equipp...

Страница 21: ...er operates only when the thermostat calls for heating or cooling This mode is generally preferred when humidity control is a priority The ON or CONT mode provides continuous indoor blower operation r...

Страница 22: ...r Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or ins...

Отзывы: