background image

Page 12

505361M 09/07

Electrical Connections

NOTE − 

24VAC, Class II circuit connections are made in

the low voltage junction box

NOTE − Units are approved for use only with copper
conductors.

NOTE − A complete unit wiring diagram is located inside
the unit control box cover.

NOTE − To facilitate conduit, a hole is in the bottom of the
control box. Connect conduit to the control box using a
proper conduit fitting.

Refer to the indoor unit installation instruction for additional
wiring application diagrams and refer to unit nameplate for
minimum circuit ampacity and maximum overcurrent
protection size. Figures 21 and 22 illustrate typical outdoor
unit wiring diagrams for the 13HPD series heat pumps.

In the U.S.A., wiring must conform with current local
codes and the current National Electric Code (NEC).

In Canada, wiring must conform with current local codes
and the current Canadian Electrical Code (CEC).

WARNING

Electric Shock Hazard. Can cause
injury or death.

Line voltage is present at all
components on units with single-pole
contactors, even when unit is not in
operation!

Unit may have multiple power
supplies. Disconnect all remote
electric power supplies before
opening access panel.

Unit must be grounded in accordance
with national and local codes.

WIRING CONNECTIONS

1. Install line voltage power supply to unit from a properly

sized disconnect switch. Any excess high voltage field
wiring should be trimmed or secured away from the
low voltage field wiring.

2. Ground unit at unit disconnect switch or to an earth

ground.

NOTE − For proper voltages, select thermostat wire gauge
per the following table:

Table 5. Wire Run Lengths

Wire run length

AWG #

Insulation type

Less than 100 feet (30 m)

18

Color−coded with a minimum
temperature rating of 35

º

C.

More than 100 feet (30 m)

16

3. Connect conduit to the unit using provided conduit

bushing.

4. Install room thermostat (ordered separately) on an

inside wall approximately in the center of the
conditioned area and five feet (1.5 m) from the floor.
It should not be installed on an outside wall or where
it can be affected by sunlight, drafts or vibrations.

5. Install low voltage wiring from outdoor to indoor unit

and from thermostat to indoor unit as illustrated in
figures 21 and 22.

6. Do not bundle any excess 24VAC control wire inside

control box. Run control wire through installed wire tie
and tighten wire tie to provided low voltage strain relief
and to maintain separation of field installed low and
high voltage circuits.

Thermostat

Indoor Unit

Outdoor Unit

R

C

W1

Y1

O

G

R

C

W1

W2

W3

G

R

C

W1

Y1

O

COMMON

1ST STAGE

AUXILIARY HEAT

INDOOR BLOWER

COMPRESSOR

24V POWER

REVERSING VALVE

(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC
THERMOSTAT AND INDOOR UNIT.)

24V POWER

COMMON

1ST STAGE

AUXILIARY HEAT

Figure 19. Outdoor Unit and Blower Unit Thermostat

Designation

R

C

W1

Y1

O

G

R

C

W1

W2

W3

G

E

R

C

W1

Y1

O

EMERGENCY

HEAT

EMERGENCY

HEAT RELAY

OUTDOOR
THERMOSTAT

Thermostat

Indoor Unit

Outdoor Unit

COMMON

INDOOR BLOWER

COMMON

(SOME CONNECTIONS MAY NOT APPLY. REFER TO
SPECIFIC THERMOSTAT AND INDOOR UNIT.)

24V POWER

24V POWER

1ST STAGE

AUXILIARY HEAT

REVERSING VALVE

COMPRESSOR

1ST STAGE

AUXILIARY HEAT

Figure 20. Outdoor Unit and Blower Unit Thermostat

Designation (with Emergency Heat)

Содержание Merit 13HPD018

Страница 1: ...61M 09 07 Supersedes 504 943M Table of Contents Shipping and Packing List 1 13HPD Outdoor Unit 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant from Existing System 4 Disconnecting and...

Страница 2: ...rom address shown below or contact your supervisor Lennox Industries Inc P O Box 799900 Dallas TX 75379 9900 General Information These instructions are intended as a general guide and do not supersede...

Страница 3: ...stripping of the various caps used the appropriately sized wrench should be used and fitted snugly over the cap before tightening Operating Angle Type Service Valve To Access Angle Type Service Port...

Страница 4: ...tem clockwise 90 3 Replace the stem cap and tighten as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench...

Страница 5: ...lifting heavy objects See Unit Dimensions on page 2 to determine the correct mounting size slab platform or support Refer to figure 7 for mandatory installation clearance requirements SEE NOTES BELOW...

Страница 6: ...s the refrigerant lines will not create unnecessary vibration and subsequent sounds REFRIGERANT LINE SET Field refrigerant piping consists of liquid and vapor lines from the outdoor unit braze connect...

Страница 7: ...TUDS STRAP SLEEVE WOOD BLOCK STRAP SLEEVE WIRE TIE WIRE TIE WIRE TIE INSIDE WALL Figure 11 Refrigerant Line Set Installing Vertical Runs New Construction Shown NOTE Similar installation practices shou...

Страница 8: ...fixed orifice size for each unit In non standard applications the provided fixed orifice may not be appropriate CTXV SYSTEMS 1 On fully cased coils remove the coil access and plumbing panels 2 Remove...

Страница 9: ...VALVE Figure 16 Typical Service Valve Port Core Removal WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressu...

Страница 10: ...s IMPORTANT Leak detector must be capable of sensing HFC refrigerant 1 Connect an HCFC 22 manifold gauge set high pressure hose to the vapor valve service port NOTE Normally the high pressure hose is...

Страница 11: ...if there is a rapid rise in sure indicates a relatively large leak If this occurs repeat the leak testing procedure NOTE The term absolute pressure means the total actual pressure within a given volu...

Страница 12: ...ground NOTE For proper voltages select thermostat wire gauge per the following table Table 5 Wire Run Lengths Wire run length AWG Insulation type Less than 100 feet 30 m 18 Color coded with a minimum...

Страница 13: ...must be grounded in accordance with national and local codes NOTE For use with copper conductors only Refer to unit rating plate for minimum circuit ampacity and maximum over current protection size...

Страница 14: ...you have consulted with the power company and the voltage condition has been corrected 6 Set the thermostat for a cooling demand Turn on power to the indoor indoor unit and close the outdoor unit disc...

Страница 15: ...the unit during warm weather use one of the following procedures CHARGE USING THE SUBCOOLING METHOD OUTDOOR TEMPERATURE 65 F 18 C When the outdoor ambient temperature is below 65 F 18 C use the subcoo...

Страница 16: ...mperature F C Outdoor Temperature F C Approach Temperature F C Model 018 024 030 036 042 048 060 F C 7 3 9 8 4 4 9 5 13 7 2 7 3 9 9 5 7 3 9 NOTE For best results use the same electronic thermome ter t...

Страница 17: ...es two components a defrost thermostat and a defrost control board DCB DEFROST THERMOSTAT The defrost thermostat as illustrated in figure 27 is located on the liquid line between the CTXV and the dist...

Страница 18: ...gure 29 DS1 and DS2 Diagnostic LEDs The DCB uses two LEDs DS1 and DS2 for diagnostics The LEDs flash a specific sequence according to the condition Table 10 DS1 and DS2 LED Codes Defrost Control Board...

Страница 19: ...occasional sounds that may occur while the unit is cycling in and out of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out...

Страница 20: ...n operation 4 Electronic Air Cleaner Some systems are equipped with an electronic air cleaner designed to remove airborne particles from the air passing through the cleaner If your system is so equipp...

Страница 21: ...er operates only when the thermostat calls for heating or cooling This mode is generally preferred when humidity control is a priority The ON or CONT mode provides continuous indoor blower operation r...

Страница 22: ...r Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or ins...

Отзывы: