Installation - Operation - Maintenance manual (IOM)
•
AIR COOLED CHILLERS & SPLIT UNITS - 1106-E
• 60 •
Size
702V 752VE 803V 853VE 953V 1003VE
Operating limits for Evaporator
Water Test pressure
Bar
10
Refrigerant Test pressure
Bar
26,5
Water Max. operating pressure
Bar
6
Refrigerant Max. operating pressure
Bar
26,5
Water Min. flow
m3/h
8°C
∆
T
Water Max. flow
m3/h
153,5 153,5 153,5 153,5 180 180
Operating limits for Pressure gauge control
Safety Cut of low pressure
Bar
0,7
Safety Interlocking of low pressure
Bar
2,2
Safety Cut of high pressure
Bar
26,5
Safety Interlocking of high pressure
Bar
20
Size
1053V 1153VE 1254V 1354VE 1404V 1504VE
Operating limits for Evaporator
Water Test pressure
Bar
10
Refrigerant Test pressure
Bar
26,5
Water Max. operating pressure
Bar
6
Refrigerant Max. operating pressure
Bar
26,5
Water Min. flow
m3/h
8°C
∆
T
Water Max. flow
m3/h
220 220 220 220 250 250
Operating limits for Pressure gauge control
Safety Cut of low pressure
Bar
0,7
Safety Interlocking of low pressure
Bar
2,2
Safety Cut of high pressure
Bar
26,5
Safety Interlocking of high pressure
Bar
20
Содержание MCC Series
Страница 2: ......
Страница 25: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 1106 E 23 AT 18 18 FAN CURVE...
Страница 68: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 0105 E 66 CERTIFICATES...
Страница 69: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 0105 E 67...
Страница 70: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 0105 E 68...
Страница 85: ......