UNITS WITH REMOTE CONDENSER
Unit with remote condenser
without capacity control
Unit with remote condenser
with capacity control
H1 :
15 m. maxi
H2 :
5 m. maxi
H3 :
0,3 m. maxi
H4 :
0,15 m. maxi
1 -
Lower trap with single tube
2 -
Clode coupled trap
3 -
Lower trap with double tubes
4 -
Higher trap with double tubes
WARNING
:
The liquid level between the condenser and the check valve A must compensate the check valve
pressure drop
If receiver option : PED declaration class 3
If no receiver option : PED declaration class 1