Installation - Operation - Maintenance manual (IOM)
•
AIR COOLED CHILLERS & SPLIT UNITS - 1106-E
• 56 •
Screw chiller - operating limits
ALL UNITS - STANDARD
Size
402V 422VE 442V 452VE 502V
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
49,5 48,5
Size
552VE 602V 652VE 702V 752VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
48,5 48,5 48,5 49 49
Size
803V 853VE 953V 1003VE 1053V
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
49 49 48,5
48,5
47,5
Size
1153VE 1254V 1354VE 1404V 1504VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
47,5 48,5 48,5 47,5 47,5
Содержание MCC Series
Страница 2: ......
Страница 25: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 1106 E 23 AT 18 18 FAN CURVE...
Страница 68: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 0105 E 66 CERTIFICATES...
Страница 69: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 0105 E 67...
Страница 70: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 0105 E 68...
Страница 85: ......