Installation - Operation - Maintenance manual (IOM)
•
AIR COOLED CHILLERS & SPLIT UNITS - 1106-E
• 41 •
8.3 MANUFACTURER’S RECOMMENDED INSPECTIONS
8.3.1 - LIQUID CHILLERS WITH RECIPROCATING COMPRESSOR(S)
8.3.1.1 - Number of recommended preventive maintenance visits :
NUMBER OF RECOMMENDED PREVENTIVE MAINTENANCE VISITS
Year
Start up
500/1000H
visit
Major
technical
inspection
Inspection
visit
15 000 h
inspection
30000 h
inspection
Tube
analysis
1
1
1
2
2
1
3
3
1
3
4
3
1
5
1
3
1
(1)
6
1
3
7
3
1
8
1
3
9
1
3
10
3
1
1
+10
Every year
3 times a
year
Every
15000 hours
Every
30000 hours
Every 3
years
This table is published for units operating under normal conditions with an average annual runtime of 4000 hours.
In hostile industrial environments, a specific maintenance visit schedule must be envisaged.
(1) Depending on the quality of the water