Installation - Operation - Maintenance manual (IOM)
•
AIR COOLED CHILLERS & SPLIT UNITS - 1106-E
• 57 •
ALL UNITS – HIGH AMBIENT
Size
442V 452VE
502V 552VE
602V 652VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
53,5
53,5 52 52 52 52
Size
702V 752VE
803V 853VE
953V 1003VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
52,5 52,5 52,5 52,5 52 52
Size
1053V 1153VE
1254V 1354VE
1404V 1504VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
51,5 51,5 52 52 51,5 51,5
Содержание MCC Series
Страница 2: ......
Страница 25: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 1106 E 23 AT 18 18 FAN CURVE...
Страница 68: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 0105 E 66 CERTIFICATES...
Страница 69: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 0105 E 67...
Страница 70: ...Installation Operation Maintenance manual IOM AIR COOLED CHILLERS SPLIT UNITS 0105 E 68...
Страница 85: ......