background image

8

Indoor Unit Condensate Piping Connections

IMPORTANT

Make sure that drain piping is properly routed and 

insulated to prevent both leaks and condensation.

1. 

Use a field-provided hose clamp to secure the drain 

line stub on the side of the cassette base to a field-

supplied 1” (25 mm) drain line.

NOTE: 

Take care not to over-tighten the hose clamp as 

this may damage the drain line stub.

NOTE: 

Connection between stub and drain line must be 

watertight. Apply non hardening plumbing joint 

compound if needed to ensure a watertight seal. 

2. 

Confirm proper slope (not less than 1/4 inch per foot 

(18 mm per m)) and routing of condensate lines to 

ensure moisture is drained away from the indoor unit.

3.  Drain should be as short as possible and should 

not have any droops or kinks that would restrict 

condensate flow and shall be approved resistant pipe. 

 

There  must  be  a  2-inch  (51  mm)  space  between  

the  end  of  the  condensate  drain  and  the  final 

termination  point  (ground,  open  drain,  etc.)  to 

ensure that the line will drain freely.

4.  After the system installation is complete, the 

condensate drain line must be checked for leaks and 

proper drainage. If a field-provided condensate pump 

has been installed, it must be checked to ensure proper 

operation. This check is part of the start-up process 

which must be done by the installing contractor.

IMPORTANT

Drain should have a slope of at least ¼ inch per foot and 

should be approved corrosion-resistant pipe. You must 

confirm operation of every drain and pump in the system 

as part of the commissioning procedure.

Outdoor Unit Installation

Placement Considerations

CAUTION

In order to avoid injury, take proper precaution when 

lifting heavy objects.

Consider the following when positioning the unit:

•  In coastal areas or other places with salty atmosphere 

of sulfate gas, corrosion may shorten the life of the 

unit. In coastal areas, the coil should be cleaned with 

potable water several times per year to avoid corrosive 

buildup (salt).

•   Some localities are adopting sound ordinances based 

on the unit’s sound level registered from the adjacent 

property, not from the property where the unit is in-

stalled. Install the unit as far as possible from the prop-

erty line.

•  When possible, do not install the unit directly outside 

a window. Glass has a very high level of sound trans-

mission.

•  Install unit level.

Ground

Level

Building Structure

Figure 6. 

Install Unit Level

•  Choose a place solid enough to bear the weight and 

vibration of the unit, where the operation noise will not 

be amplified.

•  Choose a location where the hot air discharged from 

the unit or the operation noise will not be a nuisance 

to neighbors.

•  Avoid installing the outdoor unit near a bedroom or 

other places where noise may cause a problem

• 

There must be sufficient space to carry the unit into 

and out of the site.

• 

There must be unobstructed air flow around the air in

-

let and the air outlet.

• 

The unit must not be installed in areas where a flam

-

mable gas leak may occur.

•  Install the outdoor unit a minimum of 3 feet (1m) away 

from any antenna, power cord (line), radio, telephone, 

security  system,  or  intercom.  Electrical  interference 

and radio frequencies from any of these sources may 

affect operation.

•  Since water drains from the outdoor unit during vari-

ous stages of operation, do not place anything which 

may be damaged by moisture under the unit.

Direct Sunlight, Rain, Snow and Ice Protection

•  If the outdoor unit is subjected to prolong exposure to 

direct sunlight with temperatures over 100°F (38°C) a 

canopy is suggested as illustrated in “Figure 7. Out

-

door Unit on Pedestal (Stand) and Protective Canopy” 

or “Figure 12. Dog House-Style Shelter” on page 10.

IMPORTANT

The construction of a canopy or shade is necessary 

because of an ambient limit control set to 122°F (50°C) 

to protect the electronics. If the outdoor unit is placed in 

direct sunlight it is possible that the limit may activate 

and shut down the unit. 

•  Place unit away from overhanging roof lines which 

would allow water or ice to drop on, or in front of, coil 

Содержание M0STAT60Q-1

Страница 1: ...lean up All mini split operating conditions must be verified ac cording to these installation instructions MLA MPB and MFMA Series SINGLE ZONE MINI SPLIT SYSTEMS 208 230V Floor Mount Console 508048 01...

Страница 2: ...ccessories Component Catalog Number M0STAT64Q 1 Programmable Wired Controller 15D30 Wired Controller Extension Cable 20 feet long Y8738 Indoor Outdoor Unit Match Ups Outdoor Unit Indoor Unit Voltage M...

Страница 3: ...ence 1 1st Revision Voltage P 208 230V 1 phase 60hz Nominal Cooling Capacity 012 1 ton Unit Type L Low Ambient Heat Pump P Heat Pump CEILING FLOOR NON DUCTED INDOOR UNITS M FM A 012 S 4 2 P Unit Type...

Страница 4: ...rated tape field provided Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable field provided Tape Line set wrapped in foam insulation...

Страница 5: ...2S4S P inches 34 1 4 20 1 4 21 7 8 13 1 8 13 3 8 mm 870 514 556 333 340 MLA012S4S P inches 34 1 4 20 1 4 21 3 4 12 1 4 13 3 8 mm 870 514 552 311 594 Indoor Units Hanging Brackets 2 FRONT VIEW SIDE VIE...

Страница 6: ...e 6 inches 152 mm when mounted on brackets and with no obstructions on the other three sides Figure 3 Outdoor Unit Clearances Inches mm Indoor Unit FRONT VIEW SIDE VIEW 4 102 WALL SUPPLY AIR 40 1016 S...

Страница 7: ...sed to strong electromagnetic forces Areas exposed to acids or alkaline detergents DO Place the unit so that it is not exposed to direct sun light Ensure the structural ceiling can support the weight...

Страница 8: ...er several times per year to avoid corrosive buildup salt Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the property wher...

Страница 9: ...et 12 in 305 mm 79 in 2007 mm Figure 9 Outdoor Unit Air Flow Obstructed by Snow Figure 10 Avoid Defrost Water Ice Hazard Prevailing Winds Normally wind baffles are not required for a outdoor unit Howe...

Страница 10: ...l mounting brack et insert the provided drain connector into one of the 1 inch 25 mm drain holes and attached a field provided insulated drain hose to the connector Use field provid ed rubber plugs to...

Страница 11: ...ength required for the application 4 Cut the selected pipes with a pipe cutter Make the cuts flat and smooth as illustrated in Figure 18 Cutting Pipe 9 0 Lean Crude Burr o Figure 18 Cutting Pipe 5 Ins...

Страница 12: ...ON THE OUTSIDE OF THE FLARE MALE FLARE CONNECTION Figure 19 Making Connections Male to Female Connection 17 Once snug continue another half turn on each nut which should create a leak free joint A to...

Страница 13: ...non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas servic...

Страница 14: ...ons are complete Indoor Unit All indoor units are powered by the outdoor unit Communication Wiring Indoor Units 30K and Below Use one stranded 4 conductor wire to provide power and communication Commu...

Страница 15: ...g Factory Setting For Setting Down louver For Setting Down louver SW101 SW101 ACTIVE ACTIVE 1 1 2 2 ON ON 1 1 2 2 ON ON 1 1 2 2 ON ON 1 1 2 2 ON ON SW103 SW103 For Setting Fan Motor Control then No Po...

Страница 16: ...G CN 21 Y G CN 1A Y G Y G COMPRESSOR Y G CN 50 3 U V W BLUE RED BLACK EXV OUTDOOR MAIN PCB OUTDOOR TE MP S E NS OR COMPR E S S OR DIS CHAR GE TE MP S E NS OR OUTDOOR C OIL TEMP SENSOR RED BLACK WHTIE...

Страница 17: ...amount of additional refrigerant Failure to do so may result in reduced performance Table 8 Additional Refrigerant Charge System Size KBtu Pipe Length feet meters Amount of Refrigerant to add 12 25 7...

Страница 18: ...failure the system will immediately stop When power returns the Operation light on the indoor unit will flash To restart the unit press the ON OFF button on the remote control If the system has an aut...

Страница 19: ...Figure 30 Open Front Panel 2 Remove the Air Filter Press the clamps on the right and left sides of the air filter down slightly then pull upward to remove the air filter Air Outlet Selection Switch Fi...

Страница 20: ...actory installed CN4 Adapter Cable Optional Programmable Wired Controller 20 Foot Cable provided with Programmable Wired Controller Figure 33 Connecting Optional Programmable Wired Controller Connect...

Отзывы: