background image

10

12” (305mm) 

Min. Distance

Wind Barrier

Inlet Air

Prevailing Winter Winds from Air Inlet Side

Discharge Air

Wind Barrier

Prevailing Winter Winds From Air Discharge Side

79” (2007mm) 

Min. Distance

Figure 11. Wind Barrier

12 in

305 mm

24 in

610 mm

24 in

610 mm

12 in

305 mm

NOTE - Minimum clearances shown.

Figure 12. 

Dog House-Style Shelter

12 in

305 mm

24 in

610 mm

12 in

305 mm

24 in

610 mm

NOTE - Minimum clearances shown.

Figure 13. 

Unit installed in Alcove

Buried Refrigerant Pipe Protection

•  All 

refrigerant lines must be insulated regardless of if 

it is buried.

•  In addition to insulating each line of piping, buried lines 

must rest inside a 

sealed, watertight

 conduit.

•  The conduit must be designed so it cannot collect and 

retain water.

Outdoor Unit Condensate Piping

Condensate formed during the heating and defrost 

processes must be drained from heat pump units. Drain 

holes are provided in the base of the units to ensure 

proper drainage. 

•  Heat pumps must be raised when installed on a con-

crete pad or the ground to allow drainage to occur. I

•  f the heat pump unit is installed on wall mounting brack-

et, insert the provided drain connector into one of the 1 

inch (25 mm) drain holes and attached a field-provided 

insulated drain hose to the connector. Use field-provid

-

ed rubber plugs to cover any unused drain holes if the 

unit is installed over a walk way or door.

Drain

Connector

Chassis

Condensate Drain

(location varies per model)

Figure 14. Condensate Drain

Securing the Outdoor Unit

Slab or Roof Mounting

Install the unit a minimum of 4 inches (102 mm) above the 

roof or ground surface to avoid ice build-up around the 

unit. Place the unit above a load bearing wall or area of 

the roof that can adequately support the unit. Consult local 

codes for rooftop applications.

CAUTION

Roof Damage!
This system contains both refrigerant and oil. Some 

rubber roofing material may absorb oil. This will cause 

the rubber to swell when it comes into contact with oil. 

The rubber will then bubble and could cause leaks. 

Protect the roof surface to avoid exposure to refrigerant 

and oil during service and installation. Failure to follow 

this notice could result in damage to roof surface.

Securing Outdoor Unit to Slab, Frame, or Rails

If the outdoor unit is installed on a field-provided slab or 

frame, use lag bolts or equivalent to secure the outdoor 

unit to the slab or frame.

Содержание M0STAT60Q-1

Страница 1: ...lean up All mini split operating conditions must be verified ac cording to these installation instructions MLA MPB and MFMA Series SINGLE ZONE MINI SPLIT SYSTEMS 208 230V Floor Mount Console 508048 01...

Страница 2: ...ccessories Component Catalog Number M0STAT64Q 1 Programmable Wired Controller 15D30 Wired Controller Extension Cable 20 feet long Y8738 Indoor Outdoor Unit Match Ups Outdoor Unit Indoor Unit Voltage M...

Страница 3: ...ence 1 1st Revision Voltage P 208 230V 1 phase 60hz Nominal Cooling Capacity 012 1 ton Unit Type L Low Ambient Heat Pump P Heat Pump CEILING FLOOR NON DUCTED INDOOR UNITS M FM A 012 S 4 2 P Unit Type...

Страница 4: ...rated tape field provided Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable field provided Tape Line set wrapped in foam insulation...

Страница 5: ...2S4S P inches 34 1 4 20 1 4 21 7 8 13 1 8 13 3 8 mm 870 514 556 333 340 MLA012S4S P inches 34 1 4 20 1 4 21 3 4 12 1 4 13 3 8 mm 870 514 552 311 594 Indoor Units Hanging Brackets 2 FRONT VIEW SIDE VIE...

Страница 6: ...e 6 inches 152 mm when mounted on brackets and with no obstructions on the other three sides Figure 3 Outdoor Unit Clearances Inches mm Indoor Unit FRONT VIEW SIDE VIEW 4 102 WALL SUPPLY AIR 40 1016 S...

Страница 7: ...sed to strong electromagnetic forces Areas exposed to acids or alkaline detergents DO Place the unit so that it is not exposed to direct sun light Ensure the structural ceiling can support the weight...

Страница 8: ...er several times per year to avoid corrosive buildup salt Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the property wher...

Страница 9: ...et 12 in 305 mm 79 in 2007 mm Figure 9 Outdoor Unit Air Flow Obstructed by Snow Figure 10 Avoid Defrost Water Ice Hazard Prevailing Winds Normally wind baffles are not required for a outdoor unit Howe...

Страница 10: ...l mounting brack et insert the provided drain connector into one of the 1 inch 25 mm drain holes and attached a field provided insulated drain hose to the connector Use field provid ed rubber plugs to...

Страница 11: ...ength required for the application 4 Cut the selected pipes with a pipe cutter Make the cuts flat and smooth as illustrated in Figure 18 Cutting Pipe 9 0 Lean Crude Burr o Figure 18 Cutting Pipe 5 Ins...

Страница 12: ...ON THE OUTSIDE OF THE FLARE MALE FLARE CONNECTION Figure 19 Making Connections Male to Female Connection 17 Once snug continue another half turn on each nut which should create a leak free joint A to...

Страница 13: ...non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas servic...

Страница 14: ...ons are complete Indoor Unit All indoor units are powered by the outdoor unit Communication Wiring Indoor Units 30K and Below Use one stranded 4 conductor wire to provide power and communication Commu...

Страница 15: ...g Factory Setting For Setting Down louver For Setting Down louver SW101 SW101 ACTIVE ACTIVE 1 1 2 2 ON ON 1 1 2 2 ON ON 1 1 2 2 ON ON 1 1 2 2 ON ON SW103 SW103 For Setting Fan Motor Control then No Po...

Страница 16: ...G CN 21 Y G CN 1A Y G Y G COMPRESSOR Y G CN 50 3 U V W BLUE RED BLACK EXV OUTDOOR MAIN PCB OUTDOOR TE MP S E NS OR COMPR E S S OR DIS CHAR GE TE MP S E NS OR OUTDOOR C OIL TEMP SENSOR RED BLACK WHTIE...

Страница 17: ...amount of additional refrigerant Failure to do so may result in reduced performance Table 8 Additional Refrigerant Charge System Size KBtu Pipe Length feet meters Amount of Refrigerant to add 12 25 7...

Страница 18: ...failure the system will immediately stop When power returns the Operation light on the indoor unit will flash To restart the unit press the ON OFF button on the remote control If the system has an aut...

Страница 19: ...Figure 30 Open Front Panel 2 Remove the Air Filter Press the clamps on the right and left sides of the air filter down slightly then pull upward to remove the air filter Air Outlet Selection Switch Fi...

Страница 20: ...actory installed CN4 Adapter Cable Optional Programmable Wired Controller 20 Foot Cable provided with Programmable Wired Controller Figure 33 Connecting Optional Programmable Wired Controller Connect...

Отзывы: