background image

18

Dry Mode Operation (Dehumidification)

Procedure

1.  Use the provided wireless remote control and press 

the 

MODE

 button and select 

DRY

 mode.

2.  Press the 

UP/ DOWN

 button to select the desired 

temperature. The temperature setting range is from 

62°F (17°C) to 86°F (30°C) in one degree increments.

NOTE: 

The blower is preset at a low speed and cannot be 

changed therefore it will get cold and most likely 

will over shoot the temperature setting by 6-10

°

(3-5

°

C) depending on the room size or other 

various factors. Also the 

Follow Me

 

mode does 

not operate in this mode. 

NOTE: 

In addition, the indoor units do not have a humidistat 

installed therefore they are unable to determine 

humidity levels. This product is not recommend as 

a main source for dehumidification.

Sequence of Operation

When in dry mode operation the unit is actually in cooling 

mode with a low speed blower operation. Set remote temp 

to a lower room temp to begin the dry mode operation. 

The compressor will stop when the room temperature is 

4°F (2°C) lower than the temperature setting. 
However there is a temperature compensation for cooling 

mode that is 4°F (2°C). So the unit will stop when the 

temperature is 8°F (4°C) lower than the room temperature 

settings.

User Guide

Default Settings

When the system restarts after a power failure, it will 

default to the factory settings - AUTO mode, AUTO fan, 

24°C (76°F). This may cause inconsistencies on the 

remote control and unit panel. Use your remote control to 

update the status.

Auto-Restart

In case of power failure, the system will immediately stop. 

When power returns, the Operation light on the indoor unit 

will  flash.  To  restart  the  unit,  press  the  ON/OFF  button 

on the remote control. If the system has an auto restart 

function, the unit will restart using the same settings.

Louver Angle Memory Function

Some models are designed with a louver angle memory 

function. When the unit restarts after a power failure, the 

angle of the horizontal louvers will automatically return to 

the previous position.
The angle of the horizontal louver should not be set too 

small as condensation may form and drip into the machine. 

To reset the louver, press the manual button, which will 

reset the horizontal louver settings.
The louvers can be in automatic swing function and will 

swing with in a preset open and close in both heat and 

cooling. If you chose to position the louvers in one place. 

see manual mode.

Refrigerant Leak Detection System

In the event of a refrigerant leak, the LCD screen will 

display “EC” and the LED indicator light will flash.

Manual Operations

This display panel on the indoor unit can be used to operate 

the unit in case the remote control has been misplaced or 

is out of batteries.

Infrared receiver

Timer indicator

PRE-DEF 

(pre-heating/defrost) 

indicator  

Operation indicator

Manual button

Figure 25. Console Display

• 

MANUAL

 - This button selects the mode in the follow-

ing order: AUTO, FORCED COOL and OFF.

• 

FORCED COOL

  -  In  FORCED  COOL  mode,  the 

Operation  light  flashes. The  system  will  then  turn  to 

AUTO after it has cooled with a high wind speed for 

30 minutes. The remote control will be disabled during 

this operation.

• 

OFF

 - When the panel is turned OFF, the unit turns off 

and the remote control is re-enabled.

Содержание M0STAT60Q-1

Страница 1: ...lean up All mini split operating conditions must be verified ac cording to these installation instructions MLA MPB and MFMA Series SINGLE ZONE MINI SPLIT SYSTEMS 208 230V Floor Mount Console 508048 01...

Страница 2: ...ccessories Component Catalog Number M0STAT64Q 1 Programmable Wired Controller 15D30 Wired Controller Extension Cable 20 feet long Y8738 Indoor Outdoor Unit Match Ups Outdoor Unit Indoor Unit Voltage M...

Страница 3: ...ence 1 1st Revision Voltage P 208 230V 1 phase 60hz Nominal Cooling Capacity 012 1 ton Unit Type L Low Ambient Heat Pump P Heat Pump CEILING FLOOR NON DUCTED INDOOR UNITS M FM A 012 S 4 2 P Unit Type...

Страница 4: ...rated tape field provided Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable field provided Tape Line set wrapped in foam insulation...

Страница 5: ...2S4S P inches 34 1 4 20 1 4 21 7 8 13 1 8 13 3 8 mm 870 514 556 333 340 MLA012S4S P inches 34 1 4 20 1 4 21 3 4 12 1 4 13 3 8 mm 870 514 552 311 594 Indoor Units Hanging Brackets 2 FRONT VIEW SIDE VIE...

Страница 6: ...e 6 inches 152 mm when mounted on brackets and with no obstructions on the other three sides Figure 3 Outdoor Unit Clearances Inches mm Indoor Unit FRONT VIEW SIDE VIEW 4 102 WALL SUPPLY AIR 40 1016 S...

Страница 7: ...sed to strong electromagnetic forces Areas exposed to acids or alkaline detergents DO Place the unit so that it is not exposed to direct sun light Ensure the structural ceiling can support the weight...

Страница 8: ...er several times per year to avoid corrosive buildup salt Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the property wher...

Страница 9: ...et 12 in 305 mm 79 in 2007 mm Figure 9 Outdoor Unit Air Flow Obstructed by Snow Figure 10 Avoid Defrost Water Ice Hazard Prevailing Winds Normally wind baffles are not required for a outdoor unit Howe...

Страница 10: ...l mounting brack et insert the provided drain connector into one of the 1 inch 25 mm drain holes and attached a field provided insulated drain hose to the connector Use field provid ed rubber plugs to...

Страница 11: ...ength required for the application 4 Cut the selected pipes with a pipe cutter Make the cuts flat and smooth as illustrated in Figure 18 Cutting Pipe 9 0 Lean Crude Burr o Figure 18 Cutting Pipe 5 Ins...

Страница 12: ...ON THE OUTSIDE OF THE FLARE MALE FLARE CONNECTION Figure 19 Making Connections Male to Female Connection 17 Once snug continue another half turn on each nut which should create a leak free joint A to...

Страница 13: ...non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas servic...

Страница 14: ...ons are complete Indoor Unit All indoor units are powered by the outdoor unit Communication Wiring Indoor Units 30K and Below Use one stranded 4 conductor wire to provide power and communication Commu...

Страница 15: ...g Factory Setting For Setting Down louver For Setting Down louver SW101 SW101 ACTIVE ACTIVE 1 1 2 2 ON ON 1 1 2 2 ON ON 1 1 2 2 ON ON 1 1 2 2 ON ON SW103 SW103 For Setting Fan Motor Control then No Po...

Страница 16: ...G CN 21 Y G CN 1A Y G Y G COMPRESSOR Y G CN 50 3 U V W BLUE RED BLACK EXV OUTDOOR MAIN PCB OUTDOOR TE MP S E NS OR COMPR E S S OR DIS CHAR GE TE MP S E NS OR OUTDOOR C OIL TEMP SENSOR RED BLACK WHTIE...

Страница 17: ...amount of additional refrigerant Failure to do so may result in reduced performance Table 8 Additional Refrigerant Charge System Size KBtu Pipe Length feet meters Amount of Refrigerant to add 12 25 7...

Страница 18: ...failure the system will immediately stop When power returns the Operation light on the indoor unit will flash To restart the unit press the ON OFF button on the remote control If the system has an aut...

Страница 19: ...Figure 30 Open Front Panel 2 Remove the Air Filter Press the clamps on the right and left sides of the air filter down slightly then pull upward to remove the air filter Air Outlet Selection Switch Fi...

Страница 20: ...actory installed CN4 Adapter Cable Optional Programmable Wired Controller 20 Foot Cable provided with Programmable Wired Controller Figure 33 Connecting Optional Programmable Wired Controller Connect...

Отзывы: