Table 19. Alert Codes and Troubleshooting
Initial notification of critical alerts will pop-up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. Moderate alerts
are not e-mailed to Homeowners. Dealers will get an email and code can be seen on thermostat under the installer notification section.
NOTE:
Anytime the word
DEVICE
or
DEVICE2
is used in this table, it will be replaced on all alert code notification screens with the actual offending device name, for example, thermostat, heat
pump, etc.).
Alert
Code
Inverter
Flash
Code
Priority
Condition
Applicable
Component
Actual Displayed
Alert Text
Component or System Operational State and Troubleshooting Tip
432
28
Moderate /
Critical
Variable
capacity
outdoor unit*
OD Inverter DC
Link High Voltage
The inverter has detected a DC link high voltage condition.
•
Error occurs when the DC link capacitor voltage is greater than 480VDC.
• If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition.
• Anti-short cycle timer is initiated.
•
If condition occurs 10 times within 60 consecutive minutes, the system will lockout – critical condition.
•
Inverter LEDs will flash code 28.
•
Refer to the unit service documentation for detailed troubleshooting procedures.
Inverter flash code 28., The sequence is:
• Red LED: Two Flashes
• Green LED: Eight Flashes
To clear, disconnect power to outdoor unit and restart.
Troubleshooting Suggestions:
•
Check wire connections (U, V and W) at inverter plug in harness and compressor.
•
Check the resistance of compressor windings. If not in range, replace compressor.
• Check compressor to ground. If ground issue, replace compressor.
• Check input power (Single Phase - 208/ 10%. If out of range, correct main power issue.
•
Check DC Link voltage and MICOM Sensing voltage. If out of range, replace inverter. if okay, possible mechanical issue with
compressor.
Go to outdoor unit service manual for detail troubleshooting procedures and require values for testing DC link voltages and
various insulation resistance characteristics.