Table 19. Alert Codes and Troubleshooting
Initial notification of critical alerts will pop-up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu. Moderate alerts
are not e-mailed to Homeowners. Dealers will get an email and code can be seen on thermostat under the installer notification section.
NOTE:
Anytime the word
DEVICE
or
DEVICE2
is used in this table, it will be replaced on all alert code notification screens with the actual offending device name, for example, thermostat, heat
pump, etc.).
Alert
Code
Inverter
Flash
Code
Priority
Condition
Applicable
Component
Actual Displayed
Alert Text
Component or System Operational State and Troubleshooting Tip
441
14
Moderate
Variable
capacity
outdoor unit*
OD Inverter
Compressor
Slowdown - High
Compressor
Current
This alert code is for more information than an issue with the system.
• Compressor slowdown due to high compressor current.
• Compressor current is approaching limit.
• The compressor speed automatically slows.
•
This error code is primarily for informational purposes as the inverter controls the compressor to operate within design
parameters. Alert code 441 typically occurs at startup as the compressor current increases rapidly during startup.
•
The inverter will reduce the compressor speed by 4 Hz and slow the compressor ramp up speed to the requested
compressor demand speed (capacity). This is normal and expected operation of the inverter to control the inverter within
design parameters. In most cases the alert code 441 notification does not require any additional service or diagnostic
procedures.
•
The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz.
• Possible issue is system running at high pressures.
• Check for high pressure trips or other alert codes in thermostat and outdoor control.
•
Inverter LEDs will flash code 14.
•
Refer to the unit service documentation for detailed troubleshooting procedures.
Inverter flash code 14. The sequence is:
• Red LED: One Flash
• Green LED: Four Flashes
Automatically clears when the condition no longer exists.
442
Critical
Outdoor unit
Compressor Top
Cap Switch Strike
Lockout
The top cap switch has opened five times within one hour. As a result, the outdoor unit is locked out
.
•
This condition occurs when compressor thermal protection sensor opens five times within one hour.
• Outdoor unit will stop.
• To clear, disconnect power to outdoor unit and restart.
443
Critical
Outdoor unit
MUC Unit Code
to Inverter Model
Mismatch
The Lennox variable capacity unitary control (outdoor control) has incorrect appliance unit size code selected.
•
Check for proper configuring under unit size code used for outdoor unit (see unit configuration guide or in installation
instructions).
•
If replacing inverter, verify inverter model matches unit size.
•
Remove the thermostat from the system while applying power and reprogramming.
• Automatically clears after the correct match is detected following a power reset.
444
Critical
Heat Pump
Reversing Valve
Relay Failed to
Close
Relay failure. Verify by call for heat pump heating. Check for 24VAC out from
O
. Replace outdoor unit control board.