41
Table 13. Thermostat (HD Display) Parameters
Parameter
Description
Outdoor
Temperature
Source
Options are off, Internet (AccuWeather) or sensor. Default is Internet (AccuWeather).
Proximity Control
Options are ON and OFF. Default is OFF. Is used to wake-up the display from screen saver mode when motion near the HD Display is detected.
Reset thermostat
Resets the thermostat settings to factory default.
Screen Locked
Options are unlocked, partially locked and locked. Default is unlocked.
Screen Saver
Options are off, weather, power save and logo. Default is off.
NOTE:
When the user performs a picture upload from the settings > display > screen saver page, then on this screen it will only indicate that logo was selected. If no
picture has been uploaded, then the Lennox logo would be displayed.
Wide Setpoint
Options are ON and OFF. Default is OFF. This allows a wider low and high temperature. Normal range is 60 to 90°F (15.6 to 32.2°C) . When this parameter is set to ON,
the range is 40 to 100°F (4.4 to 37.8°C). This feature can also be set through the user interface setting screen. From the home screen go to menu > settings > heat &
cool (or it may be just heat or cool) > wider set-point range.
Table 14.
PureAir S
Parameters
Parameter
Description
Equipment
PureAir Filter
Dirty Filter
Detection and UV
Life Detection
Default: ON. Options are either ON or OFF.
This parameter turns on and off the filter life and UV lamp life reporting. When set to off, the control will continue to calculate the remaining filter life through
continuous sampling, but will not use filter tests to determine filter life. The control will:
•
Perform a filter calibration upon indication of a filter change regardless of the value of this parameter.
•
Perform a UVA lamp calibration upon indication of a lamp change regardless of the value of this parameter.
•
Calculate UVA lamp life remaining regardless of the value of this parameter.
Alarms 504 and 503 will not be sent while this parameter is set to “Off”
The Diagnostics screen on the thermostat will continue to show values for both filter life and UV lamp life regardless of the value of this parameter.
Max Air Filtered
between Tests
Default is 100%, Range is 50% to 100% Changes can be made in increments of 10%. This parameter:
•
Modifies the amount of air that is allowed to pass through the filter after a valid % life determination before a filter test is initiated.
•
Expressed as a percentage of the cubic feet of air that would pass through the filter if the fan operated at continuous fan CFM for 30 days.
UV lamp operation
detection
Default: ON. Options are either ON or OFF.
Filter Life
Provides percentage of remaining filter life. This is for display purposes only and cannot be changed.
Last replacement
date for filter
Date last filter reset was accomplished. This is for display purposes only and cannot be changed
Purifier life
Provides percentage of remaining purifier life. This is for display purposes only and cannot be changed
Last replacement
date for purifier
Date last purifier insert reset was accomplished. This is for display purposes only and cannot be changed
• Reset
PureAir S
will reset all
PureAir S
parameters back to factory defaults.
•
Reset purifier will reset it to 100%. This is usually accomplished after the purifier insert has been replaced.
•
Reset filter will reset it to 100%. This is usually accomplished after the air filter has been replaced.