72
s
inGle
s
taGe
c
OndensinG
i
n
c
OOlinG
Table 29. Single Stage Condensing In Cooling
(At minimum blower CFM superheat must be at or above 5˚SH)
Size
1.5 Tons
2 Tons
2.5 Tons
3 Tons
Minimum CFM @180 CFM
Per Ton
270 CFM
360 CFM
450 CFM
540 CFM
Recommend CFM @300 CFM Per Ton
For Zoning
450 CFM
600 CFM
750 CFM
900 CFM
CFM @400CFM Per
Ton
600 CFM
800 CFM
1,000 CFM
1200 CFM
Size
3.5 Tons
4Tons
5 Tons
Minimum CFM @180 CFM
Per Ton
630 CFM
720 CFM
900 CFM
Recommend CFM @300 CFM Per Ton
For Zoning
1,050 CFM
1200 CFM
1,500 CFM
CFM @400CFM Per
Ton
1,400 CFM
1,600 CFM
2,000 CFM
Содержание Harmony III