![Lennox Harmony III Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/lennox/harmony-iii/harmony-iii_installation-setup-and-user-manual_1877175027.webp)
27
3.2. Furnace Variable Speed Motor Electrical
Adjustments
NOTE:
Follow all equipment installation instructions provided with each unit.
The variable-speed motor (VSM) in the furnace is controlled by the integrated
furnace control (IFC). Adjustment of these drive controls is made by cutting the
clippable on-board links and selecting DIP switch settings. This is described in the
following paragraphs.
• The furnace blower motor speed must be adjusted to produce the zoning CFM
requirements managed by the zone control system.
• The Harmony III zoning system control’s pulse width modulated (PWM) output
signal is connected to the DS terminal on the furnace control. The PWM signal,
along with any other thermostat request (
G
,
W1
, or
W1
+
W2
), controls fan speed
linearly between the minimum and maximum CFM for the furnace as determined
by the cool speed DIP switches (see SLP98 Installation Instructions for settings).
• Locate the integrated control in the furnace control box area. Before connecting
the zone control panel to the integrated control, complete the applicable electrical
adjustments shown in the following figures.
+
W915 2 Stage Compr (Y1 to Y2)—DO NOT CUT
W951 Heat Pump (R to O)—DO NOT CUT
W914 Dehum - Harmony (R to DS)—CUT IN ALL CASES
EAC
HUM
ON-BOARD LINKS:
Electrical Adjustments
1.
In all cases
—cut the clippable on
‐
board link W914 Dehum - Harmony
(between R and DS, see figure 18); if not cut, the zone control panel
DS fuse will blow.
tween Y1 and Y2).
Do NOT cut any wires in the variable speed motor harness.
Figure 23. Typical Furnace VSM Electrical Adjustments
Set the upper limit of blower CFM as follows:
1.
Determine the maximum system CFM requirements (sum of all the individual
zones).
2.
From the Blower Motor Performance tables (see furnace Installation Instructions)
determine the HIGH speed cool DIP switch setting that corresponds to this
CFM.
3.
Set the HIGH speed cool DIP switch setting on the integrated control to this
value.
NOTE:
The lower limit of blower CFM is factory set. It is not field adjustable.
The minimum airflow achieved by the any of the gas furnaces when connected to a
Harmony III zoning system control listed in “Minimum CFM for Harmony III zoning
system with Variable Speed Blower Motors (Gas Furnaces)” on page 16. A 3%
duty cycle corresponds to the minimum CFM, and a 97% duty cycle corresponds
to the maximum CFM.
NOTE:
Any on/off delays present for a heating or cooling sequence are still present
with Harmony III zoning system control operation.
3.3. Variable Speed Motor Furnace System Operations
The dehumidification on-board clippable link W914 Dehum - Harmony (R to DS) on
the integrated furnace control must be cut for operation with the Harmony III zoning
system control. Once the link is cut, the presence of the Harmony III™ zoning
system, versus a standard dehumidification control, is automatically detected by
the integrated control.
IMPORTANT
DO NOT alter blower harness!
3.3.1. Operation
When the integrated control is properly connected to a Harmony III zone control,
operation is as follows:
•
Integrated control DIP switches 1 and 2, which configure the control for operation
with various types of thermostats, are ignored.
• The zone control sends a
W1
Signal to the furnace which goes through its normal
ignition sequence as described in the furnace installation instructions.
• The blower will start and operate at the minimum blower speed after a 45 second
delay.
• After the temperature of the DAS rises above 100ºF the zone control will provide
a PWM signal to the furnace on terminal
DS
based upon the Zone PIAB Jumper
selections (and the heating air reduction jumper).
• The blower speed (CFM) is set according to the pulse width modulated (PWM)
signal from the Harmony III zoning system control.
• The blower speed adjusts immediately with PWM adjustments.
•
The furnace firing rate is based on current operating CFM and internal lookup
table for midpoint temperature rise. If resulting firing rate is below minimum firing
rate, it will operate at minimum fire rate. Accordingly, if resulting firing rate is
above maximum firing rate, it will operate at maximum firing rate.
• Firing rate adjusts anytime the PWM deviates by more than 5% (e.g. 60% >
65%).
NOTE:
Integrated control DIP switches 14 through 19 are not disabled, and can
be used in conjunction with Harmony III zoning system to increase or
decrease airflow volume during heating operation.
NOTE:
DIP switches 14-19 adjust firing rate when Harmony III zoning system
is detected. Air volume is controlled by Harmony III zoning system. The
Содержание Harmony III
Страница 80: ...80...