![Lennox Harmony III Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/lennox/harmony-iii/harmony-iii_installation-setup-and-user-manual_1877175010.webp)
10
By installing jumpers at different % on each PIAB bank, you can direct different
amounts of air volume to each zone. You must jumper a % on zone 1 and at
least one other zone, and you must jumper OFF on unused zones as shown
in the following figure.
Pin shown with
jumper on
ZONE 1 AT 10%.
Pin shown with
jumper on
ZONE 2 AT 0%
(allows min. cfm
airflow).
ZONE 1
ZONE 3
PIAB
PIAB
ZONE 2
ZONE 4
PIAB
PIAB
NOTE - Only zones 2,
3, and 4 have an OFF
setting.
ZONES 3
AND 4 ARE
SHOWN
NOT USED
(JUMPERS
SET ON
“OFF”).
Figure 8. PIAB Jumper Settings (Typical)
NOTE:
The blower speed may be affected by the reduction jumpers, if installed.
See “1.10.6. Continuous Air Reduction Jumpers” on page 11 for more
details.
1.10.3. Upgrading from Harmony II zoning system?
NOTE:
If replacing a Harmony II zoning system, use conversion values in “Table
10. Air Jumper Positions Conversion Chart” to maintain equivalent air
settings when setting up the Harmony III zoning system.
Table 10. Air Jumper Positions Conversion Chart
Model
Equivalent Positions (%)
Harmony II zoning
system
25
35
45
55
65
75
85
95
Harmony III zoning
system
0
10
30
40
50
70
80
90
1.10.4. Zone 1 PIAB Jumpers – 140ºF DAS
Zone 1 PIAB terminal strip has an additional jumper setting (labeled 140F DAS)
that may be used for added operational flexibility (see “Figure 9. 140ºF DAS
Jumper”). When the supplied jumper is in place across both pins, the discharge air
sensor (DAS) upper limit will be 140°F instead of 160°F (default) to provide added
operational flexibility.
HEATING STAGING
JUMPERS
COOLING STAGING
JUMPERS
CONTINUOUS AIR
REDUCTION JUMPERS
HEATING AIR
REDUCTION JUMPERS
PIAB
JUMPERS
Figure 9. 140
º
F DAS Jumper
NOTE:
If the heating staging jumper is set to either 120 or 130 and the 140F DAS
jumper is in place, the furnace will stage up at 115ºF and down to 130ºF
(see “1.10.8.1. Heating Staging Temperature Jumper” on page 11) for
further details.
1.10.5. Determining PIAB Jumper Settings
NOTE:
Use “6.3.2. PIAB Calculation Worksheet” on page 65 (also see example
below) to help calculate the zone control system PIAB settings.
1.
From a cooling load analysis, determine what CFM is required for each zone.
Also, from the air handler, determine its minimum and maximum CFM ratings.
2.
Using the PIAB formula, found in Table 5 and reflected in the worksheet below,
calculate the Percent Into Adjustment Band (PIAB) using the values from step
1 for each zone. “Determine PIAB Jumper Settings” on page 11 also gives
example CFM values to illustrates how to determine the correct jumper for the
PIAB for Zone 1 using those values.
3.
Set the air selection jumper for the zone using the percent air determined in
step 2. If the percent air falls between available jumper settings, select the
nearest unit of ten.
4.
For each zone, repeat steps 1 through 3.
NOTE:
See “1.10.4. Zone 1 PIAB Jumpers – 140ºF DAS” or information on 140F
DAS (discharge air sensor) jumper used on Zone 1 PIAB.