23
DEADBAND
Default is 2°F. The deadband setting is the
minimum difference between the cooling and
heating set points. This setting is used in cool/heat
mode to ensure smooth equipment operation. The
deadband is adjustable from 2 to 9°F. Use the + or -
option to select desired deadband.
Touch <
to
return to previous menu.
SMOOTH SET RECOVERY(SSR)
Options are enable or disable. Default is enable.
When enabled, smooth set recovery begins
recovery up to two hours before the programmed
time so that the programmed temperature is
reached at the corresponding programmed event
time. Assume 12°F per hour for first stage
gas/electric heating and 6°F per hour for first stage
compressor based heating or cooling. With
Smooth Set Recovery disabled, the control will
start a recovery at the programmed time.
NOTE
- Smooth Set Recovery and Stage2 Lock
Out operations vary depending on equipment
(see
table 1).
SSR STAGE 2 LOCK OUT
Default is 20 minutes. Use the + or - option to set
the number of minutes before the programmed
event time that stage 2 is allowed to operate (20 to
120 minutes in 10 minute increments). Touch
<
to
return to previous menu. This setting is ignored
when SSR is disabled.
DEALER INFORMATION
This allows the installer to add dealer name,
address, phone, email, website and number.
Touch
<
to return to previous menu.
TEMPERATURE OFFSET
Default is 0°F. This setting can be used to offset
the displayed space temperature by up to +/- 5°F.
This offset also applies to the control temperature.
Touch
<
to return to previous menu.
HUMIDITY OFFSET
Default is 0%. This can be used to offset the
displayed and controlled space relative humidity
(RH) by up to +/- 10% RH. Touch
<
to return to
previous menu.
Содержание ComfortSense 7500
Страница 12: ...12 Figure 3 Enhanced Dehumidification Accessory Typical Wiring Diagram ...
Страница 13: ...13 Tc To To Tc Figure 4 CBX32MV XXX 230 06 or Higher and CBX40UHV Wiring Diagrams Condensing Unit Applications ...
Страница 14: ...14 To Tc To Tc Figure 5 CBX32MV XXX 230 06 or Higher and CBX40UHV Wiring Diagrams Heat Pump Unit Applications ...
Страница 18: ...18 TSTAT EL280P TSTAT EL296E EL296V SL280V To Tc To Tc Figure 9 Thermostat Wiring Diagrams continued ...