Description
4th
digit
3rd
digit
2nd
digit
1st
digit
R/W/Z Min
Std
Max
3541 outside
air
temperature
threshold
to
activate
function
Onset
R/W
8
16
22
3542 ratio
for
dynamic
management
Ratio
R/W
0
1,4
2
3543 minimum
time
between
two
defrost
Timeout
R/W
30
45
90
3544 number
restart
of
fans
for
the
end
of
cycle
Restart
R/W
1
3
5
3545 choice
of
one
compressor
by
tandem
during
defrost
1/2
Tand
R/W
0
0
1
3546 state
of
defrost
cycle
delayed
by
BMS
Bms
Wait
R/W
0
0
1
3611 set
point
of
configuration
Expert
Expansion
Valve
Configuration
Option
R/W
0
0
1
3621 set
point
of
superheat
S.Heat
R/W
3
5
10
3622 kp
set
point
for
pid
control
Kp
R/W
0
7
30
3623 ti
set
point
for
pid
control
Ti
R/W
0
60
360
3624 td
set
point
for
pid
control
Td
R/W
0
2
9
3625 offset
for
pressure
sensor
Offset
R/W
‐
5
0
5
3626 offset
for
temperature
probe
Offset
R/W
‐
5
0
5
3627 choice
of
manual
mode
Manual
R/W
0
0
1
3628 value
of
number
of
steps
for
manual
mode
Steps
R/W
0
0
480
3631 set
point
of
superheat
S.Heat
R/W
3
5
10
3632 kp
set
point
for
pid
control
Kp
R/W
0
7
30
3633 ti
set
point
for
pid
control
Ti
R/W
0
60
360
3634 td
set
point
for
pid
control
Td
R/W
0
2
9
3635 offset
for
pressure
sensor
Offset
R/W
‐
5
0
5
3636 offset
for
temperature
probe
Offset
R/W
‐
5
0
5
3637 choice
of
manual
mode
Manual
R/W
0
0
1
3638 value
of
number
of
steps
for
manual
mode
Steps
R/W
0
0
480
3711 1st
heaters,
set
point
of
configuration
Main
R/W
0
0
7
3712 2nd
heaters,
set
point
of
configuration
2nd
R/W
0
0
2
3713 Hot
water
pump,
set
point
of
configuration
Pump
R/W
0
0
1
3721 1st
heaters,
setpoint
for
activation
operation
of
component
Enable.1
R/W/Z
0
1
1
3722 1st
heaters,
state
of
unload
50%
by
BMS
Bms
50%
R/W
0
0
1
3723 1st
heaters,
state
of
unload
100%
by
BMS
Bms
Unl.
R/W
0
0
1
3724 2nd
heaters,
setpoint
for
activation
operation
of
component
Enable.2
R/W/Z
0
1
1
3731 1st
heaters,
set
point
for
priority
inversion
starting
Swap
1
R/W/Z
0
0
3
3732 1st
heaters,
outside
air
temperature
threshold
for
swap
control
Swap
1
R/W
‐
20
10
50
3733 1st
heaters,
outside
air
temperature
threshold
for
unload
Low
L.
1
R/W
‐
20
10
50
3734 1st
heaters,
delta
‐
t
of
one
stage
DeltaT.1
R/W
1
8
20
3735 1st
heaters,
integral
time
control
Ti.
1
R/W
5
30
120
3736 2nd
heaters,
set
point
for
priority
inversion
starting
Swap
2
R/W/Z
0
0
1
3737 2nd
heaters,
delta
‐
t
of
one
compressor
DeltaT.2
R/W
1
8
20
3738 2nd
heaters,
integral
time
control
Ti.
2
R/W
5
30
120
3751 set
point
of
limit
maximum
power
Expert
Heater
Electrical
TriacMax
R/W
0
100
100
3761 opening
percentage
valve
for
freeze
protection
Leak
R/W
0
0
50
3762 outside
air
temperature
threshold
to
activate
function
Onset
R/W
‐
20
‐
20
50
3763 choice
to
close
or
open
valve
in
case
of
freezing
alarm
Freeze
R/W
0
0
1
Expert
Expert
Expert
Expert
Expert
Expert
Expert
Heater
Heater
Heater
Condenser
Expansion
Valve
Expansion
Valve
Heater
Hot
Water
Defrost
Circuit
1
Circuit
2
Configuration
Mode
Control
CLIMATIC
RT_UNITARY
‐
IOM
‐
1508
‐
E
.
92
.