• 63 •
77
Integer
R
0
~
65536
78
Integer
R
0
~
65536
CLIMATIC RT_UNITARY-IOM-1508-E
BMS
@Address
R/W
DESCRIPTION
MIN
Fact.
MAX
Alarm, 4
bit.0 = (241) Circuit 2, High Pressure, Sensor
bit.1 = (242) Circuit 2, Low Presure, Sensor
bit.2 = (243) Circuit 2, Liquid Temperature, Probe
bit.3 = (244) Circuit 2, Suction Temperature, Probe
bit.4 = (214) Circuit 2, Compressor, Electrical
bit.5 = (215) Circuit 2, High Pressure Cut Off
bit.6 = (216) Circuit 2, Reversing Valve, Blocked
bit.7 = (217) Circuit 2, Low Pressure Cut Off
bit.8 = (218) Circuit 2, Risk Of Frosting
bit.9 = (232) Circuit 2, Expansion Valve, Motor
bit.10 = (76) Circuit 2, Condenser fan, Inverter, Communication Bus
bit.11 = (202) Circuit 2, Condenser Fan
bit.12 = (203) Circuit 2, Condenser Fan, Inverter
bit.13 = (2) Water Condenser, Flow Switch Cut Off
bit.14 = (25) Water Condenser Temperature, Too Low
bit.15 = (26) Water Condenser Temperature, Too High
Alarm, 5
bit.0 = (84) Outside Humidity, Sensor
bit.1 = (23) Room Temperature, Too High
bit.2 = (24) Room Temperature, Too Low
bit.3 = (32) Room Humidity, Too Low
bit.4 = (33) Room Humidity, Too High
bit.5 = (21) Supply Temperature, Too High
bit.6 = (4) Blower, Filters, Dirty
bit.7 = (5) Blower, Filters, Missing
bit.8 = (89) Air Quality, Sensor
bit.9 = (29) Air Quality, Too High
bit.10 = (54) Recovery, Filters, Dirty
bit.11 = (31) Humidi
fi
er, Failure
bit.12 =
bit.13 =
bit.14 = (110) Circuit 1, Leak Refrigerant, Detected
bit.15 = (210) Circuit 2, Leak Refrigerant, Detected