Menu
Description
4th
digit
3rd
digit
2nd
digit
1st
digit
R/W/Z Min
Std
Max
2271 set
point
of
dehumidification
Sp.
Deh.
R/W/Z
0
10
100
2272 set
point
of
humidification
Sp.
Hum.
R/W/Z
0
0
100
2281 activation
of
tcb
feature
Mode
R/W
0
0
1
2282 state
of
'g'
signal
‐
G
R
0
0
1
2283 state
of
'b'
signal
‐
B
R
0
0
1
2284 state
of
'y1'
signal
‐
Y1
R
0
0
1
2285 state
of
'y2'
signal
‐
Y2
R
0
0
1
2286 state
of
'w1'
signal
‐
W1
R
0
0
1
2287 state
of
'w2'
signal
‐
W2
R
0
0
1
2311 state
of
configuration
Config.
R
0
0
21
2312 states
of
management
Status
R
23
23
62
2313 state
of
the
auxiliary
contact
State
iD
R
0
0
1
2314 state
of
the
relay
Relay
R
0
0
1
2315 count
value
of
operating
time
Run
Time
R
0
0
9999
2316 setpoint
for
activation
operation
of
component
Enabled
R/W/Z
0
1
1
2317 setpoint
for
activation
operation
in
room
control
dead
zone
Dead
Z.
R/W/Z
0
1
1
2318 temperature
threshold
for
activation
night
refreshment
function
Night
Eco
R/W
8
22
35
2321 state
of
configuration
Config.
R
0
0
21
2322 states
of
management
Status
R
23
23
62
2323 state
of
the
safety
contact
of
inverter
State
iD
R
0
0
1
2324 speed
percentage
calculated
for
the
inverter
Inverter
R
0
0
100
2325 speed
percentage
send
to
the
inverter
Output
R
0
0
24000
2326 calculated
value
of
air
flow
or
evaporator
flow
switch
Flow
R
0
0
24000
2327 choice
of
speed
function
Function
R/W
0
0
2
2328 nominal
threshold
for
air
flow
control
Flow
H.
R/W
0
85
100
2329 low
threshold
for
air
flow
control
Flow
L.
R/W
0
33
100
2331 state
of
configuration
Config.
R
0
0
21
2332 value
of
differential
pressure
sensor
on
air
flow
Delta
dP
R
0
0
1000
2333 air
flow
threshold
alarm
Air
Flow
R/W
0
25
1000
2334 filters
missing
threshold
alarm
Missing
R/W
0
50
1000
2335 dirty
filters
threshold
alarm
Dirty
R/W
50
250
1000
2341 state
of
smoke
detection
contact
User
Blower
Safety
Fire
iD
R
0
0
1
2411 state
of
configuration
Config.
R
0
0
21
2412 value
of
the
evaporating
pressure
or
temperature
Evap.
R
‐
1
‐
1
20
2413 value
of
the
suction
temperature
Suction
R
‐
99,9
0
99,9
2414 value
of
the
condensing
pressure
or
temperature
Cond.
R
‐
1
‐
1
45
2415 value
of
the
liquid
temperature
Liquid
R
‐
99,9
0
99,9
2416 low
pressure,
state
of
the
safety
Low
P.
R
0
0
1
2417 state
of
the
reversing
valve
R.Valve
R
0
0
1
2418 speed
percentage
calculated
for
the
inverter
Inverter
R
0
0
100
2419 speed
percentage
send
to
the
inverter
Output
R
0
0
1
2421 state
of
configuration
Config.
R
0
0
21
2422 states
of
management
Status
R
23
23
62
2423 state
of
the
auxiliary
contact
State
iD
R
0
0
1
2424 state
of
the
relay
Relay
R
0
0
1
2425 count
value
of
operating
time
Run
Time
R
0
0
9999
User
User
User
User
User
User
User
Control
Control
Blower
Blower
Blower
Compressor
Compressor
Circ.1
Comp.1
Tcb
Fan
Speed
Air
Flow
Circuit
1
Humidity
Sp
CLIMATIC
RT_UNITARY
‐
IOM
‐
1508
‐