Menu
Description
4th
digit
3rd
digit
2nd
digit
1st
digit
R/W/Z Min
Std
Max
3221 offset
for
room
temperature
value
Offset
R/W
‐
5
0
5
3222 room
temperature
threshold
for
unloading
cooling
mode
Limit
C.
R/W
0
0
40
3223 room
temperature
threshold
for
unloading
heating
mode
Limit
H.
R/W
0
40
40
3224 external
value
of
set
point
for
control
temperature
4
‐
20mA
R
‐
5
0
5
3225 Dynamic
set
point
(cooling
setpoint
offset
according
to
outside
temperature)
Sp.Dyna.
R/W/Z
0
20
20
3226 set
point
of
cooling
mode
Sp.Cool.
R/W/Z
8
22
35
3227 set
point
of
heating
mode
Sp.Heat.
R/W/Z
8
19
35
3228 integral
time
control
for
cooling
mode
Ti.Cool.
R/W
10
60
120
3229 integral
time
control
for
heating
mode
Ti.Heat.
R/W
10
60
120
3231 activation
of
the
smoothing
function
of
temperature
Smooth
R/W/Z
0
0
1
3232 low
limit
threshold
in
cooling
mode
Lim.Cool
R/W
4
4
58
3233 high
limit
threshold
in
heating
mode
Lim.Heat
R/W
4
38
58
3234 offset
for
high
limit
threshold
in
cooling
mode
Adj.Cool
R/W
‐
5
0
5
3235 offset
for
low
limit
threshold
in
heating
mode
Adj.Heat
R/W
‐
5
0
5
3236 outdoor
temperature
low
threshold
for
slope
on
the
supply
temperature
setpoint
Out.Low
R/W
‐
20
0
50
3237 coefficient
of
the
low
outside
temperature
for
the
slope
of
the
supply
temperature
setpoint
Coef.Low
R/W
‐
50
0
50
3238 outdoor
temperature
high
threshold
for
slope
on
the
supply
temperature
setpoint
Out.High
R/W
‐
20
30
50
3239 coefficient
of
the
high
outside
temperature
for
the
slope
of
the
supply
temperature
setpoint
Coef.High
R/W
‐
50
0
50
3241 setpoint
for
activation
operation
of
control
Enable
R/W/Z
0
0
1
3242 set
point
of
dehumidification
Sp.
Deh.
R/W/Z
0
100
100
3243 set
point
of
humidification
Sp.
Hum.
R/W/Z
0
0
100
3244 integral
time
control
for
dehumidification
Ti.
Deh.
R/W
10
60
120
3245 integral
time
control
for
humidification
Ti.
Hum.
R/W
10
60
120
3251 lower
supply
temperature
threshold,
1st
level
of
alarm
Sup
Lo.1
R/W
5
6
19
3252 lower
supply
temperature
threshold,
2nd
level
of
alarm
Sup
Lo.2
R/W
1
2
17
3253 upper
supply
temperature
threshold,
1st
level
of
alarm
Sup
Hi.1
R/W
20
40
70
3254 upper
supply
temperature
threshold,
2nd
level
of
alarm
Sup
Hi.2
R/W
20
60
70
3255 lower
room
temperature
threshold
of
alarm
Room
Lo.
R/W
5
5
40
3256 upper
room
temperature
threshold
of
alarm
Room
Hi.
R/W
5
40
40
3257 dew
point
control
DewPoint
R/W
0
0
1
3258 lower
room
humidity
threshold
of
alarm
Room
Lo.
R/W
0
0
100
3259 upper
room
humidity
threshold
of
alarm
Room
Hi.
R/W
0
100
100
3261 state
of
unload
cooling
mode
by
BMS
Cool.Mod
R/W
0
0
1
3262 state
of
unload
cooling
mode
by
BMS
Heat.Mod
R/W
0
0
1
3263 value
of
the
outside
temperature
send
by
BMS
Out.
T.
R/W
‐
99,9
‐
99,9
99,9
3264 value
of
the
room
temperature
send
by
BMS
Room
T.
R/W
‐
99,9
‐
99,9
99,9
3265 value
of
the
outside
humidity
send
by
BMS
Out.
Hr.
R/W
0
0
100
3266 value
of
the
room
humidity
send
by
BMS
Room
Hr.
R/W
0
0
100
3311 choice
of
air
flow
sensor
AirFlow
R/W
0
0
1
3312 choice
of
inverter
Modul.
R/W
0
0
2
3313 choice
of
kit
Kit
R/W
0
0
5
3314 choice
of
motor
size
Motor
R/W
0
0
10
3315 choice
of
fan
type
Fan
R/W
0
0
4
3321 setpoint
for
activation
operation
of
component
Enable
R/W/Z
0
1
1
3322 setpoint
for
activation
operation
in
room
control
dead
zone
Dead
Z.
R/W/Z
0
0
2
3323 temperature
threshold
for
activation
night
refreshment
function
Night
Eco
R/W
8
22
35
3324 time,
cyclic
dead
zone
function,
fan
on
Time
On
R/W
0
300
32400
3325 time,
cyclic
dead
zone
function,
fan
off
Time
Off
R/W
0
3300
32400
Expert
Expert
Expert
Expert
Expert
Expert
Expert
Control
Control
Blower
Control
Control
Control
Blower
Configuration
Mode
Room
Supply
Humidity
Safety
Bms
CLIMATIC
RT_UNITARY
‐
IOM
‐
1508
‐
E
.
90
.