IOM BASIC CLIMATIC CONTROLLER - Page 15
parameters lists
Settings
Access
Ref.
Configuration Parameters
Unit Min Max Factory
General Password
Factory
Adjust.
Hidden
H32 Configuration of Input ID10
2 = Remote ON / OFF
Num 0 28 2
-
X X
H33 Configuration of Input ID11
1 = Flow Switch
Num 0 28 1
-
X X
H34 Configuration ST4 (if Digital Input)
Num
0
28
0
-
X X
H35 Configuration of output RL2
9 = Compressor step 2
Num 0 17 9
-
X X
H36 Configuration of output RL3
0 = Disabled, 11= Compressor step 4
Num 0 17 11
-
X X
H37 Configuration of output RL4
0 = Disabled, 16 = Compressor step 5
Num 0 17 16
-
X X
H38 Configuration of output RL5
12 = Fan 2 Circuit 1
Num 0 17 12
-
X X
H39 Configuration of output RL6
13 = Fan 3 Circuit 1
14 = Fan 2 Circuit 2
Num 0 17 13
-
X X
H40 Configuration of output RL7
7 = Pump
Num 0 17 7
-
X X
H41 Polarity RL2
Flag
0
1
0
-
X X
H42 Polarity RL3
Flag
0
1
0
-
X X
H43 Polarity RL4
Flag
0
1
0
-
X X
H44 Polarity RL5
Flag
0
1
0
-
X X
H45 Alarm relay polarity
0 = Output ON if Alarm Active
1 = Output OFF if Alarm Active
Flag 0 1
0
-
X X
H46 Configuration fan 1 Circuit 1 output
0 = Triac output from TK1
1 = 4-20mA output from AN1
2 = Solid State Relay Output from TK1
Flag 0 2
2
-
X X
H47 Configuration fan 1 Circuit 2 output
0 = Triac output from TK1
1 = 4-20mA output from AN1
2 = Solid State Relay Output from TK1
Flag 0 2
2
-
X X
H48 Configuration serial protocol
0 = BMS Communications Disabled
1 = BMS Communications enabled
Flag 0 1
0
-
X X
H49 Selection of operating mode
0 = Selection by Keyboard
Flag 0 1
0
-
X -
H50 Enable dynamic set point
0 = Disable, 1 = Enable
Flag 0 1
0
-
-
X X
H51 Offset of dynamic set point during cooling
°C
-50
80
30
-
-
X X
H52 Offset of dynamic set point during heating
°C
-50
80
30
-
-
X X
H53 Dynamic outdoor temp. set point during cooling
°C
-127 127
35
-
-
X X
H54 Dynamic outdoor temp. set point during heating
°C
-127 127
-5
-
-
X X
H55 Delta dynamic outdoor temp. set point during
cooling
°C -50 80 25
-
-
X X
H56 Delta dynamic outdoor temp. set point during
heating
°C -50 80 28
-
-
X X
H57 Offset Sensor 1
°C -12.7 12.7
0
-
X X
H58 Offset Sensor 2
°C -12.7 12.7
0
-
X X
H59 Offset Sensor 3 (Note : °C/10, Kpa*10)
°C /
Kpa
-127 127 -10
-
X X
H60 Offset Sensor 4
°C -12.7 12.7
0
-
X
H61 Offset Sensor 5
°C -12.7 12.7
0
-
-
X X
H62 Offset Sensor 6 (Note : °C/10, Kpa*10)
°C /
Kpa
-127 127
-6
-
X X
H63 Voltage Frequency
0=50 Hz 1=60 Hz
Flag 0 1
0
-
X -
H64 Temperature Display
0= °C 1=°F
Flag 0 1
0
-
X X
H65 Family serial address
Used to set the Address of the controller when using a
Modbus Interface
Num 0 14 0
-
X X
H66 Device serial address
Used to set the Address of the controller when using a
Modbus Interface
Num 0 14 0
-
X X
H67 User password
Num
0
255
See LENNET
-
X X
H68 Copy card password
Factory use only
Num 0 255
See LENNET
-
X X
H69 Keyboard Present
Flag
0
1
1
-
X X