IOM BASIC CLIMATIC CONTROLLER - Page 3
This equipment is an electronic device that controls
packaged water cooling systems.
The thermostat allows the following operations:
- Unit ON/OFF
- Select system operating mode
- Set point adjustment
- Alarm signal relay
- Display temperature
- Status of the unit alarms
- Possibility of remote ON/OFF.
- A remote controller as an option
The control supplied incorporated on the unit contains the
following devices:
REGULATION:
The control makes the system regulation as follow:
- The signals of analogue inputs through the inlet and outlet
temperature and from the refrigerant piping temperature.
- Receives digital inputs through the status of low, high and
pressostat, flow switch (water flow) status and from electrical
protection of fans and compressor.
According to the valves and status of analogue and digital
inputs manages.
The out put signals; compressor, fan and water pump
operating, obtaining the regulation of the inlet water
temperature to the unit, regulating the speed of the air fan
volume, output signals water.
Heater, water tank heater, and hot gas valve (all these
elements are an option) used to protect the unit, and also
activates the alarm codes about, setting pressurestat, flow
switch, water flow, and the electrical protection of fan and
compressor (see alarm section).
- A group of parameters allow the control be programmed
for each application within factory set limitations.
GENERAL DESCRIPTION
The control supplied incorporated on the unit
contains the following devices :
CLIMATIC BASIC CONTROLLER
- Keypad
Located within the unit.
- Control Module
Located at the electrical box
This device controls the operation of the unit,
allowing the regulation of the system.
- Fan Control
Located at the electrical box
Allows the fan voltage to be varied in respect of the
condensing temperature.
A remote controller is offered as an option.
To install this optional remote controller proceeded
as
follow:
- Connect exactly as indicated in electrical diagram
- The wire should not exceed
5
0 m.
The three cables for connection from the keypad
to the power board must be kept separate from
other cables, using an individual cable channel;
and use shielded cables, with a cross-section of
1 mm
2
.
Keypad located
within the unit
Control Module
Fan control plate
Terminal block
Electrical box at the unit
Remote controller (optional)
Three-lead shielded cable
with a cross-section of 1mm
2
* Connection to be made by user MAXIMUM LENGTH 50m