Page 14 - IOM BASIC CLIMATIC CONTROLLER
parameters lists
Settings
Access
Ref.
Control Setpoints
Unit Min Max Factory
General
Password
Factory
Adjust.
Hidden
G01 Cooling Setpoint
°C
6
12
6.5
X
G02 Heating Setpoint
°C
0
0
0
-
-
X X
Settings
Access
Ref.
Configuration Parameters
Unit Min Max Factory
General
Password
Factory
Adjust.
Hidden
H01 Maximum Heating Set Point
°C
0
90
0
-
-
X X
H02 Minimum Heating Set Point
°C
-40
0
0
-
-
X
X
H03 Maximum Cooling Set Point
°C
6
90
12
X
- -
H04 Minimum Cooling Set Point
°C
-40
12
6
-
X X
H05 Number of Circuits (Chiller dependant)
Num
0
2
2
-
X X
H06 Compressors per Circuit (Chiller Dependant)
Num
0
4
2
-
X X
H07 Capacity Steps per compressor
Num
0
3
0
-
X
X
H08 Compressor ON sequence
0 = Start Compressor with least running hours, Stop
Compressor with most running hours.
1 = Start Compressor 1, 2, 3. Stop Compressor 3,2,1
Flag 0 1
0
-
X X
H09 Circuit balancing
0 = Start Compressors in Circuit 1 before Circuit 2
1 = Balance the Compressors in both Circuits
Flag 0 1
0
-
X X
H10 Heat Pump
0 = Chiller, 1 = Heat Pump
Flag 0 1
0
-
X
X
H11 Configuration of Sensor ST1
1 = Entering Water Temperature
Num 0 4
1
-
X X
H12 Configuration of Sensor ST2
1 = Leaving Water Temperature
Num 0 3
1
-
X X
H13 Configuration of Sensor ST3
2 = 4-20Ma Condenser Pressure Circuit 1
Num 0 5
2
-
X X
H14 Configuration of Sensor ST4
3 = Outside Air Temperature
Num 0 3
3
-
X X
H15 Configuration of Sensor ST5
0 = No Probe
Num 0 1
0
-
X X
H16 Configuration of Sensor ST6
2 = 4-20Ma Condenser Pressure Circuit 2
Num 0 4
2
-
X X
H17 Bottom of scale pressure value
KPa*10
0 350 300 -
X X
H18 Polarity of Input ID1 ID2 ID3 ID4
Num
0
15
15
-
X X
H19 Polarity of Input ID5 ID6 ID7 ID8
Num
0
15
15
-
X X
H20 Polarity of Input ID9 ID10 ID11 ST4
Num
0
15
15
-
X X
H21 Polarity of Input ST1 (if Digital Input)
Flag
0
1
0
-
X
X
H22 Polarity of Input ST2 (if Digital Input)
Flag
0
1
0
-
X
X
H23 Configuration of Input ID1
10 = HIGH Pressure Circuit 1
Num 0 28 10
-
X X
H24 Configuration of Input ID2
12 = LOW Pressure Circuit 1
Num 0 28 12
-
X X
H25 Configuration of Input ID3
8 = Cond. Fan Thermal Overload Circuit 1
Num 0 28 8
-
X X
H26 Configuration of Input ID4
4 = Compressor Thermal Overload Circuit 1
Num 0 28 4
-
X X
H27 Configuration of Input ID5
11 = HIGH Pressure Circuit 2
Num 0 28 11
-
X X
H28 Configuration of Input ID6
13 = LOW Pressure Circuit 2
Num 0 28 13
-
X X
H29 Configuration of Input ID7
9 = Cond. Fan Thermal Overload Circuit 2
Num 0 28 9
-
X X
H30 Configuration of Input ID8
? = Compressor Thermal Overload Circuit 2
Num 0 28 ?
-
X X
H31 Configuration of Input ID9
0 = Not Used
Num 0 28 0
-
X X