• 84 •
0
1
+VRL (
≈
30 Vdc)
2
GND
3
Rx/Tx-
4
RX/Tx+
5
GND
6
+VRL (
≈
30 Vdc)
BALTIC-IOM-0412-E / Control manual
Jumpers:
The "displays" are directly supplied by the Climatic™ board with a 30 VDC power supply. Pay attention to the value of this voltage
when multiple cards are used.
J14 and J15 closed or cut the power supply:
• J14 and J15 set between 1-2: connectors A, B, C and SC are in parallel. Power is available on all connectors.
• J14 and J15 set between 2-3: B and C connectors are supplied in parallel but the connectors A and SC are not. Displays connected
to these ports are not powered.
If J14 and J15 are set differently, the DT50 dispatcher DOESN'T WORK and therefore connected displays don't work.
Terminal
Wire function
Connections
Earth
Shield
1st pair A
2nd pair A
3rd pair A
3rd pair B
2nd pair B
1st pair B
CONNECTION ON THE DT50 SPLITTER
DT50 dispatcher installation guide
The board is equipped with three RJ12 phone jacks and a screw connector (SC).
Display's ferrites protection
To avoid appearance of RF interference that may cause destruction of components in the displays, you need to equip the cable of a
ferrite, during its installation (provided by LENNOX).
DISPLAY DM60
Содержание BAC 024 SNM 3M
Страница 1: ...20 85 kW Installation operating and maintenance BALTIC IOM 0412 E BALTIC Rooftop units air cooled...
Страница 2: ......
Страница 4: ......
Страница 76: ...72 BALTIC IOM 0412 E Service manual...
Страница 98: ...94 BALTIC IOM 0412 E Certificates CE CONFORMITY DECLARATION...
Страница 99: ...95 BALTIC IOM 0412 E Certificates CE CONFORMITY DECLARATION...
Страница 101: ...97 BALTIC IOM 0412 E Certificates CERTIGAZ...