BALTIC-IOM-0412-E / Service manual
SERVICE DIAGNOSTIC
Electric heater
Water leaks
CLIMATIC™ Displays
Fault
Possible cause and symptoms
Solution
High temperature trip out on
electric heater
Low air
fl
ow rate
Measure and estimate the air
fl
ow and pressure and compare
with the speci
fi
cation from customer.
Incorrect position of the klixon
Check that the klixon, is positioned in the air
fl
ow, relocate
klixon if necessary
Check that there is no heat transfer from the klixon support.
Fault
Possible cause and symptoms
Solution
Water found in the ventilation
section
Cooling mode:
water carried away from the coil because of
excessive air
fl
ow and speed on the coil.
Estimate the air
fl
ow rate and check the speed is lower than
2,8 m/s
Low air pressure in the compartment due to
a high air
fl
ow rate or a high pressure drop
before the fan
Check
fi
lter
Reduce air
fl
ow rate
Check seals around the ventilation section.
Check the door seal
Check for the presence of silicone seals in the corners of the
door and at the bottom of the refrigeration section bulkhead.
Water ingress in the
fi
lter
compartment
Water ingress through a leaking fresh air hood
or when running 100% fresh air
Check the seals and
fl
anges in the fresh air hood
Reduce the air
fl
ow rate if necessary
Fault
Possible cause and symptoms
Solution
Nothing is written on the screen
but it’s enlightened
Idem
Press on the three right-hand side’s buttons at the same time
during a few seconds then recon
fi
gure display address setting
at 32.
Nothing occurs on the unit or an
option disappeared
Possible problem of units' con
fi
guration
Check the instructions from 3811 to 3833 and recon
fi
gure
options if necessary.
The message “no link” appears
Problem of addresses’ recognition
Disconnect the DS from the unit and then reconnect it.
All the units are extinct
Problem main board plan addressing
Disconnect then re-plug; disconnect each unit from the others
then change all the plan addresses
Содержание BAC 024 SNM 3M
Страница 1: ...20 85 kW Installation operating and maintenance BALTIC IOM 0412 E BALTIC Rooftop units air cooled...
Страница 2: ......
Страница 4: ......
Страница 76: ...72 BALTIC IOM 0412 E Service manual...
Страница 98: ...94 BALTIC IOM 0412 E Certificates CE CONFORMITY DECLARATION...
Страница 99: ...95 BALTIC IOM 0412 E Certificates CE CONFORMITY DECLARATION...
Страница 101: ...97 BALTIC IOM 0412 E Certificates CERTIGAZ...