BALTIC-IOM-0412-E / Service manual
FILTERS
Filter replacement
After opening the
fi
lter access panel, lift the
fi
lter retaining log. The
fi
lters can then be removed and replaced easily by sliding the dirty
fi
lters out and clean ones in.
The CLIMATIC™ 60 controller can monitor the pressure drop across the
fi
lter
The following set points can be adjusted depeding on the installation.
• “Air
fl
ow”
in page
3343
= 25Pa by default
• “No
fi
lter “
in page
3344
= 50Pa by default
• “Dirty Filter” in page
3345
= 250Pa by default
The actual pressure drop measured accross the coil can be read on the CLIMATIC™ Display in menu
3342
.
The following faults may be identi
fi
ed
• Fault code
001
AIRFLOW FAILURE, if measured
Δ
P across the
fi
lter and coil is below the value set in page
3343
• Fault code
004
DIRTY FILTERS, if measured
Δ
P across the
fi
lter and coil is above the value set in page
3344
• Fault code
005
MISSING FILTERS, if measured
Δ
P across the
fi
lter and coil is below the value set in page
3345.
Содержание BAC 024 SNM 3M
Страница 1: ...20 85 kW Installation operating and maintenance BALTIC IOM 0412 E BALTIC Rooftop units air cooled...
Страница 2: ......
Страница 4: ......
Страница 76: ...72 BALTIC IOM 0412 E Service manual...
Страница 98: ...94 BALTIC IOM 0412 E Certificates CE CONFORMITY DECLARATION...
Страница 99: ...95 BALTIC IOM 0412 E Certificates CE CONFORMITY DECLARATION...
Страница 101: ...97 BALTIC IOM 0412 E Certificates CERTIGAZ...