INNOV@-pCO1-IOM-0907-E
7
2.2.1 Close control units with direct expansion coil
Humidity set
HUMIDIFICATION DEHUMIDIFICATION
100% 0% 100%
48.0 50.0
52.0
Ambient
2.0% 2.0%
humidity (%)
Humidification proportional band Dehumidification proportional band
1 COMPRESSOR
ON-OFF CONTACT
+ Capacity control, if any
48.0 50.0 52.0
Ambient
humidity (%)
0-10Volt MODULAT. OUTPUT
100%
COMP. 1 + COMP. 2 +
0% c.c., if any c.c., if any
48.0 50.0 51.0 52.0
Ambient
humidity (%)
100% INTEGRATED HUMIDIFIER
30%
48.0 49.8 50.0
Ambient
humidity (%)
2.2.2 Other humidity functions
Humidity set
100% 100%
48.0 50.0 52.0
Ambient
2.0% 2.0%
humidity (%)
Humidification proportional band Dehumidification proportional band
100%
0-10V COLD WATER VALVE
0%
50.0 52.0
Ambient
humidity (%)
100%
THREE-P. COLD WATER VALVE
0%
50.0 52.0
Ambient
humidity (%)
The high and low humidity alarms cause alarm screen signalling and have modifiable delay time.