7 LIST OF PARAMETERS AND DEFAULT VALUES
The table below lists the parameters in the program, together with the following information: screen code (the
screen code is displayed at the top right) to assist the identification of the parameter, the default value, the
minimum and maximum limits (range), and the unit of measure.
To find a specific parameter on the display, proceed as follows:
Identify the parameter in the table below and the corresponding screen code
Using the list of the screens (following paragraph) and the screen code, access the screen on the
display
PARAMETER DESCRIPTION
SCREEN
DEFAULT
SPECIAL VALUE
RANGE
UOM
Maintenance Menu
Select display language
A0
English
En, It, Fr, De
Enter password
A6
----
0-9999
Modify outlet fan operating hours
A7
0
0-99 . 0-999
hours
Modify compressor 1 operating hours
A7
0
0-99 . 0-999
hours
Modify compressor 2 operating hours
A7
0
0-99 . 0-999
hours
Device operating hour threshold: main fan
A8
99
0-99
hours x
1000
Device operating hour threshold: compr. circuit 1
A8
99
0-99
hours x
1000
Device operating hour threshold: compr. circuit 2
A8
99
0-99
hours x
1000
Humidity probe calibration
A9
0
-9.9
–
9.9
%RH
Condenser 1 pressure probe calibration
A9
0
-99.9
–
99.9
bar
Condenser 2 pressure probe calibration
A9
0
-99.9
–
99.9
bar
Ambient temperature probe calibration
Aa
0
-99.9
–
99.9
°C / °F
External temperature probe calibration
Aa
0
-99.9
–
99.9
°C / °F
Supply temperature probe calibration
Aa
0
-99.9
–
99.9
°C / °F
Recovery temperature probe calibration
Ab
0
-99.9
–
99.9
°C / °F
Condenser 1 temperature probe calibration
Ab
0
-99.9
–
99.9
°C / °F
Condenser 2 temperature probe calibration
Ab
0
-99.9
–
99.9
°C / °F
Manual activation of digital outputs 1
–
2
–
3
Ac
Off
Off
–
On
Manual activation of digital outputs 4
–
5
–
6
Ad
Off
Off
–
On
Manual activation of digital outputs 7
–
8
–
9
Ae
Off
Off
–
On
Manual activation of digital outputs 10
–
11
–
13
Af
Off
Off
–
On
Manual activation of modulating outputs 1
–
2
Ag
0
0-10.0
Volt
Manual activation of modulating outputs 3
–
4
Ah
0
0-10.0
Volt
Manual activation of pre wash built-in humidifier
Ai
No
No-Yes
Manual activation of total water drain built-in
humidifier
Ai
No
No-Yes
Hum. management: periodic drain enable
Ai1
No
No-Yes
Hum. management: periodic drain period
Ai1
120
0-120
hours
Hum. management: stop delay
Ai2
0
0-120
seconds
Hum. management: drain for inactivity period
Ai2
3
1-199
hours
Hum. management: threshold running hours
Ai3
4000
0 - 4000
hours
Driver 1 valve control mode
Aj
Automatic
Auto-Man.
Driver 1 valve manual opening steps
Aj
0
0-9999
Steps
Driver 2 valve control mode
Ak
Automatic
Auto-Man.
Driver 2 valve manual opening steps
Ak
0
0-9999
Steps
Driver 1 manual release on start-up
Al
No
No-Yes
Driver 2 manual release on start-up
Am
No
No-Yes
Enter new Maintenance password
An
----
0-9999
Printer Menu
Cyclical print interval
H1
24
0-999
hours
Send immediate print
H1
No
No-Yes
Clock Menu
Hour setting
K0
current hour
0-23
hours
Minute setting
K0
current minutes
0-59
minutes
Day setting
K0
current day
1-31
Month setting
K0
current month
1-12
Year setting
K0
current year
0-99
Enter Clock password
K1
----
0-9999