30
INNOV@-pCO1-IOM-0907-E
PARAMETER DESCRIPTION
SCREEN
DEFAULT
SPECIAL VALUE
RANGE
UOM
Number of rings for analogue modem
Ph
0
0-9
Password for supervisor remote connection
Ph
0
0-9999
Type of analogue modem
Ph
Tone
Tone-Pulse
Enter new user password
Pi
----
0-9999
Manufacturer Menu
Enter manufacturer password
Z0
----
0-9999
CONFIGURATION
-->
Enable BMS
C0
No
No-Yes
Enable printer
C0
No
No-Yes
Select unit of measure for temperature probes
and parameters
C0
ºC
ºC-ºF
Enable clock board
C0
No
No-Yes
Type of unit
C1
ED
ED-CW
Select refrigerant
C1
R407C
R22,R134a,
R404a, R407C,
R410A
Number of compressors
C2
2
1-2
Enable compressor capacity-control steps
(unloaders)
C2
No
No-Yes
Heating mode
C2
Heaters
Heaters-Battery
Humber of heaters
C2
2
0-1-2-Binary
Type of valve for heating battery
C2
0-10Volt
0-10V / 3 points
Type of coil
C3
C/H
C/H-Cool
Type of valve for the coil
C3
0-10Volt
0-10V/ 3 points
Heating mode
C3
Heaters
Heaters-Battery 2
Humber of heaters
C3
2
0-1-2-Binary
Type of valve for heating coil
C3
0-10Volt
0-10V/3 points
Digital input 5 configuration
C4
Filter alarm
Flood alarm, Filter
alarm, Fire alarm
Digital input 12 configuration
C5
Fire/smoke alarm
Fire/smoke alarm,
Water Flood alarm
Digital input 1 configuration
C6
Fire/smoke alarm
Fire/smoke alarm,
Water Flood alarm
Digital output 7 configuration
C7
Light alarm relay
Recovery valve,
Light alarm relay
Analog input 2 configuration
C8
Pressure circ. 1
Pressure circ.1,
Temp. circ. 1,
Supply air temp.
Analog input 3 configuration
C9
Pressure circ. 2
Pressure circ.2,
Temp. circ. 2,
Recovery temp.
Modulating output 1 configuration
Ca
Main fan damper
Recovery damper,
Main fan damper
Recovery type
Ca
Air
Air, Water
Enable analog humidifier output
Ca
No
No-Yes
Analog output 2 configuration
Cb
Recovery damper
Recovery damper,
Humidif. damper
Recovery damper enable
Cc
No
No-Yes
Main fan damper presence
Cc
No
No-Yes
Enable condensation function
Cd
No
No-Yes
Type of condenser
Cd
Single
Single-Separat.
Condensing output type
Cd
Inverter
Inverter-Steps
Select number of condensing fans
Cd
1
1-2
Maximum voltage threshold for Triac
Ce
92,0
0-100
%
Minimum voltage threshold for Triac
Ce
7,0
0-100
%
Duration of Triac impulse
Ce
2
0-10
m
seconds
Logic of the dehumidification contact
Cf
NC
NO-NC
Number of compressors enabled for
dehumidification
Cf
0
0-2
Enable cooling coil for dehumidification
Cf
No
No-Yes
Enable built-in humidifier
Cf
No
No-Yes
Type of humidifier
Cg
3 Kg/h 400V 3Ph
3 Kg/h / 8 Kg/g
Maximum production
Cg
70.0
0-100.0
%
Humidifier board type
Cg
PCOUMID000
PCOUMID200-
PCOUMID000
Enable humidity probe
Ch
Yes
No-Yes
Type of signal from the humidity probe
Ch
Current
0-1V, 0-10V,
Current