PARAMETER DESCRIPTION 

SCREEN 

DEFAULT 

SPECIAL VALUE 

RANGE 

UOM 

 

 

 

 

 

 

High conductivity alarm threshold 

Gb 

2000 

 

0-2000 

uS/cm 

Drain time as % of the manufacturer value 

Gc 

100 

 

50-200 

Drain frequency as % of the manufacture value 

Gc 

100 

 

50-200 

High pressure alarm set point 

Gd 

23.5 

 

-99.9 - 99.9 

bar 

High pressure alarm differential 

Gd 

1.0 

 

-99.9 - 99.9 

bar 

Condensing (pressure) setpoint 

Ge 

19.0 

 

-99.9 - 99.9 

bar 

Condensing (pressure) differential 

Ge 

4.0 

 

-99.9 - 99.9 

bar 

Modulating condensing fan speed-up time 

Ge 

30 

 

0-999 

seconds 

Condensing (temperature) setpoint 

Gf 

55.0 

 

-99.9 - 99.9 

ºC / ºF 

Condensing (temperature) differential 

Gf 

1.0 

 

-99.9 - 99.9 

ºC / ºF 

Modulating condensing fan speed-up time 

Gf 

30 

 

0-999 

seconds 

Maximum and Minimum condensing fan speed 

Gg 

10.0 / 0.0 

 

0-10.0 

Volt 

Enable high pressure alarm Prevent function 

Gh 

Yes 

 

No-Yes 

bar 

Prevent function set point (pressure) 

Gh 

20.0 

 

-99.9 - 99.9 

bar 

Prevent function differential (pressure) 

Gh 

2.0 

 

-99.9 - 99.9 

bar 

Enable high temperature alarm Prevent function 

Gi 

Yes 

 

No-Yes 

bar 

Prevent function set point (temperature) 

Gi 

70.0 

 

-99.9 - 99.9 

ºC / ºF 

Prevent function differential (temperature) 

Gi 

1.0 

 

-99.9 - 99.9 

ºC / ºF 

Enable Master Control function 

Gj 

No 

 

No-Yes 

 

Rotation mode for units in pLAN network 

Gk 

Automatic 

 

Automatic, 

Timezones, 

Running Hours 

 

Number of units set in Standby mode 

Gk 

 

0-Number of unit in 

Present/Rotat. 

mode 

 

Automatic rotation period for units in pLAN 

Gk 

24 

 

1-240 

Hours 

Timezones rotation hour for units in pLAN network 

Gl 

22 

 

0-23 

Hours 

Timezones rotation minutes for units in pLAN 
network 

Gl 

00 

 

0-59 

minutes 

Interval in days for timezones rotation in pLAN 
network 

Gl 

 

1-7 

days 

Enable Force units by temperature in pLAN 
network 

Gm 

No 

 

No-Yes 

 

Forcing delay for low and high ambient 
temperature 

Gm 

3 / 3 

 

0-999 

minutes 

Low room temp. diff. for forcing units in network 

Gn 

 

0-99.9 

ºC / ºF 

Low room temp. offset for forcing units in network 

Gn 

 

0-99.9 

ºC / ºF 

High room temp. diff. for forcing units in network 

Go 

 

0-99.9 

ºC / ºF 

High room temp. offset for forcing units in network 

Go 

 

0-99.9 

ºC / ºF 

Analog supply fan speed setting 

Gp 

80 

 

0-100% 

CAREL EXV DRIVERS 

--> 

 

 

 

 

 

Number of drivers connected 

F0 

 

0-2 

 

Enable backup battery driver 1 

F0 

No 

 

No-Yes 

 

Enable backup battery driver 1 

F0 

No 

 

No-Yes 

 

Type of valve circuit 1 

F1 

10 (Carel E2V**P) 

 

0-11 

 

Superheating set point circuit 1 

F1 

6.0 

 

2.0-50.0 

ºC 

Dead zone circuit 1 

F1 

 

0-9.9 

ºC 

Type valve circuit 2 

F2 

10 (Carel E2V**P) 

 

0-11 

 

Superheating set point circuit 2 

F2 

6.0 

 

2.0-50.0 

ºC 

Dead zone circuit 2 

F2 

 

0-9.9 

ºC 

PID control 

 proportional gain circuit 1 

F3 

2.5 

 

0.0-99.9 

 

PID control 

 integration time circuit 1 

F3 

30 

 

0-999 

seconds 

PID control 

 derivative time circuit 1 

F3 

5.0 

 

0.0-99.9 

seconds 

PID control 

 proportional gain circuit 2 

F4 

2.5 

 

0.0-99.9 

 

PID control 

 integration time circuit 2 

F4 

30 

 

0-999 

seconds 

PID control 

 derivative time circuit 2 

F4 

5.0 

 

0.0-99.9 

seconds 

Threshold for low superheat protection circuit 1 

F5 

4.0 

 

-4.0 - 10.0 

ºC 

Prot. threshold integration time, low superheat 
circuit 1 

F5 

1.0 

 

0-25.5 

seconds 

Threshold for low superheat protection circuit 2 

F6 

4.0 

 

-4.0 - 10.0 

ºC 

Prot. threshold integration time, low superheat 
circuit 2 

F6 

1.0 

 

0-25.5 

seconds 

Percentage ratio between cooling capacity and 
Driver capacity C 1 

F7 

30 

 

0-100 

Percentage ratio between cooling capacity and 
Driver capacity C 2 

F7 

30 

 

0-100 

LOP threshold 

F8 

-40.0 

 

-70.0 - 50.0 

ºC 

LOP threshold integration time 

F8 

4.0 

 

0-25.5 

seconds 

MOP start delay 

F9 

30 

 

0-500 

seconds 

MOP threshold 

F9 

16.0 

 

-50.0 - 99.9 

ºC 

Содержание @DNOVA pCO1

Страница 1: ...lennoxemeia com DNOVA pCO1 Manuel d installation mise en service et maintenance Microprocesseur INNOVA pCO1 IOM 0907 F...

Страница 2: ......

Страница 3: ...lose contr units with direct expan coil 9 2 3 3 Recovery with cooling devices on close control units with water coils 10 2 4 Outlet limit 11 2 5 Condenser fans 12 2 5 1 Single or separate coils 12 2 5...

Страница 4: ...3 5 1 Table of alarms 23 5 2 Alarm data logging 24 5 3 Main log 24 6 SCREENS 26 6 1 List of the screens 26 7 LIST OF PARAMETERS AND DEFAULT VALUES 28 8 ARCHITECTURE OF THE CONTROL SYSTEM 34 8 1 Microp...

Страница 5: ...arnings complete management of devices timing connection with local and BMS supervisory networks Carel Modbus LonWorks 1 2 LCD user interface The LCD user interface displays the following data measure...

Страница 6: ...and end opening parameters correspond to 0 and 100 respectively default values and are different for the two valves if need be the values may be modified to delay opening start and bring complete ope...

Страница 7: ...5 C Dehumid stop different 10 C 10 C Low temperature alarm High temperature alarm 2 1 3 Close control units with two water coils These close control units are equipped with a warm water coil and a col...

Страница 8: ...enabled based on the difference between the two values The proportional band identifies the air conditioning unit working range and can take different values in humidification and dehumidification mod...

Страница 9: ...Volt MODULAT OUTPUT 100 COMP 1 COMP 2 0 c c if any c c if any 48 0 50 0 51 0 52 0 Ambient humidity 100 INTEGRATED HUMIDIFIER 30 48 0 49 8 50 0 Ambient humidity 2 2 2 Other humidity functions Humidity...

Страница 10: ...Dehumid band 10 0 10 0 Low humidity alarm High humidity alarm 2 3 Recovery coil Recovery is an optional function an additional cold coil using water coming from an external source i e evaporation tow...

Страница 11: ...OFF CONTACT 23 0 23 5 26 5 Ambient temp C 0 10V RECOVERY VALVE 100 0 23 0 23 5 26 5 Ambient temp C 2 3 2 Recovery with cooling devices on close contr units with direct expan coil With recovery coil e...

Страница 12: ...C 2 OFF 0 10Volt c c c c 23 0 23 5 24 6 24 9 25 1 25 6 26 1 26 5 Ambient temp C 2 3 3 Recovery with cooling devices on close control units with water coils The following diagram shows how the cold coi...

Страница 13: ...23 5 24 2 25 0 25 7 26 5 Ambient temp C 0 10V COLD WATER VALVE 100 0 23 0 23 5 26 5 Ambient temp C THREE POINT COLD WATER VALVE 100 0 23 0 23 5 26 5 Ambient temp C As shown in the diagram if outlet te...

Страница 14: ...uts can be set in case the set minimum speed is higher than 0V the fan is operated at minimum speed 1 0 bar below the condensation set point before switching off as indicated in the diagram above 2 5...

Страница 15: ...branch I O screens display the temperature value corresponding to the pressure of each probe based on the coolant type to be selected in the Manufacturer branch 2 6 Temperature set point compensation...

Страница 16: ...If for example the maximum number of starts per hour allowed by the default values is 10 this limit can be respected by setting a 360 second time interval 2 7 3 Compressor alarms Compressors alarms ar...

Страница 17: ...m one to the other to avoid simultaneous peaks 2 8 1 Heater alarms Each heater is provided with a digital input to be connected with a compressor overload or differential for signalling any failure Im...

Страница 18: ...art modulating their opening range based on the control request 2 9 2 0 10Volt VALVES These valves use a 0 10Volt modulating signal coming from the microprocessor to modify their opening range from 0...

Страница 19: ...ER MANUFACTURER ESC key Press ESC key to go out from a menu and come back into the main screen UP key Press UP key to move into the next screen or to increment the value of a parameter ENTER key Press...

Страница 20: ...he standard telephone cable because in the remote display cable the connectors are reversed Local display panel mounted Remote display wall mounted Microprocessor pCO1 Unit Derivator TCONN it is neces...

Страница 21: ...e UP keys press UP or DOWN key to set the address press ENTER key to save and exit from this procedure 4 1 2 Address configuration of the PGD For the configuration of the address of the PGD follow the...

Страница 22: ...evice is required 4 2 1 Stand alone unit 4 2 2 Units connected in LAN max 8 units The units can be connected to the other units in LAN local area network for a maximum of 8 units Each unit can be conn...

Страница 23: ...een is displayed continue for another 5 seconds until the following screen is displayed As it can be seen network addresses from 1 to 32 are displayed together with a symbol indicating if a display sm...

Страница 24: ...applications or the flash1 bin file in the program being loaded for LAN applications 13 Click UPLOAD to start the file download procedure which will take approximately 1 to 5 minutes depending on the...

Страница 25: ...abled alarms only disappear whereas the other alarms keep displayed and the buzzer and the red led switch on again Alarms are divided into two categories manually rearmed alarms or automatically rearm...

Страница 26: ...gh conductivity alarm See threshold Gb delay 1h Humidifier A61 Built in humidifier high conductivity pre alarm See threshold Gb delay 1h A62 Built in humidifier low steam production Humidifier A63 Bui...

Страница 27: ...ent stay time compared to the 100 available memory spaces Alarm no 001 represents the first alarm gone off after MAIN data logging enabling Moving the cursor on the chronological number and using the...

Страница 28: ...electing the connected device PASSWORD available on request This menu is divided into these categories CONFIGURATION PARAMETERS CAREL EXV DRIVERS TIMING AND INITIALIZATION 6 1 List of the screens The...

Страница 29: ...T7 C1 Ge T8 C2 Gf INITIALISATION V0 C3 Gg V1 C4 Gh V2 C5 Gi C6 Gj C7 Gk C8 Gl C9 Gm Ca Gn Cb Go Cc CAREL EXV DRIVER F0 Cd F1 Ce F2 Cf F3 Cg F4 Cj F5 Ci F6 Cl F7 Cm F8 Cn F9 Co Fa Cp Fb Co Fc Cp Fd PAR...

Страница 30: ...0 99 9 99 9 C F Recovery temperature probe calibration Ab 0 99 9 99 9 C F Condenser 1 temperature probe calibration Ab 0 99 9 99 9 C F Condenser 2 temperature probe calibration Ab 0 99 9 99 9 C F Manu...

Страница 31: ...3 0 0 0 100 0 C F Temperature dead zone neutral zone P3 0 5 0 0 99 9 C F Proportional bands in Humidification and Dehumidification P4 2 0 2 0 0 0 99 9 RH Maximum production allowed built in humidifier...

Страница 32: ...C6 Fire smoke alarm Fire smoke alarm Water Flood alarm Digital output 7 configuration C7 Light alarm relay Recovery valve Light alarm relay Analog input 2 configuration C8 Pressure circ 1 Pressure ci...

Страница 33: ...Cq Yes No Yes Enable expansion card Cr Off Off On Enable expansion card alarm Cr Off Off On Expansion card alarm delay Cr 120 0 999 seconds Reheating system Cs No Reheating No Reheating Elect Heaters...

Страница 34: ...days Enable Force units by temperature in pLAN network Gm No No Yes Forcing delay for low and high ambient temperature Gm 3 3 0 999 minutes Low room temp diff for forcing units in network Gn 8 0 99 9...

Страница 35: ...0 0 3600 seconds LOP alarm delay Fj 0 0 3600 seconds MOP alarm delay Fj 0 0 3600 seconds TIMES Supply fan start and stop delay T0 10 20 0 999 seconds Integration time for P I temperature control T1 6...

Страница 36: ...uts 8 digital inputs at 24 Vac Vdc 9 digital inputs at 230 Vac or 24 Vac Vdc 10 connector with Vref for 5V power supply to probes and V Term for power supply to display 11 connector for all standard d...

Страница 37: ...llation allowing less energy consumption and a better refrigerating yield Versatile because using the electronic expansion valve implies the possibility to manage refrigerating units with very differe...

Страница 38: ...The maximum available baud rate corresponds to 19 200 programmable by parameter Connection with Rs485 network is executed by connecting the extractible connector to the board displays As for connectio...

Страница 39: ...Gateways devices able to interpret different communication protocols 9 1 Supervisor and bms Advanced Control pCO Local Area Network Max number of units 8 Description Master Slave function the master...

Страница 40: ...anks to the ability of the advanced control pCO to select the protocol used using a gateway that converts the Carel proprietary protocol to the protocol used by the BMS integrating the driver for the...

Страница 41: ...7 analogue 46 analogue 55 analogue 64 Humidity set point analogue 2 analogue 11 analogue 20 analogue 29 analogue 38 analogue 47 analogue 56 analogue 65 2Recovery set point analogue 3 analogue 12 analo...

Страница 42: ...ion allows for the functions listed in the previous paragraph Networks in which boards are connected with the LAN allow selecting the units involved in the Rotation functions thus obtaining a mixed ne...

Страница 43: ...ork functions execution 9 5 1 Critical situations Units in Present Rotation and stand by modes are enabled in any of the following critical situations concerning the running boards one of the boards h...

Страница 44: ...tation based on working hours This type of rotation involves the units with highest and lowest working hours switching the former to stand by mode and the latter to On mode The reference working hours...

Страница 45: ...kByte expandable to 512 MByte Serial Board 16 bits organisation 4 kByte upper limit 400 000 recordings per memory location useful pCO1 cycle with applications of medium complexity 0 5 s Analog inputs...

Страница 46: ......

Страница 47: ......

Страница 48: ...OMMERCIALES AUTRES PAYS Pour respecter ses engagements Lennox s efforce de fournir des informations les plus pr cises N anmoins les sp cifications valeurs et dimensions indiqu es peuvent tre modifi es...

Отзывы: