background image

Page 5

AC13 SERIES

BALL (SHOWN
CLOSED)

SERVICE PORT

CORE

TO INDOOR UNIT

TO OUTDOOR UNIT

TO 

OPEN

 ROTATE STEM

COUNTERCLOCKWISE 90°.

TO 

CLOSE 

ROTATE STEM

CLOCKWISE 90°.

SERVICE PORT

SERVICE PORT CAP

STEM CAP

VALVE
STEM

OPEN TO LINE SET WHEN VALVE IS CLOSED,
TO BOTH LINE SET AND UNIT WHEN VALVE IS
OPEN.

Figure 5. Ball−Type Service Valve

Recovering Refrigerant from Existing
HCFC−22 System

Remove existing HCFC−22 refrigerant using one of the
following methods:

METHOD 1:

Use this method if the existing outdoor unit is not equipped
with manual shut−off valves, and plan on using existing
HCFC−22 refrigerant to flush the system.

NOTE − Use recovery machine instructions for specific
setup requirements.

Perform the following task:

1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean

recovery cylinder and a recovery machine. Use the
instructions provided with the recover machine on how
to setup the connections.

3. Remove all HCFC−22 refrigerant from the existing

system. Check gauges after shutdown to confirm that
the entire system is completely void of refrigerant.

MANIFOLD GAUGES

RECOVERY MACHINE

CLEAN RECOVERY
CYLINDER

OUTDOOR UNIT

Figure 6. Typical Refrigerant Recovery (Method 1)

METHOD 2:

Use this method if the existing outdoor unit is equipped
with manual shut−off valves, and plan on using new
HCFC−22

 

refrigerant to flush the system.

IMPORTANT

: Some system configurations may contain

higher than normal refrigerant charge due to either large
internal coil volumes, and/or long line sets. The following
conditions may cause the compressor to stop functioning:

The following devices could prevent full system charge
recovery into the outdoor unit:

Outdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycled the compressor

OFF

.

Compressor can stop pumping due to tripped internal
pressure relief valve.

Compressor has internal vacuum protection that is
designed to unload the scrolls (compressor stops
pumping) when the pressure ratio meets a certain
value or when the suction pressure is as high as 20
psig. (Compressor suction pressures should never be
allowed to go into a vacuum. Prolonged operation at
low suction pressures will result in overheating of the
scrolls and permanent damage to the scroll tips, drive
bearings and internal seals).

Once the compressor can not pump down to a lower
pressure due to one of the above system conditions, shut
off the suction valve. Turn OFF the main power to unit and
use a recovery machine to recover any refrigerant left in
the indoor coil and line set.

Perform the following task:

1. Start the existing HCFC−22 system in the cooling

mode and close the liquid line valve.

2. Pump as much of the existing HCFC−22 refrigerant

with the compressor back into the outdoor unit until
you have reached the limitations of the outdoor
system. Turn the outdoor unit main power 

OFF 

and

use a recovery machine to remove the remaining
refrigerant in the system.

NOTE − It may be necessary to bypass the low pressure
switches if equipped to ensure complete refrigerant
evacuation.

3. When the low side system pressures reach 0 psig,

close the suction line valve.

4. Check gauges after shutdown to confirm that the

valves are not allowing refrigerant to flow back into the
low side of the system.

Removing Existing Outdoor Unit

Perform the following task at the existing outdoor unit:

Disconnect line set at the service valves.

Disconnect electrical service at the disconnect switch.

Remove old outdoor unit.

Содержание AC13 -018

Страница 1: ...List 1 AC13 Air Conditioner Units 1 Unit Dimensions 2 General Information 3 Recovering Refrigerant from Existing System 3 Removing Existing Outdoor Unit 5 Positioning New Outdoor Unit 6 Removing and I...

Страница 2: ...IT SUPPORT FEET AC13 BASE WITH ELONGATED LEGS H SUCTION LINE CONNECTION LIQUID LINE CONNECTION TOP VIEW RUN CAPACITOR CONTACTOR DISCHARGE LINE LIQUID LINE CONNECTIONS PARTS ARRANGEMENT AC13 A B C D E...

Страница 3: ...Rockwell Harness Scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs for small valves to 25 ft lbs for large valves to prevent refrig...

Страница 4: ...ppropriately sized wrench to turn an additional 1 12 turn clockwise as illustrated in figure 1 Operating Ball Type Service Valve To Access Ball Type Service Port A service port cap protects the servic...

Страница 5: ...system charge recovery into the outdoor unit Outdoor unit s high or low pressure switches if applicable when tripped can cycled the compressor OFF Compressor can stop pumping due to tripped internal...

Страница 6: ...roperty Install the unit as far as possible from the property line When possible do not install the unit directly outside a window Glass has a very high level of sound transmission For proper placemen...

Страница 7: ...unit at a minimum of four inches above the surface of the roof Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters Either redwood or steel supports are re...

Страница 8: ...table an uneven surface ONE BRACKET PER SIDE MIN FOR EXTRA STABILITY 2 BRACKETS PER SIDE 2 FROM EACH CORNER CONCRETE SLAB USE PLASTIC PLASTIC ANCHOR HOLE DRILL 1 4 PLASTIC SLAB NO PLASTIC ANCHOR HOLE...

Страница 9: ...ed to meter flow is 1 4 in diameter and copper INSTALLING LINE SET Line Set Isolation This reference illustrates procedures which ensure proper refrigerant line set isolation Installation of line set...

Страница 10: ...to braze the line set to the new air conditioner unit Figure 18 is provided as a general guide for preparing to braze the line set to the air conditioner unit CAUTION Brazing alloys and flux contain m...

Страница 11: ...r unit s service valves Removing Indoor Unit Metering Device Remove the existing HCFC 22 refrigerant flow control orifice or thermal expansion valve from the indoor coil REPLACEMENT PARTS If replaceme...

Страница 12: ...AC13 ENGINEERING HANDBOOK See the AC13 Engineering Handbook for approved indoor outdoor match ups applicable fixed orifice and TXV kits and application information Figures 23 and 24 illustrates the ty...

Страница 13: ...e provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 3 Attach the stubbed end of the kit val...

Страница 14: ...nly 3 Open the high pressure side of the manifold to allow HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maximum of two ounces 57 g refrigerant or th...

Страница 15: ...er of HCFC 22 refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit 10 Close manifold gauge valves and shut off the HCFC 22 cylinder and...

Страница 16: ...strain relief and to maintain separation of field installed low and high voltage circuits Start Up and Charging Procedures IMPORTANT If unit is equipped with a crankcase heater it should be energized...

Страница 17: ...djust the fan speed See indoor unit instructions to in crease decrease fan speed Changing air flow affects all temperatures recheck temperatures to confirm that the temperature drop and DT are within...

Страница 18: ...c sheet to restrict the airflow through the outdoor coil to achieve pressures from 200 250 psig 1379 1724 kPa Higher pressures are needed to check charge Block equal sections of air intake panels and...

Страница 19: ...refrigerant If refrigerant is added or removed verify charge using the Subcooling Method MORE or LESS 018 024 030 036 042 048 060 TEMP 6 3 3 6 3 3 8 4 4 12 6 7 5 2 8 6 3 3 7 3 8 Temperature of air en...

Страница 20: ...erature VAP _________ 10 Subtract to determine superheat SH VAP _____ SAT ______ SH ______ 11 Record the wet bulb temperature air entering indoor coil WB _______ 12 Record outdoor ambient temperature...

Страница 21: ...73 80 27 175 77 186 77 190 73 201 79 195 78 185 76 193 76 85 29 189 79 200 79 205 75 215 81 209 80 198 77 208 78 90 32 203 81 216 81 221 77 231 82 224 81 213 79 224 80 95 35 218 82 232 82 237 79 247 8...

Страница 22: ...cal power to the unit at the discon nect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable Filter Many indoor units are equipped with reusable foam filters...

Страница 23: ...e to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature PROGRAMMABLE THERMOSTATS Your Lennox system may be con...

Страница 24: ...n Maximum Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure...

Отзывы: