AC13 SERIES

S

Model (AC13) and size (e.g. −060) of unit.

S

Line set diameters for the unit being installed (from
table 2 and total length of installation.

Number of elbows and if there is a rise or drop of the
piping.

Table 2. Refrigerant Line Set

AC13

Valve Field
Connections

Recommended Line Set

Liquid
Line

Suction
Line

Liquid
Line

Suction
Line

L15 Line
Set

−018
−024
−030

3/8" (10
mm)

3/4" (19
mm)

3/8" (10
mm)

3/4" (19
mm)

L15−41
15 ft. − 50
ft. (4.6 m
− 15 m)

−036
−042
−048

3/8" (10
mm)

7/8" (22
mm)

3/8" (10
mm)

7/8 (22
mm)

L15−65
15 ft. − 50
ft. 4.6 m −
15 m)

−060

3/8" (10
mm)

1−1/8"
(29 mm)

3/8" (10
mm)

1−1/8"
(29 mm)

Field
Fabri-
cated

MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET

The RFC1−metering line consisted of a small bore copper
line that ran from condenser to evaporator coil. Refrigerant
was metered into the evaporator by utilizing
temperature/pressure evaporation effects on refrigerant in
the small RFC line. The length and bore of the RFC line
corresponded to the size of cooling unit.

If the AC13 is being used with either a new or existing
indoor coil which is equipped with a liquid line which served
as a metering device (RFCI), the liquid line must be
replaced prior to the installation of the AC13 unit. Typically
a liquid line used to meter flow is 1/4" in diameter and
copper.

INSTALLING LINE SET

Line Set Isolation

This reference illustrates

procedures, which ensure proper refrigerant line set
isolation:

Installation of

 line set on horizontal runs

 is

illustrated in figure 15.

Installation of 

line set on vertical runs

 is illustrated in

figure 16.

Installation of a 

transition from horizontal to

vertical

 is illustrated in figure 17.

METAL

SLEEVE

STRAPPING MATERIAL

(AROUND SUCTION

LINE ONLY)

TAPE OR

WIRE TIE

WIRE TIE
(AROUND
SUCTION LINE
ONLY)

FLOOR JOIST OR

ROOF RAFTER

TAPE OR

WIRE TIE

TO HANG LINE SET FROM JOIST OR
RAFTER, USE EITHER METAL STRAPPING
MATERIAL OR ANCHORED HEAVY NYLON
WIRE TIES.

8 FEET

8 FEET

STRAP THE SUCTION LINE TO
THE JOIST OR RAFTER AT 8 FEET
INTERVALS THEN STRAP THE
LIQUID LINE TO THE SUCTION
LINE.

FLOOR JOIST OR

ROOF RAFTER

Figure 15. Refrigerant Line Set: Installing Horizontal

Runs

NOTE − SIMILAR INSTALLATION
PRACTICES SHOULD BE USED
IF LINE SET IS TO BE INSTALLED
ON EXTERIOR OF OUTSIDE
WALL.

PVC

PIPE

FIBERGLASS

INSULATION

CAULK

OUTSIDE

WALL

SUCTION LINE WRAPPED

WITH ARMAFLEX

LIQUID LINE

IMPORTANT! REFRIGERANT
LINES MUST NOT CONTACT
STRUCTURE.

OUTSIDE WALL

LIQUID LINE

SUCTION LINE

IMPORTANT - REFRIGERANT LINES

MUST NOT CONTACT WALL.

WOOD BLOCK

BETWEEN STUDS

STRAP

SLEEVE

WOOD BLOCK

STRAP

SLEEVE

WIRE TIE

WIRE TIE

WIRE TIE

INSIDE WALL

Figure 16. Refrigerant Line Set: Installing Vertical

Runs (New Construction Shown)

Содержание AC13 -018

Страница 1: ...List 1 AC13 Air Conditioner Units 1 Unit Dimensions 2 General Information 3 Recovering Refrigerant from Existing System 3 Removing Existing Outdoor Unit 5 Positioning New Outdoor Unit 6 Removing and I...

Страница 2: ...IT SUPPORT FEET AC13 BASE WITH ELONGATED LEGS H SUCTION LINE CONNECTION LIQUID LINE CONNECTION TOP VIEW RUN CAPACITOR CONTACTOR DISCHARGE LINE LIQUID LINE CONNECTIONS PARTS ARRANGEMENT AC13 A B C D E...

Страница 3: ...Rockwell Harness Scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs for small valves to 25 ft lbs for large valves to prevent refrig...

Страница 4: ...ppropriately sized wrench to turn an additional 1 12 turn clockwise as illustrated in figure 1 Operating Ball Type Service Valve To Access Ball Type Service Port A service port cap protects the servic...

Страница 5: ...system charge recovery into the outdoor unit Outdoor unit s high or low pressure switches if applicable when tripped can cycled the compressor OFF Compressor can stop pumping due to tripped internal...

Страница 6: ...roperty Install the unit as far as possible from the property line When possible do not install the unit directly outside a window Glass has a very high level of sound transmission For proper placemen...

Страница 7: ...unit at a minimum of four inches above the surface of the roof Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters Either redwood or steel supports are re...

Страница 8: ...table an uneven surface ONE BRACKET PER SIDE MIN FOR EXTRA STABILITY 2 BRACKETS PER SIDE 2 FROM EACH CORNER CONCRETE SLAB USE PLASTIC PLASTIC ANCHOR HOLE DRILL 1 4 PLASTIC SLAB NO PLASTIC ANCHOR HOLE...

Страница 9: ...ed to meter flow is 1 4 in diameter and copper INSTALLING LINE SET Line Set Isolation This reference illustrates procedures which ensure proper refrigerant line set isolation Installation of line set...

Страница 10: ...to braze the line set to the new air conditioner unit Figure 18 is provided as a general guide for preparing to braze the line set to the air conditioner unit CAUTION Brazing alloys and flux contain m...

Страница 11: ...r unit s service valves Removing Indoor Unit Metering Device Remove the existing HCFC 22 refrigerant flow control orifice or thermal expansion valve from the indoor coil REPLACEMENT PARTS If replaceme...

Страница 12: ...AC13 ENGINEERING HANDBOOK See the AC13 Engineering Handbook for approved indoor outdoor match ups applicable fixed orifice and TXV kits and application information Figures 23 and 24 illustrates the ty...

Страница 13: ...e provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 3 Attach the stubbed end of the kit val...

Страница 14: ...nly 3 Open the high pressure side of the manifold to allow HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maximum of two ounces 57 g refrigerant or th...

Страница 15: ...er of HCFC 22 refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit 10 Close manifold gauge valves and shut off the HCFC 22 cylinder and...

Страница 16: ...strain relief and to maintain separation of field installed low and high voltage circuits Start Up and Charging Procedures IMPORTANT If unit is equipped with a crankcase heater it should be energized...

Страница 17: ...djust the fan speed See indoor unit instructions to in crease decrease fan speed Changing air flow affects all temperatures recheck temperatures to confirm that the temperature drop and DT are within...

Страница 18: ...c sheet to restrict the airflow through the outdoor coil to achieve pressures from 200 250 psig 1379 1724 kPa Higher pressures are needed to check charge Block equal sections of air intake panels and...

Страница 19: ...refrigerant If refrigerant is added or removed verify charge using the Subcooling Method MORE or LESS 018 024 030 036 042 048 060 TEMP 6 3 3 6 3 3 8 4 4 12 6 7 5 2 8 6 3 3 7 3 8 Temperature of air en...

Страница 20: ...erature VAP _________ 10 Subtract to determine superheat SH VAP _____ SAT ______ SH ______ 11 Record the wet bulb temperature air entering indoor coil WB _______ 12 Record outdoor ambient temperature...

Страница 21: ...73 80 27 175 77 186 77 190 73 201 79 195 78 185 76 193 76 85 29 189 79 200 79 205 75 215 81 209 80 198 77 208 78 90 32 203 81 216 81 221 77 231 82 224 81 213 79 224 80 95 35 218 82 232 82 237 79 247 8...

Страница 22: ...cal power to the unit at the discon nect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable Filter Many indoor units are equipped with reusable foam filters...

Страница 23: ...e to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature PROGRAMMABLE THERMOSTATS Your Lennox system may be con...

Страница 24: ...n Maximum Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure...

Отзывы: