Page 13

AC13 SERIES

TEFLON

WASHER

LIQUID

LINE

FIXED

ORIFICE

(Uncased Coil Shown)

LIQUID LINE ASSEMBLY

WITH BRASS NUT

LIQUID LINE
ORIFICE HOUSING

Figure 25. Typical Fixed Orifice Installation

TYPICAL TXV INSTALLATION PROCEDURE

The TXV unit can be installed internal or external to the
indoor coil. In applications where an uncased coil is being
installed in a field−provided plenum, install the TXV in a
manner that will provide access for field servicing of the
TXV. Refer to Figure 26 for reference during installation of
TXV unit.

TWO PIECE

PATCH PLATE

(UNCASED COIL

ONLY)

SUCTION
LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER LINE

FITTING (SEE FIGURE 28
FOR FURTHER DETAILS)

SENSING

LINE

EQUALIZER
LINE

TXV

TEFLON
RING

(Uncased Coil Shown)

SENSING BULB INSULATION IS
REQUIRED IF MOUNTED EXTERNAL
TO THE COIL CASING. SEE FIGURE 27
FOR BULB POSITIONING.

STUB END

TEFLON

RING

LIQUID LINE ASSEMBLY

WITH BRASS NUT

DISTRIBUTOR

ASSEMBLY

Figure 26. Typical TXV Installation

To prevent any possibility of water damage, properly
insulate all parts of the TXV assembly that may sweat due
to temperature differences between the valve and its
surrounding ambient temperatures.

1. Remove the field−provided fitting that temporary

reconnected the liquid line to the indoor unit’s
distributor assembly.

2. Install one of the provided Teflon rings around the

stubbed end of the TXV and lightly lubricate the
connector threads and expose surface of the Teflon
ring with refrigerant oil.

3. Attach the stubbed end of the kit valve to the liquid line

assembly. Finger tighten and use an appropriately
sized wrench to turn an additional 1/2 turn clockwise
as illustrated in figure 22, or 20 ft−lb.

4. Place the remaining Teflon ring around the other end

of the TXV. Lightly lubricate connector threads and
expose surface of the Teflon ring with refrigerant oil.

5. Attach the liquid line to the TXV. Finger tighten and use

an appropriately sized wrench to turn an additional 1/2
turn clockwise as illustrated in figure 22, or 20 ft−lb.

6. Attach the suction line sensing bulb in the proper

orientation as illustrated in figure 27 using the clamp
and screws provided.

NOTE − Insulating the sensing bulb once installed may be
required when the bulb location is external to the coil
casing.

ON 7/8" AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O’CLOCK
POSITION. NEVER MOUNT
ON BOTTOM OF LINE.

12

ON LINES SMALLER THAN
7/8", MOUNT SENSING BULB
AT EITHER THE 3 OR 9
O’CLOCK POSITION.

12

BULB

SUCTION LINE

SUCTION LINE

NOTE − Never mount on bottom of line.

BULB

BULB

BULB

Figure 27. TXV Sensing Bulb Installation

7. Remove and discard either the flare seal cap or flare

nut with copper flare seal bonnet from the equalizer
line port on the suction line as illustrated in figure 28.

IMPORTANT

When removing the flare nut, ensure that the copper
flare seal bonnet is removed.

Содержание AC13 -018

Страница 1: ...List 1 AC13 Air Conditioner Units 1 Unit Dimensions 2 General Information 3 Recovering Refrigerant from Existing System 3 Removing Existing Outdoor Unit 5 Positioning New Outdoor Unit 6 Removing and I...

Страница 2: ...IT SUPPORT FEET AC13 BASE WITH ELONGATED LEGS H SUCTION LINE CONNECTION LIQUID LINE CONNECTION TOP VIEW RUN CAPACITOR CONTACTOR DISCHARGE LINE LIQUID LINE CONNECTIONS PARTS ARRANGEMENT AC13 A B C D E...

Страница 3: ...Rockwell Harness Scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs for small valves to 25 ft lbs for large valves to prevent refrig...

Страница 4: ...ppropriately sized wrench to turn an additional 1 12 turn clockwise as illustrated in figure 1 Operating Ball Type Service Valve To Access Ball Type Service Port A service port cap protects the servic...

Страница 5: ...system charge recovery into the outdoor unit Outdoor unit s high or low pressure switches if applicable when tripped can cycled the compressor OFF Compressor can stop pumping due to tripped internal...

Страница 6: ...roperty Install the unit as far as possible from the property line When possible do not install the unit directly outside a window Glass has a very high level of sound transmission For proper placemen...

Страница 7: ...unit at a minimum of four inches above the surface of the roof Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters Either redwood or steel supports are re...

Страница 8: ...table an uneven surface ONE BRACKET PER SIDE MIN FOR EXTRA STABILITY 2 BRACKETS PER SIDE 2 FROM EACH CORNER CONCRETE SLAB USE PLASTIC PLASTIC ANCHOR HOLE DRILL 1 4 PLASTIC SLAB NO PLASTIC ANCHOR HOLE...

Страница 9: ...ed to meter flow is 1 4 in diameter and copper INSTALLING LINE SET Line Set Isolation This reference illustrates procedures which ensure proper refrigerant line set isolation Installation of line set...

Страница 10: ...to braze the line set to the new air conditioner unit Figure 18 is provided as a general guide for preparing to braze the line set to the air conditioner unit CAUTION Brazing alloys and flux contain m...

Страница 11: ...r unit s service valves Removing Indoor Unit Metering Device Remove the existing HCFC 22 refrigerant flow control orifice or thermal expansion valve from the indoor coil REPLACEMENT PARTS If replaceme...

Страница 12: ...AC13 ENGINEERING HANDBOOK See the AC13 Engineering Handbook for approved indoor outdoor match ups applicable fixed orifice and TXV kits and application information Figures 23 and 24 illustrates the ty...

Страница 13: ...e provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 3 Attach the stubbed end of the kit val...

Страница 14: ...nly 3 Open the high pressure side of the manifold to allow HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maximum of two ounces 57 g refrigerant or th...

Страница 15: ...er of HCFC 22 refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit 10 Close manifold gauge valves and shut off the HCFC 22 cylinder and...

Страница 16: ...strain relief and to maintain separation of field installed low and high voltage circuits Start Up and Charging Procedures IMPORTANT If unit is equipped with a crankcase heater it should be energized...

Страница 17: ...djust the fan speed See indoor unit instructions to in crease decrease fan speed Changing air flow affects all temperatures recheck temperatures to confirm that the temperature drop and DT are within...

Страница 18: ...c sheet to restrict the airflow through the outdoor coil to achieve pressures from 200 250 psig 1379 1724 kPa Higher pressures are needed to check charge Block equal sections of air intake panels and...

Страница 19: ...refrigerant If refrigerant is added or removed verify charge using the Subcooling Method MORE or LESS 018 024 030 036 042 048 060 TEMP 6 3 3 6 3 3 8 4 4 12 6 7 5 2 8 6 3 3 7 3 8 Temperature of air en...

Страница 20: ...erature VAP _________ 10 Subtract to determine superheat SH VAP _____ SAT ______ SH ______ 11 Record the wet bulb temperature air entering indoor coil WB _______ 12 Record outdoor ambient temperature...

Страница 21: ...73 80 27 175 77 186 77 190 73 201 79 195 78 185 76 193 76 85 29 189 79 200 79 205 75 215 81 209 80 198 77 208 78 90 32 203 81 216 81 221 77 231 82 224 81 213 79 224 80 95 35 218 82 232 82 237 79 247 8...

Страница 22: ...cal power to the unit at the discon nect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable Filter Many indoor units are equipped with reusable foam filters...

Страница 23: ...e to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature PROGRAMMABLE THERMOSTATS Your Lennox system may be con...

Страница 24: ...n Maximum Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure...

Отзывы: