background image

Page 8

506109−01 10/08

MAINTAIN MINIMUM
PANEL ANGLE (AS
CLOSE TO PARALLEL
WITH THE UNIT AS
POSSIBLE) WHILE
INSTALLING PANEL.

PREFERRED ANGLE
FOR INSTALLATION

ANGLE MAY BE TOO
EXTREME

HOLD DOOR FIRMLY TO THE HINGED
SIDE TO MAINTAIN FULLY−ENGAGED
TABS

Figure 13. Removing/Installing Louvered Panels

(Detail D)

INSTALLING PANEL

Install the louvered panels as follows:

1. Position the panel almost parallel with the unit as

illustrated in figure 13, detail D with the screw side as
close to the unit as possible.

2. With a continuous motion slightly rotate and guide the

lip of top tab inward as illustrated in figure 12, details
A and C; then upward into the top slot of the hinge
corner post.

3. Rotate panel to vertical to fully engage all tabs.
4. Holding the panel’s hinged side firmly in place, close

the right−hand side of the panel, aligning the screw
holes.

5. When panel is correctly positioned and aligned, insert

the screws and tighten.

STABILIZING UNIT ON UNEVEN SURFACES

To help stabilize an outdoor unit, some installations may
require strapping the unit to the pad using brackets and
anchors commonly available in the marketplace.

With unit positioned at installation site, remove two side
louvered panels to expose the unit base pan.

 

Install the

brackets as illustrated in figure 14 using conventional
practices; replace the panels after installation is complete.

IMPORTANT

Unit Stabilizer Bracket Use (field−provided):

Always use stabilizers when unit is raised above the
factory height. (Elevated units could become unsta-
ble in gusty wind conditions).

Stabilizers may be used on factory height units
when mounted on unstable an uneven surface.

ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY,
2 BRACKETS PER SIDE, 2" FROM EACH CORNER.

CONCRETE SLAB − USE PLASTIC
PLASTIC ANCHOR (HOLE DRILL
1/4")PLASTIC SLAB − NO PLASTIC
ANCHOR (HOLE DRILL 1/8")

COIL

BASE PAN

CORNER POST

STABILIZING

BRACKET (18 GAUGE

METAL − 2" WIDTH;

HEIGHT AS REQ’D)

Slab Side Mounting

#10 1/2" LONG SELF−

DRILLING SHEET

METAL SCREWS

#10 1−1/4" LONG

HEX HD SCREW

AND FLATWASHER

MINIMUM 1
PER SIDE

Deck Top
Mounting

STABILIZING BRACKET
(18 GAUGE METAL − 2"
WIDTH; HEIGHT AS
REQ’D); BEND TO FORM
RIGHT ANGLE

FOR EXTRA

STABILITY

Figure 14. Installing Stabilizer Brackets

New or Replacement Line Set

This section provides information on installation or
replacement of existing line set. If line set is not being
installed then proceed to 

Brazing Connections 

on page 10.

If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds. Also, consider the following when
placing and installing a high−efficiency air conditioner.

REFRIGERANT LINE SET

Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor unit
coil (flare or sweat connections). Use Lennox L15 (sweat,
non−flare) series line set, or use field−fabricated refrigerant
lines as listed in table 2.

NOTE − When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, or contact Lennox Technical
Support Product Applications for assistance. To obtain the
correct information from Lennox, be sure to communicate
the following points:

Содержание AC13 -018

Страница 1: ...List 1 AC13 Air Conditioner Units 1 Unit Dimensions 2 General Information 3 Recovering Refrigerant from Existing System 3 Removing Existing Outdoor Unit 5 Positioning New Outdoor Unit 6 Removing and I...

Страница 2: ...IT SUPPORT FEET AC13 BASE WITH ELONGATED LEGS H SUCTION LINE CONNECTION LIQUID LINE CONNECTION TOP VIEW RUN CAPACITOR CONTACTOR DISCHARGE LINE LIQUID LINE CONNECTIONS PARTS ARRANGEMENT AC13 A B C D E...

Страница 3: ...Rockwell Harness Scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs for small valves to 25 ft lbs for large valves to prevent refrig...

Страница 4: ...ppropriately sized wrench to turn an additional 1 12 turn clockwise as illustrated in figure 1 Operating Ball Type Service Valve To Access Ball Type Service Port A service port cap protects the servic...

Страница 5: ...system charge recovery into the outdoor unit Outdoor unit s high or low pressure switches if applicable when tripped can cycled the compressor OFF Compressor can stop pumping due to tripped internal...

Страница 6: ...roperty Install the unit as far as possible from the property line When possible do not install the unit directly outside a window Glass has a very high level of sound transmission For proper placemen...

Страница 7: ...unit at a minimum of four inches above the surface of the roof Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters Either redwood or steel supports are re...

Страница 8: ...table an uneven surface ONE BRACKET PER SIDE MIN FOR EXTRA STABILITY 2 BRACKETS PER SIDE 2 FROM EACH CORNER CONCRETE SLAB USE PLASTIC PLASTIC ANCHOR HOLE DRILL 1 4 PLASTIC SLAB NO PLASTIC ANCHOR HOLE...

Страница 9: ...ed to meter flow is 1 4 in diameter and copper INSTALLING LINE SET Line Set Isolation This reference illustrates procedures which ensure proper refrigerant line set isolation Installation of line set...

Страница 10: ...to braze the line set to the new air conditioner unit Figure 18 is provided as a general guide for preparing to braze the line set to the air conditioner unit CAUTION Brazing alloys and flux contain m...

Страница 11: ...r unit s service valves Removing Indoor Unit Metering Device Remove the existing HCFC 22 refrigerant flow control orifice or thermal expansion valve from the indoor coil REPLACEMENT PARTS If replaceme...

Страница 12: ...AC13 ENGINEERING HANDBOOK See the AC13 Engineering Handbook for approved indoor outdoor match ups applicable fixed orifice and TXV kits and application information Figures 23 and 24 illustrates the ty...

Страница 13: ...e provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 3 Attach the stubbed end of the kit val...

Страница 14: ...nly 3 Open the high pressure side of the manifold to allow HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maximum of two ounces 57 g refrigerant or th...

Страница 15: ...er of HCFC 22 refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit 10 Close manifold gauge valves and shut off the HCFC 22 cylinder and...

Страница 16: ...strain relief and to maintain separation of field installed low and high voltage circuits Start Up and Charging Procedures IMPORTANT If unit is equipped with a crankcase heater it should be energized...

Страница 17: ...djust the fan speed See indoor unit instructions to in crease decrease fan speed Changing air flow affects all temperatures recheck temperatures to confirm that the temperature drop and DT are within...

Страница 18: ...c sheet to restrict the airflow through the outdoor coil to achieve pressures from 200 250 psig 1379 1724 kPa Higher pressures are needed to check charge Block equal sections of air intake panels and...

Страница 19: ...refrigerant If refrigerant is added or removed verify charge using the Subcooling Method MORE or LESS 018 024 030 036 042 048 060 TEMP 6 3 3 6 3 3 8 4 4 12 6 7 5 2 8 6 3 3 7 3 8 Temperature of air en...

Страница 20: ...erature VAP _________ 10 Subtract to determine superheat SH VAP _____ SAT ______ SH ______ 11 Record the wet bulb temperature air entering indoor coil WB _______ 12 Record outdoor ambient temperature...

Страница 21: ...73 80 27 175 77 186 77 190 73 201 79 195 78 185 76 193 76 85 29 189 79 200 79 205 75 215 81 209 80 198 77 208 78 90 32 203 81 216 81 221 77 231 82 224 81 213 79 224 80 95 35 218 82 232 82 237 79 247 8...

Страница 22: ...cal power to the unit at the discon nect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable Filter Many indoor units are equipped with reusable foam filters...

Страница 23: ...e to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature PROGRAMMABLE THERMOSTATS Your Lennox system may be con...

Страница 24: ...n Maximum Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure...

Отзывы: