background image

Page 14

506109−01 10/08

SUCTION LINE

FLARE NUT

COPPER

FLARE SEAL

BONNET

MALE BRASS EQUALIZER

LINE FITTING

FLARE SEAL

CAP

OR

Figure 28. Copper Flare Seal Bonnet Removal

8. Connect the equalizer line from the TXV to the

equalizer suction port on the suction line. Finger
tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated
in figure 22.

Testing for Leaks

After the line set has been connected to the indoor unit and
air conditioner, check the line set connections and indoor
unit for leaks. Use the following procedure to test for leaks:

IMPORTANT

Leak detector must be capable of sensing HFC
refrigerant.

WARNING

Refrigerant can be harmful if it is inhaled.
Refrigerant must be used and recovered
responsibly.

Failure to follow this warning may result in personal
injury or death.

WARNING

Fire, Explosion and Personal Safety
Hazard.

Failure to follow this warning could
result in damage, personal injury or
death.

Never use oxygen to pressurize or
purge refrigeration lines. Oxygen,
when exposed to a spark or open
flame, can cause damage by fire and/
or an explosion, that could result in
personal injury or death.

1. Connect an HCFC−22 manifold gauge set high

pressure hose to the suction valve service port.

(Normally, the high pressure hose is connected to the
liquid line port; however, connecting it to the suction
port better protects the manifold gauge set from high
pressure damage.)

NOTE − Normally, the high pressure hose is connected to
the liquid line port; however, connecting it to the suction
port better protects the manifold gauge set from high
pressure damage.

2. With both manifold valves closed, connect the cylinder

of HCFC−22 refrigerant to the center port of the
manifold gauge set. Open the valve on the HCFC−22
cylinder (suction only).

3. Open the high pressure side of the manifold to allow

HCFC−22 into the line set and indoor unit. Weigh in a
trace amount of HCFC−22.

 [A trace amount is a

maximum of two ounces (57 g) refrigerant or three
pounds (31 kPa) pressure]. 

Close the valve on the

HCFC−22 cylinder and the valve on the high pressure
side of the manifold gauge set. Disconnect the
HCFC−22 cylinder.

4. Connect a cylinder of dry nitrogen with a pressure

regulating valve to the center port of the manifold
gauge set.

5. Adjust dry nitrogen pressure to 150 psig (1034 kPa).

Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.

6. After a few minutes, open one of the service valve

ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector

NOTE − 

Amounts of refrigerant will vary with line lengths.

7. Check all joints for leaks.
8. Purge dry nitrogen and HCFC−22 mixture.
9. Correct any leaks and recheck.

10. After leak testing disconnect gauges from service

ports.

Evacuating the System

WARNING

Danger of Equipment Damage. Avoid deep
vacuum operation. Do not use compressors to
evacuate a system. Extremely low vacuums can
cause internal arcing and compressor failure.
Damage caused by deep vacuum operation will
void warranty.

IMPORTANT

Use a thermocouple or thermistor electronic
vacuum gauge that is calibrated in microns. Use an
instrument capable of accurately measuring down
to 50 microns.

Evacuating the system of non−condensables is critical for
proper operation of the unit. Non−condensables are
defined as any gas that will not condense under
temperatures and pressures present during operation of
an air conditioning system. Non−condensables and water
suction combine with refrigerant to produce substances
that corrode copper piping and compressor parts.

1. Connect manifold gauge set to the service valve ports

as follows:

 

low pressure gauge to 

suction 

line service valve

Содержание AC13 -018

Страница 1: ...List 1 AC13 Air Conditioner Units 1 Unit Dimensions 2 General Information 3 Recovering Refrigerant from Existing System 3 Removing Existing Outdoor Unit 5 Positioning New Outdoor Unit 6 Removing and I...

Страница 2: ...IT SUPPORT FEET AC13 BASE WITH ELONGATED LEGS H SUCTION LINE CONNECTION LIQUID LINE CONNECTION TOP VIEW RUN CAPACITOR CONTACTOR DISCHARGE LINE LIQUID LINE CONNECTIONS PARTS ARRANGEMENT AC13 A B C D E...

Страница 3: ...Rockwell Harness Scale minimum Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs for small valves to 25 ft lbs for large valves to prevent refrig...

Страница 4: ...ppropriately sized wrench to turn an additional 1 12 turn clockwise as illustrated in figure 1 Operating Ball Type Service Valve To Access Ball Type Service Port A service port cap protects the servic...

Страница 5: ...system charge recovery into the outdoor unit Outdoor unit s high or low pressure switches if applicable when tripped can cycled the compressor OFF Compressor can stop pumping due to tripped internal...

Страница 6: ...roperty Install the unit as far as possible from the property line When possible do not install the unit directly outside a window Glass has a very high level of sound transmission For proper placemen...

Страница 7: ...unit at a minimum of four inches above the surface of the roof Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters Either redwood or steel supports are re...

Страница 8: ...table an uneven surface ONE BRACKET PER SIDE MIN FOR EXTRA STABILITY 2 BRACKETS PER SIDE 2 FROM EACH CORNER CONCRETE SLAB USE PLASTIC PLASTIC ANCHOR HOLE DRILL 1 4 PLASTIC SLAB NO PLASTIC ANCHOR HOLE...

Страница 9: ...ed to meter flow is 1 4 in diameter and copper INSTALLING LINE SET Line Set Isolation This reference illustrates procedures which ensure proper refrigerant line set isolation Installation of line set...

Страница 10: ...to braze the line set to the new air conditioner unit Figure 18 is provided as a general guide for preparing to braze the line set to the air conditioner unit CAUTION Brazing alloys and flux contain m...

Страница 11: ...r unit s service valves Removing Indoor Unit Metering Device Remove the existing HCFC 22 refrigerant flow control orifice or thermal expansion valve from the indoor coil REPLACEMENT PARTS If replaceme...

Страница 12: ...AC13 ENGINEERING HANDBOOK See the AC13 Engineering Handbook for approved indoor outdoor match ups applicable fixed orifice and TXV kits and application information Figures 23 and 24 illustrates the ty...

Страница 13: ...e provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil 3 Attach the stubbed end of the kit val...

Страница 14: ...nly 3 Open the high pressure side of the manifold to allow HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maximum of two ounces 57 g refrigerant or th...

Страница 15: ...er of HCFC 22 refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit 10 Close manifold gauge valves and shut off the HCFC 22 cylinder and...

Страница 16: ...strain relief and to maintain separation of field installed low and high voltage circuits Start Up and Charging Procedures IMPORTANT If unit is equipped with a crankcase heater it should be energized...

Страница 17: ...djust the fan speed See indoor unit instructions to in crease decrease fan speed Changing air flow affects all temperatures recheck temperatures to confirm that the temperature drop and DT are within...

Страница 18: ...c sheet to restrict the airflow through the outdoor coil to achieve pressures from 200 250 psig 1379 1724 kPa Higher pressures are needed to check charge Block equal sections of air intake panels and...

Страница 19: ...refrigerant If refrigerant is added or removed verify charge using the Subcooling Method MORE or LESS 018 024 030 036 042 048 060 TEMP 6 3 3 6 3 3 8 4 4 12 6 7 5 2 8 6 3 3 7 3 8 Temperature of air en...

Страница 20: ...erature VAP _________ 10 Subtract to determine superheat SH VAP _____ SAT ______ SH ______ 11 Record the wet bulb temperature air entering indoor coil WB _______ 12 Record outdoor ambient temperature...

Страница 21: ...73 80 27 175 77 186 77 190 73 201 79 195 78 185 76 193 76 85 29 189 79 200 79 205 75 215 81 209 80 198 77 208 78 90 32 203 81 216 81 221 77 231 82 224 81 213 79 224 80 95 35 218 82 232 82 237 79 247 8...

Страница 22: ...cal power to the unit at the discon nect switch before performing any maintenance The unit may have multiple power supplies 3 Reusable Filter Many indoor units are equipped with reusable foam filters...

Страница 23: ...e to cooling mode to maintain predetermined comfort settings Temperature Indicator The temperature indicator displays the actual room temperature PROGRAMMABLE THERMOSTATS Your Lennox system may be con...

Страница 24: ...n Maximum Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure...

Отзывы: