AQUA
4
–AGU-1405-E
- 3 -
3
KEY CUSTOMER BENEFITS
Nominal cooling capacity @ 12/7°C and 35°C air ambient: 50 to 330kW
Nominal heating capacity @ 40/45°C and 7°C air ambient: 50 to 340kW
3.1 The AQUA
4
P: unique concept for thermal comfort with less energy consumption.
The polyvalent heat pump AQUA
4
P units are designed to meet the requirements of
simultaneous and independent
cooling and
heating for air conditioning in the most efficient way. The AQUA
4
P units provide a hot water circuit and a cold water circuit to the entire
building and are more commonly called 4 pipe system.
3.2 The AQUA
4
M: hot water all the year at a lower cost.
The polyvalent heat pump AQUA
4
M units are designed to meet the requirements of cooling
and / or
heating in the most efficient way.
The units have the ability to provide hot water
simultaneously or independently
of cooling and heating needs. The AQUA
4
M units are
generally called 2 pipe units because two hydraulic pipes are connected to the terminal building, the other two hydraulic pipes are
generally dedicated to hot sanitary water.
3.3 Benefits :
Conserving and optimizing energy consumption
-
High energy ratio at part load and full load (EER/COP/ESEER)
-
Simultaneous or independent demands for heating and cooling
-
Constantly balanced heating and cooling needs to obtain maximum Total Efficiency Ratio : TER*
-
100% heat recovery at any conditions
-
Advanced programmable pCO1 with a local control interface PGD1
Secure operating map as standard
-
Winter cooling operation down to -15°C ambient.
-
Heating operation down to -10°C ambient with 45°C outlet water temperature
-
Heat recovery or production of hot water temperature from 25°C to 55°C
-
High ambient operating up to 45°C
Quieter unit
-
-8 dB(A) noise level reduction vs traditional heat pump in standard
-
Jump to -12dB(A)
noise level reduction
with low noise version
-
Innovative hybrid structure of fan blades
-
Unique sound proof cabinet enclosing all components to reduce radiated sound levels
Defrost without impacting comfort
-
Hydrophilic treatment on coil
-
Dynamic control on defrost
-
Circuits defrost completely independently
-
Integrated water tank up to 765 litres
(*) TER :
Total Efficiency Ratio is the total energy efficiency of the units when there is a production of chilled water and hot water
simultaneously. Cold water and hot water are valuated to the total power consumption of the unit: TER = (cooling ca recovered
heating capacity) / total power consumption. Energy ratio TER of polyvalent heat pumps are significantly higher than the standard EER
and COP demonstrating considerable energy savings during inter-season periods (version P) or domestic hot water production (M
version).
Cooling
Heating
Circuit 1
Circuit 2
C Heating
Circuit 1
Circuit 2
Cooling
Circuit 1
Heating
Hot water
production (DHW)
(DHW)
C Hot
water (DHW)
H Hot
water (DHW)
Circuit 1
Circuit 2
Circuit 2
Circuit 2
Circuit 1
Circuit 1
Содержание AAH041
Страница 1: ...lennoxemeia com AQUA4 AAH APPLICATION GUIDE Polyvalent air cooled heat pump 50 330 kW AQUA4 AGU 1405 E...
Страница 2: ......
Страница 13: ...AQUA4 AGU 1405 E 11 Example of 2 pipe installation for Hotel and Hospital...
Страница 20: ...AQUA4 AGU 1405 E 18 Nb of compressor 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 4...
Страница 45: ...AQUA4 AGU 1405 E 43 AAH PS PL MS ML 094 and 104 Box F3 AAH PS PL MS ML 124 144 164 and 194 Box F4...
Страница 46: ...AQUA4 AGU 1405 E 44 AAH PS PL MS ML 214 and 244 Box F5 AAH PS PL MS ML 274 294 and 324 Box F6...