AQUA
4
–AGU-1405-E
- 22 -
Power supply
400 / 3+N / 50
Maximum absorbed current (FLA) [without options]
A
81
87
96
105
126
148
Start up current (LRA) [without options]
A
194
198
220
222
241
307
Start up current with soft starter [without options]
A
126
129
143
145
157
200
Number of fans
8
8
6
6
6
6
Air flow
m3/h
41340
41340
72700
72700
67672
67672
Absorbed power of fans
kW
2.3
2.3
6.3
6.3
6.3
6.3
Absorbed current of fans
A
8.8
8.8
15
15
15
15
Sound power level Lw
db(A)
81
81
81
82
83
86
Sound pressure level Lp @ 10 m Q=2
db(A)
53
53
53
54
55
58
Compressors / Circuits
4/2
4/2
4/2
4/2
4/2
4/2
Water tank volume (option)
l
340
600
Dimensions [LxWxH]
mm
3610 x 1183 x 1679 3610 x 1654 x 1846
Weight [without options]
kg
1190
1210
1530
1550
1690
1710