AQUA
4
–AGU-1405-E
- 21 -
Table 2 – General data of AQUA
4
M and AQUA
4
P standard S version from AQUA
4
094 to AQUA
4
194 in nominal conditions :
Unit M (2 pipe) and P (4 pipe) version S
AAH094 AAH104 AAH124 AAH144 AAH164 AAH194
Cooling at 12/7°C with air ambient at 35°C
Cooling capacity
kW
98.4
107.5
129.5
142
161.6
180.2
Total absorbed power
kW
32.3
36.5
43.4
48.4
54.8
66.2
EER
3.05
2.95
2.98
2.93
2.95
2.72
ESEER
4.47
4.55
3.98
4.07
4.21
4.32
Water flow
l/h
16899
18461
22241
24394
27745
30947
Total pressure drop
kPa
35
40
42
50
46
41
Available pressure head - Pump(s) LP single or
normal/backup switching (option)
kPa
124
114
102
145
140
138
Available pressure head - Pump(s) HP single or
normal/backup switching (option)
kPa
182
172
182
166
161
260
Available pressure head - Twin pumps LP parallel
operating (option)
kPa
148
138
128
114
110
134
Available pressure head - Twin pumps HP parallel
operating (option)
kPa
182
173
188
177
179
198
Heating at 40/45°C with air ambient at 7°C
Heating capacity
kW
102.9
112.8
135.7
150.3
169.8
195.6
Total absorbed power
kW
31.9
35.5
44.6
49.6
55.4
63.7
COP
3.23
3.18
3.04
3.03
3.06
3.07
Water flow
l/h
17885
19611
23577
26121
29508
33988
Total pressure drop
kPa
39
46
47
58
53
49
Available pressure head - Pump(s) LP single or
normal/backup switching (option)
kPa
110
98
85
122
120
108
Available pressure head - Pump(s) HP single or
normal/backup switching (option)
kPa
168
156
163
143
141
229
Available pressure head - Twin pumps LP parallel
operating (option)
kPa
135
123
111
92
92
118
Available pressure head - Twin pumps HP parallel
operating (option)
kPa
169
158
174
160
165
181
Cooling 12/7°C and Heating at 40/45°C
Cooling capacity
kW
97.8
107.9
125.8
139
160.3
184.2
Heating capacity
kW
126.5
140.1
162.7
180.4
207
239.1
Total absorbed power
kW
30.2
33.9
38.8
43.5
49.2
57.8
TER
7.43
7.32
7.44
7.34
7.47
7.32
Water flow of cold circuit
l/h
16798
18522
21605
23879
27522
31637
Water flow of hot circuit
l/h
21991
24343
28272
31347
35974
41557
Available pressure head - Pump(s) LP single or
normal/backup switching (option) - cold circuit
kPa
124
113
106
149
141
132
Available pressure head - Pump(s) HP single or
normal/backup switching (option) - cold circuit
kPa
183
172
186
170
163
255
Available pressure head - Twin pumps LP parallel
operating (option) - cold circuit
kPa
148
138
132
117
112
131
Available pressure head - Twin pumps HP parallel
operating (option) - cold circuit
kPa
183
173
191
180
180
195
Available pressure head - Pump(s) LP single or
normal/backup switching (option) - hot circuit
kPa
87
68
58
89
79
46
Available pressure head - Pump(s) HP single or
normal/backup switching (option) - hot circuit
kPa
145
126
137
110
100
167
Available pressure head - Twin pumps LP parallel
operating (option) - hot circuit
kPa
95
87
62
55
86
95
Available pressure head - Twin pumps HP parallel
operating (option) - hot circuit
kPa
130
156
137
138
150
130
Содержание AAH041
Страница 1: ...lennoxemeia com AQUA4 AAH APPLICATION GUIDE Polyvalent air cooled heat pump 50 330 kW AQUA4 AGU 1405 E...
Страница 2: ......
Страница 13: ...AQUA4 AGU 1405 E 11 Example of 2 pipe installation for Hotel and Hospital...
Страница 20: ...AQUA4 AGU 1405 E 18 Nb of compressor 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 4...
Страница 45: ...AQUA4 AGU 1405 E 43 AAH PS PL MS ML 094 and 104 Box F3 AAH PS PL MS ML 124 144 164 and 194 Box F4...
Страница 46: ...AQUA4 AGU 1405 E 44 AAH PS PL MS ML 214 and 244 Box F5 AAH PS PL MS ML 274 294 and 324 Box F6...